Plan Review Details - Permit 04010913
Plan Review Stops For Permit 04010913
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-07-12 Cont ID  
Sent By rmcdouga Date 2004-03-15 Time 08:41 Rev Time 0.25
Received By mjacobs Date 2004-07-12 Time 12:30 Sent To  
Notes
2004-07-12 00:00:00WINDOW SUBMITTALS OK
2004-03-15 00:00:00BUILDING PROVISO
  
 SUBMIT A REVISED INSTALLATION SCHEDULE
 FOR THE STORM PANELS FOR APPROVAL PRIOR
 TO INSTALLATION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-02-19 Cont ID  
Sent By btrobaug Date 2004-03-05 Time 17:23 Rev Time 2.50
Received By rmcdouga Date 2004-02-19 Time 09:23 Sent To  
Notes
2004-02-19 00:00:00DENIED
  
 1) THE ENERGY CALCULATION FORM DOES NOT
 INCLUDE THE CEILING AREA OF THE COFFERED
 CEILINGS. PLEASE CORRECT. SEE FBC
 CHAPTER 13 SECTION 604.
  
 2) SPECIFY ON THE PLANS THAT THE DOOR
 FROM THE GARAGE TO THE CONDITIONED AREA
 OF THE STRUCTURE IS INSULATED OR SOLID
 CORE AS REQUIRED BY FBC CHAPTER 13 SECT.
 603.
  
 3) REVISE SGD BUCK DETAIL ON A4. THE
 NOTE SHOULD READ TO FASTEN THROUGH THE
 1X BUCK. FBC 1707.4.4.2.
  
 4) THE RIGHT ELEVATION ON A3 HAS THE
 WRONG MASONRY OPENING SIZE LISTED FOR
 THE OPENING ON THE LEFT. IT IS LISTED AS
 32"X 48" ON THE FLOOR PLAN ON A2. PLEASE
 CORRECT.
  
 5) CORRECT THE OPENING SIZE FOR #3 ON
 THE STORM PANEL INSTALLATION SCHEDULE.
 REVISE THE HEIGHT FOR #13 ON THE SCHED.
 THE HEIGHT LISTED ON THE PLANS EXCEEDS
 80".
  
 6) THE MASONRY OPENING SIZES FOR THE
 FIXED GLASS WINDOWS ON THE LEFT
 ELEVATION ON A4 FOR WINDOWS #12 & #13
 ARE INNCORRECT. THEY SHOULD BE 64" IN
 HEIGHT. PLEASE CORRECT.
  
 7) SUBMIT THE ENGINEERED DRAWINGS FOR
 THE 16'X8' GARAGE DOOR. THE ONE
 SUBMITTED IS FOR A MAXIMUM 9' WIDTH.
  
 8) SUBMIT PRODUCT APPROVALS FOR A 16'
 LONG MULLION BETWEEN THE 16' WIDE SGD
 AND THE TRANSOM AT THE GREAT ROOM. THE
 ONE SUBMITTED ONLY LISTS UP TO 12' MULL
 LENGTH. OR SPECIFY A LINTEL, STRUCTURAL
 STEEL HEADER OR OTHER DESIGN.
  
 9)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2004-10-12 Cont ID  
Sent By btrobaug Date 2004-10-12 Time 10:43 Rev Time 0.50
Received By btrobaug Date 2004-10-12 Time 09:17 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2004-09-21 Cont ID  
Sent By csiegber Date 2004-10-04 Time 13:01 Rev Time 0.50
Received By btrobaug Date 2004-09-21 Time 08:53 Sent To  
Notes
2004-09-21 00:00:00 
 PLEASE SHOW THE PANEL LOCATIONS ON THE
 PLAN.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-03-05 Cont ID  
Sent By csiegber Date 2004-09-14 Time 09:25 Rev Time 0.50
Received By btrobaug Date 2004-03-05 Time 17:10 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-01-30 Cont ID  
Sent By csiegber Date 2004-03-04 Time 13:48 Rev Time 0.50
Received By btrobaug Date 2004-01-30 Time 07:25 Sent To M
Notes
2004-01-30 00:00:00PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} AN EQUIPMENT GROUNDING CONDUCTOR IS
 REQUIRED FROM THE DISCONNECT TO THE
 PANEL PER 250.122.
  
 2} THE RECEPTACLE PLACEMENT IN THE
 MASTER BATH DOES NOT COMPLY WITH THE 3'
 REQUIREMENT OF ARTICLE 210.52(D).
  
 3} A SMOKE DETECTOR MUST BE ADDED
 OUTSIDE THE DOORS TO THE MASTER SUITE
 TO COMPLY WITH 8-1.4.1.6.2. NFPA-72.
  
 4} A SMOKE DETECTOR MUST BE ADDED
 OUTSIDE THE DOOR OF THE "DEN/BEDROOM
 3", ALSO FOR COMPLIANCE WITH
 8-1.4.1.6.2. NFPA-72.
  
 5} ANOTHER RECEPTACLE IS REQUIRED IN
 BATH #2 TO COMPLY WITH 210.52(D).
  
 6} NOTE THAT THE ARCHITECTS
 SIGNATURE IS REQUIRED ON HIS/HER SEAL
 PER 61G116.003.INITIALS ARE NOT
 ACCEPTABLE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  
  
  
  
  
  
  
  
  
  
  
  
  
 2)NOTE: PLEASE SEE BLDG PLAN REVIEW
 NOTES. PLEASE CORRELATE PLANS/PAPERWORK
 FOR COTTAGES.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
 2)NOTE: PLEASE SEE BLDG PLAN REVIEW
 NOTES. PLEASE CORRELATE PLANS/PAPERWORK
 FOR COTTAGES.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-10-04 Cont ID  
Sent By csiegber Date 2004-10-04 Time 13:01 Rev Time 0.00
Received By csiegber Date 2004-10-04 Time 13:01 Sent To E
Notes
2004-10-04 00:00:00TO BT DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-09-14 Cont ID  
Sent By csiegber Date 2004-09-14 Time 09:25 Rev Time 0.00
Received By csiegber Date 2004-09-14 Time 09:25 Sent To E
Notes
2004-09-14 00:00:00TO BT DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-03-04 Cont ID  
Sent By csiegber Date 2004-03-04 Time 13:48 Rev Time 0.00
Received By csiegber Date 2004-03-04 Time 13:48 Sent To E
Notes
2004-03-04 00:00:00TO BT DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-02-19 Cont ID  
Sent By mmclean Date 2004-01-22 Time 16:28 Rev Time 0.00
Received By rmcdouga Date 2004-01-21 Time 14:03 Sent To  
Notes
2004-01-23 00:00:00TO SFD RACK/E
2004-01-21 00:00:00TO Z

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-01-30 Cont ID  
Sent By btrobaug Date 2004-01-30 Time 11:33 Rev Time 0.33
Received By pkrauss Date 2004-01-30 Time 15:48 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-03-15 Cont ID  
Sent By rmcdouga Date 2004-03-15 Time 09:11 Rev Time 0.00
Received By rmcdouga Date 2004-03-15 Time 09:11 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2004-02-03 Cont ID  
Sent By pkrauss Date 2004-01-30 Time 15:49 Rev Time 0.33
Received By jleech Date 2004-02-03 Time 14:38 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2004-01-22 Cont ID  
Sent By mmclean Date 2004-01-22 Time 16:28 Rev Time 0.00
Received By mmclean Date 2004-01-22 Time 16:28 Sent To I
Notes
***NONE***