Plan Review Details - Permit 04010909
Plan Review Stops For Permit 04010909
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2005-03-08 Cont ID  
Sent By jwitmer Date 2005-03-08 Time 14:24 Rev Time 1.55
Received By jwitmer Date 2005-03-08 Time 14:24 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2004-10-19 Cont ID  
Sent By jwitmer Date 2004-10-19 Time 15:18 Rev Time 0.55
Received By jwitmer Date 2004-10-19 Time 15:18 Sent To  
Notes
2004-10-19 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04010909
 ADD: 4847 FRED GLADSTONE DR
 CONT: THE WHITING-TURNER CONT CO
 TEL: (561)718-2367
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 3RD REVIEW
 ACTION: DENIED
  
 1) COMMENT# 1 FROM PREVIOUS REVIEW,
 PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
 THE SOILS REPORTS PROVIDED ARE NOT
 SIGNED NOR SEALED. ORIGINAL SIGNATURES
 REQUIRED, NOT STAMPED!
  
 2)COMMENT#4 FROM THE PREVIOUS REVIEW
 DELT WITH THE FL BUILDING CODE COMPON-
 ENTS AND CLADDING REQUIRING PRODUCT TEST
 ING REPORTS, MISSING REPORTS ARE THE
 FOLLOWING:
 A) WINDOWS FIXED AND SLIDERS, THE FL
 APPROVAL SHEETS WERE SUBMITTED BUT THE
 PRODUCT TESTING REPORTS AND TECHNICAL
 DRAWINGS ARE MISSING.
 B)SWING EXTERIOR DOORS-YKK AP AMERICA,
 NON-IMPACT HIGHLIGHTED, NO REPORT NOR
 TECHNICAL DRAWINGS.WILL REQUIRE SHUTTERS
 C) ROOFING ASSEMBLIES- ALTUSA ROOF TILE
 SUBMITTED REPORT METRO-DADE REPORT, BUT
 THE FL APPROVAL IS FOR A SBCCI REPORT.
 D) STORM SHUTTERS- NO INFORMATION WAS
 SUBMITTED.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-06-25 Cont ID  
Sent By jwitmer Date 2004-06-25 Time 13:57 Rev Time 1.50
Received By jwitmer Date 2004-06-25 Time 13:57 Sent To  
Notes
2004-06-25 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04010909
 ADD: 4832 N HAVERHILL RD
 CONT: THE WHITING-TURNER CO
 TEL: (561)478-1881
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 2ND REVIEW
 ACTION: DENIED
  
 1) COMMENT #2 FROM PREVIOUS REVIEW,
 FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 WHERE THE BEARING CAPACITY OF THE SOIL
 IS NOT DEFINITLY KNOWN OR IS IN QUESTION
 THE BUILDING OFFICIAL MAY REQUIRE EXPLOR
 ATIONS, TEST OR OTHER ADEQUATE PROOF AS
 TO THE PERMISSIBLE SAFE BEARING
 CAPACITY. REQUIRED TEST AND RECOMMENDA-
 TIONS SUBMITTED TO VERIFY BEARING CAPA-
 CITY SHALL BE CERTIFIED BY A GEOTECH-
 NICALREPORT FROM A DESIGN PROFESSIONAL
 PROPERLY LICENSED IN THE STATE OF
 FLORIDA.
 THE RESPONCE IS FOR DENSITY.
 WE ARE NOT TALKING ABOUT DENSITY WHERE
 SOILS ARE ADDED AND A DENSITY REPORT IS
 REQUIRED. THIS AREA HAS QUESTIONABLE
 SOILS, BORINGS TO THE DEPTH OF 15' ARE
 TO MAKE SURE THE MINIMUM SAFE ALLOWABLE
 LOADS SPECIFIED ARE MET!!!!
  
 2) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) SWING EXTERIOR DOORS
 B) WINDOWS FIXED OR SLIDING
 C) ROOFING ASSEMBLIES
 D) STORM SHUTTERS
 E) TRUSS ANCHORS
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
 NO PRODUCT APPROVALS HAVE BEEN
 SUBMITTED!!!!!!!!!!!!!!!!!!!!!!!!!!!!
  
 3) COMMENT# 5 FROM PREVIOUS RREVIEW,
 2304.5 CLEARENCE BETWEEN WOOD SIDING
 & EARTH ON THE EXTERIOR OF A BUILDING
 SHALL NOT BE LESS THAN 6" EXCEPT WHERE
 SIDING, SHEATHING AND FRAME WALL ARE OF
 APPROVED DURABLE WOOD OR APPROVED PRE-
 SERVATIVE TREAATED WOOD.
 THE RESPONCE"IS THERE IS NO EXPOSED
 WOOD ON THE BUILDING."
 THE CODE CLEARLY STATES THAT EVEN FOR
 "SHEATHING" WHICH IS COVERED BY ANOTHER
 MATERIAL WILL HAVE A 6" INSPECTION AREA
 FOR TERMITES.
  
 4) COMMENT# 7 FROM PREVIOUS REVIEW,
 PROVIDE WINDOW AND DOOR BUCK DETAILS
 AND ATTACHMENT SCHEDULE?
 1707.4.4.1 ANCHOR REQUIREMENTS:
 WINDOW & DOOR ASSEMBLIES SHALL BE ANCHOR
 ED IN ACCORDANCE WITH THE PUBLISHED
 MANUFACTURER'S RECOMMENDATIONS TO
 ACHIEVE THEDESIGN PRESSURE SPECIFIED.
 SUBSTITUTE ANCHORING SYSTEM USED FOR
 THE SUBSTRATE NOT SPECIFIED BY THE
 FENESTRATION MANUFACTURER SHALL PROVIDE
 EQUAL OR GREATER ANCHORING AS DEMONSTRA-
 TED BY ACCEPTED ENGINEERING PRACTICES.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-03-02 Cont ID  
Sent By jwitmer Date 2004-03-02 Time 16:21 Rev Time 1.00
Received By jwitmer Date 2004-03-02 Time 16:14 Sent To  
Notes
2004-03-02 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04010909
 ADD: 4847 FRED GLADSTONE DR
 CONT: THE WHITING-TURNER
 TEL: (561)718-2367
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 WHERE THE BEARING CAPACITY OF THE SOIL I
 S NOT DEFINITEY KNOWN, OR IS IN QUESTION
 THE BUILDING OFFICIAL MAY REQUIRE EXPLOR
 ATIONS, TEST OR OTHER ADEQUATE PROOF AS
 TO THE PERMISSIBLE SAFE BEARING
 CAPACITY. REQUIRED TEST AND RECOMMENDA-
 TIONS SUBMITTED TO VERIFY BEARING CAPA-
 CITY SHALL BE CERTIFIED BY A GEOTECH-
 NICALREPORT FROM A DESIGN PROFESSIONAL P
 ROPERLY LICENSED IN THE STATE OF
 FLORIDA.
  
 3) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) WINDOWS FIXED OR SLIDERS
 B) SWING EXTERIOR DOORS
 C) ROOFING ASSEMBLIES
 D) STORM SHUTTERS
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 4) PROVIDE THE SCREW SIZE AND SPACING
 FOR THE WALL AND ROOF SHEATHING?
  
 5) 2304.5 CLEARENCE BETWEEN WOOD SIDING
 & EARTH ON THE EXTERIOR OF A BUILDING
 SHALL NOT BE LESS THAN 6" EXCEPT WHERE
 SIDING, SHEATHING AND FRAME WALL ARE OF
 APPROVED DURABLE WOOD OR APPROVED PRE-
 SERVATIVE TREAATED WOOD.
  
 6) PROVIDE ADD INFORMATION AS TO GUAGE
 OF EXTERIOR WALL STUDS?
  
 7) PROVIDE WINDOW AND DOOR BUCK DETAILS
 AND ATTACHMENT SCHEDULE?
  
 8)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2004-01-28 Cont ID  
Sent By dpalmer Date 2004-01-28 Time 13:09 Rev Time 0.50
Received By dpalmer Date 2004-01-28 Time 13:09 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2004-01-29 Cont ID  
Sent By mamini Date 2004-01-29 Time 09:26 Rev Time 0.50
Received By mamini Date 2004-01-29 Time 09:26 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-06-22 Cont ID  
Sent By mcarsill Date 2004-06-22 Time 11:02 Rev Time 0.00
Received By mcarsill Date 2004-06-22 Time 11:02 Sent To  
Notes
2004-06-22 00:00:001) A KNOX BOX APPLICATION WILL BE
 DROPPED OFF TO THE GENERAL CONTRACTOR
 WORKING ON THE SITE. THIS DEPARTMENT
 WILL NOT RELY ON A ROVING GUARD TO
 PROVIDE ACCESS TO THE CAMPUS VIA THE
 GUARDHOUSE IN THE EVENT OF AN
 EMERGENCY AFTER NORMAL BUSINESS HOURS.
 THE PERMIT RESPONSE BY GREGORY GALFORD
 IS NOT CORRECT.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-01-29 Cont ID  
Sent By mcarsill Date 2004-01-29 Time 07:21 Rev Time 0.00
Received By mcarsill Date 2004-01-29 Time 07:21 Sent To  
Notes
2004-01-29 00:00:001) PROPOSED GUARDHOUSE SHALL NOT
 INTERFERE WITH FIRE AND PARAMEDICAL
 ACCESS.
  
 2) GUARDHOUSE SHALL NOT INTERFERE
 WITH ANY REQUIRED VERTICAL OR
 HORIZONTAL WIDTHS.
  
 3) WILL THE GUARDHOUSE BE STAFFED FULL
 OR PART TIME.
  
 4) IF THE GUARDHOUSE IS NOT STAFFED
 FULL TIME HOW DOES FIRE RESCUE ENTER
 THROUGH THE GATES.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-03-04 Cont ID  
Sent By adarroug Date 2005-03-04 Time 16:39 Rev Time 0.00
Received By adarroug Date 2005-03-04 Time 16:39 Sent To B
Notes
2005-03-04 00:00:00TO JWITMER DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-10-15 Cont ID  
Sent By csiegber Date 2004-10-15 Time 10:04 Rev Time 0.00
Received By csiegber Date 2004-10-15 Time 10:04 Sent To  
Notes
2004-10-15 00:00:00TO COMM BD#23

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-03-02 Cont ID  
Sent By mmclean Date 2004-07-08 Time 16:55 Rev Time 0.00
Received By csiegber Date 2004-01-21 Time 11:57 Sent To  
Notes
2004-01-27 00:00:00TO COMM BD#12
2004-01-21 00:00:00TO Z

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-01-28 Cont ID  
Sent By pkrauss Date 2004-01-28 Time 16:13 Rev Time 0.25
Received By pkrauss Date 2004-01-28 Time 16:13 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2004-02-03 Cont ID  
Sent By kstevens Date 2004-02-03 Time 09:05 Rev Time 0.25
Received By kstevens Date 2004-02-03 Time 09:05 Sent To  
Notes
2004-02-03 00:00:00NO PLUMBING PLANS SUBMITTED - NO PLUMB-
 ING REQUIRED PER EXCEPTION TO SECTION
 403.4

Review Stop Z ZONING
Rev No 3 Status P Date 2004-10-26 Cont ID  
Sent By mmclean Date 2004-10-26 Time 10:38 Rev Time 0.00
Received By mmclean Date 2004-10-26 Time 10:38 Sent To  
Notes
2004-10-26 00:00:00JOSH LONG, PLANNER 822-1449

Review Stop Z ZONING
Rev No 2 Status F Date 2004-07-08 Cont ID  
Sent By mmclean Date 2004-07-08 Time 16:55 Rev Time 0.00
Received By mmclean Date 2004-07-08 Time 16:54 Sent To I
Notes
2004-07-08 00:00:00DENIED, BY JOSH LONG, PLANNER 659-8031
 NEED MINOR PD AMENDMENT

Review Stop Z ZONING
Rev No 1 Status F Date 2004-01-23 Cont ID  
Sent By mmclean Date 2004-01-23 Time 10:26 Rev Time 0.00
Received By mmclean Date 2004-01-23 Time 10:25 Sent To I
Notes
2004-01-23 00:00:00DENIED, NEED A MINOR PD AMENDMENT PER
 JOSH LONG PLANNER 659-8031 MM