| Plan Review Stops For Permit 04010887 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
N |
Date |
2004-06-17 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2004-06-17 |
Time |
11:07 |
Rev Time |
0.25 |
| Received By |
shill |
Date |
2004-06-17 |
Time |
11:07 |
Sent To |
|
|
| Notes |
| 2004-06-17 00:00:00 | MEP REVISION DATED 6/7/04 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2004-06-04 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2004-06-04 |
Time |
08:20 |
Rev Time |
0.50 |
| Received By |
shill |
Date |
2004-06-04 |
Time |
08:20 |
Sent To |
|
|
| Notes |
| 2004-06-04 00:00:00 | CHILLER SLAB DETAILS, WOOD FURRING | | | LETTER |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2004-04-14 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2004-05-26 |
Time |
09:25 |
Rev Time |
3.00 |
| Received By |
shill |
Date |
2004-04-13 |
Time |
10:57 |
Sent To |
|
|
| Notes |
| 2004-04-14 00:00:00 | CHANGES MADE BY ARCH & ENGINEER | | | SITE SPECIFIC SUBMITTED | | 2004-04-13 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | [email protected] | | | | | | 1.)SHEET E1 HAS THE PRINTED NAME AND | | | LICENSE NUMBER OF BETANCOURT, PE BUT | | | HAS BEEN SEALED AND SIGNED BY ME GARCIA | | | PE. | | | | | | 2.)SHEETS P1-P6 ON ONE SET ARE SIGNED | | | BUT NOT SEALED. | | | | | | 3.)THE SHEETS SEALED BY ENGINEERS ARE | | | REQUIRED TO HAVE THE ENGINEER'S TITLE | | | BLOCK, FAC61G15-23.002.IF GARTEK | | | ENGINEERING CORP IS ON THE TITLE BLOCK, | | | THE CA NUMBER IS TO BE ON EACH SHEET | | | AS WELL AS THE OTHER REQUIRED | | | INFORMATION. | | | | | | 4.)SEE PREVIOUS LIST, FLORIDA STATE, | | | LOCAL OR SITE SPECIFIC PRODUCT | | | APPROVALS REQUIRED IN ADDITION TO | | | TEST REPORTS.WWW.FLORIDABUILDING.ORG | | | I HAVE EMAILED THE MANUFACTURER AT | | | [email protected] REQUESTING A | | | SITE SPECIFIC.IF THIS IS NOT PROVIDED | | | BEFORE PERMIT ISSUANCE, A SEPARATE | | | PERMIT WILL BE REQUIRED FOR THESE | | | ITEMS PURSUANT TO RULE 9B-72FAC. | | | | | | 5.)PROVIDE DESIGN PRESSURES FOR THE | | | STOREFRONT GLASS. | | | | | | ***NO RESUB FEE FOR BUILDING COMMENTS*** |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2004-03-31 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2004-03-29 |
Time |
17:21 |
Rev Time |
3.00 |
| Received By |
shill |
Date |
2004-03-29 |
Time |
17:21 |
Sent To |
|
|
| Notes |
| 2004-03-29 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | [email protected] | | | | | | 1.)TO EXPEDITE PLAN REVIEW, ALL | | | CHANGES TO THE PLAN ARE TO BE CLEARLY | | | MARKED.FOR INSTANCE, SHEET LS1, THE | | | ROOM DESIGNATIONS WERE CHANGED FROM | | | "CLASSROOM" TO "ROOM".THIS WAS DONE ON | | | SEVERAL SHEETS, BUT NONE WERE MARKED. | | | | | | 2.)NOTE:DAYCARE (D) OCCUPANCY AS | | | PER LETTER FROM ALLAN DEUPP, MANAGER, | | | PROCUREMENT & PROJECT IMPLEMENTATION | | | GROUP, PALM BEACH COUNTY. | | | | | | 3.)FBC423.21.4, TOILET FACILITIES | | | SHALL HAVE A 6' IMPERVIOUS WAINSCOT. | | | | | | 4.)PROVIDE TEST REPORTS AND FLORIDA | | | STATEWIDE, LOCAL OR SITE SPECIFIC | | | PRODUCT APPROVALS FOR THE EXTERIOR DOORS | | | AND STOREFRONT GLASS. | | | WWW.FLORIDABUILDING.ORG. | | | | | | 5.)THE PRINTED NAME AND LICENSE | | | NUMBER OF THE PERSON SEALING THE PLAN | | | IS TO BE PRINTED ON EACH SHEET, FAC | | | 61G1-16.003.THE SEAL ON SOME SHEETS | | | IS ILLEGIBLE. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2004-02-26 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2004-02-26 |
Time |
06:37 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
2004-02-26 |
Time |
06:37 |
Sent To |
|
|
| Notes |
| 2004-02-26 00:00:00 | PLAN REVIEW ONLY, NOT A PERMIT | | | APPLICATION. | | | | | | SHEET LS1 DECLARES BUILDING TYPE AS "IV | | | UNPROTECTED 1 HOUR SPRINKLERED."PLEASE | | | CLARIFY. | | | | | | SHEET LS1 DECLARES OCCUPANCY AS DAY | | | CARE.IT APPEARS THE INTENDED OCCUPANCY | | | IS PRIMARILY PRE-SCHOOL, IE; | | | EDUCATIONAL.SEE FBC 313.1. | | | | | | FBC TABLE 704.1 REQUIRES A 2 HR FIRE | | | RATED MIXED OCCUPANCY SEPARATION FOR | | | GROUP E OCCUPANCY.PLEASE REVISE AS | | | NECESSARY. | | | | | | SHEET A2, DETAILS 1/A2, 2/A2 AND 3/A2. | | | SHOW SPECIFIC CONNECTION METHODS FOR THE | | | FRAMING TO THE EXISTING STRUCTURE.SEE | | | FBC 104.2.1. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
P |
Date |
2004-07-09 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-07-09 |
Time |
11:41 |
Rev Time |
0.33 |
| Received By |
dpalmer |
Date |
2004-07-09 |
Time |
11:41 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
F |
Date |
2004-06-23 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-06-23 |
Time |
16:26 |
Rev Time |
0.33 |
| Received By |
dpalmer |
Date |
2004-06-23 |
Time |
16:26 |
Sent To |
|
|
| Notes |
| 2004-06-23 00:00:00 | ********** UNSAT ************* | | | | | | 1)NOTE: PLEASE CORRELATE REVISIONS AS | | | SHOWN ON TITLE BLOCKS. | | | PLEASE ALSO SEE REV #5 IS NOT SHOWN ON | | | PLANS AS SHOWN ON TITLE BLOCK. | | | PLEASE SEE REV #4 IS SHOWN AS BEING | | | BLDG DEPT COMMENTS, YET NO REVIEW OR | | | COMMENTS ARE RECORDED FROM THIS OFFICE.? | | | | | | | | | PLEASE SEE NOTES FROM PREVIOUS REVISION | | | WHICH HAD COMMENTS HAVE NOT YET BEEN | | | SUBMITTED FOR REVIEW. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2004-06-14 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-06-18 |
Time |
12:56 |
Rev Time |
0.50 |
| Received By |
dpalmer |
Date |
2004-06-14 |
Time |
16:50 |
Sent To |
|
|
| Notes |
| 2004-06-14 00:00:00 | ******* UNSAT ******** | | | | | | 1)NOTE: PLEASE SEE E-3, NOTE MENTIONS | | | "NEW GENERAL STORAGE" DIRECTLY INFRONT | | | OF NEW ELECTRICAL PANELS? PLEASE SEE | | | 110.26 | | | | | | 2)NOTE: PLEASE CLARIFY GFI PROTECTION | | | FOR KITCHEN RECEPTS PER 210.8B3 | | | ALL 125V 15/20A. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected]. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2004-03-26 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2004-03-26 |
Time |
09:19 |
Rev Time |
1.00 |
| Received By |
btrobaug |
Date |
2004-03-26 |
Time |
07:28 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2004-01-26 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-01-26 |
Time |
15:08 |
Rev Time |
2.00 |
| Received By |
dpalmer |
Date |
2004-01-26 |
Time |
13:46 |
Sent To |
|
|
| Notes |
| 2004-01-26 00:00:00 | ************* UNSAT ******** | | | | | | PLANS ONLY IN FOR PLAN REVIEW | | | | | | 1)NOTE: PLEASE CLARIFY NEW OR EXISTING | | | RECEPT FOR A/C EUIIPMENT. 210.63 | | | | | | 2)NOTE: PLEASE SHOW ALL CONTINOUS LOADS | | | AT 125% , ALSO LARGEST MOTOR. | | | 215.3, 230.42 ETC | | | | | | 3)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW SERVICE EQUIPMENT BEING INSTALL- | | | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE | | | RATED FOR THE AVAILABLE FAULT CURRENT. | | | PER 110.9/215.5 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
N |
Date |
2004-02-12 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2004-02-12 |
Time |
11:02 |
Rev Time |
0.00 |
| Received By |
drunnels |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2004-03-23 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2004-03-23 |
Time |
16:57 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2004-03-23 |
Time |
16:57 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2004-01-22 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2004-01-22 |
Time |
16:16 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2004-01-22 |
Time |
16:16 |
Sent To |
|
|
| Notes |
| 2004-01-22 00:00:00 | 1) DEMOLITION, RENOVATION, AND | | | CONSTRUCTION SHALL COMPLY WITH | | | NFPA 241. | | | | | | 2) DEBRIS SHALL BE REMOVED FROM THE | | | BUILDING DAILY. | | | | | | 3) ALL CLOSET AND BATHROOM DOOR LOCKS | | | SHALL BE OPENABLE FROM THE OUTSIDE. | | | | | | 4) PANIC HARDWARE SHALL BE PROVIDED | | | ON DOORS WITH AN OCCUPANT LOAD OF 100 | | | OR MORE PERSONS. | | | | | | 5) PLEASE INDICATE INTERIOR FINISH | | | CLASSIFICATION FOR WALLS AND CEILINGS. | | | | | | 6) ENSURE BUILDING ADDRESS IS AVAILABLE. | | | A MINIMUM OF 6" HIGH NUMBERS ARE | | | REQUIRED. | | | | | | 7) SEPARATE PLANS AND PERMITS | | | REQUIRED FOR FIRE SPRINKLER REMODEL. | | | | | | 8) SEPARATE PLANS AND PERMITS REQUIRED | | | FOR NEW FIRE ALARM EQUIPMENT. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
9 |
Status |
N |
Date |
2004-08-26 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-08-26 |
Time |
15:49 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-08-26 |
Time |
15:49 |
Sent To |
P |
|
| Notes |
| 2004-08-26 00:00:00 | TO KS BOX/RE |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
8 |
Status |
N |
Date |
2004-08-12 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-08-12 |
Time |
15:23 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-08-12 |
Time |
15:22 |
Sent To |
P |
|
| Notes |
| 2004-08-12 00:00:00 | TO KS BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
7 |
Status |
N |
Date |
2004-07-02 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-07-02 |
Time |
13:26 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-07-02 |
Time |
13:26 |
Sent To |
|
|
| Notes |
| 2004-07-02 00:00:00 | TO COMM BD#10 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2004-06-18 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-06-18 |
Time |
12:56 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-06-18 |
Time |
12:56 |
Sent To |
E |
|
| Notes |
| 2004-06-18 00:00:00 | TO DP DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2004-06-08 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-06-08 |
Time |
15:17 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-06-08 |
Time |
15:17 |
Sent To |
|
|
| Notes |
| 2004-06-08 00:00:00 | TO COMM BD#21 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2004-05-26 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2004-05-26 |
Time |
09:25 |
Rev Time |
0.00 |
| Received By |
alange |
Date |
2004-05-26 |
Time |
09:25 |
Sent To |
B |
|
| Notes |
| 2004-05-26 00:00:00 | TO SH DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2004-04-07 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-04-07 |
Time |
15:26 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-04-07 |
Time |
15:26 |
Sent To |
|
|
| Notes |
| 2004-04-07 00:00:00 | TO COMM BD#15 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2004-03-23 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-03-23 |
Time |
09:49 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-03-23 |
Time |
09:49 |
Sent To |
|
|
| Notes |
| 2004-03-23 00:00:00 | TO COMM BD#16 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2004-02-26 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2004-04-13 |
Time |
08:00 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2004-01-20 |
Time |
16:04 |
Sent To |
|
|
| Notes |
| 2004-01-20 00:00:00 | TO COMM BD#36 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2004-07-12 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2004-07-12 |
Time |
12:05 |
Rev Time |
0.55 |
| Received By |
pkrauss |
Date |
2004-07-12 |
Time |
11:46 |
Sent To |
|
|
| Notes |
| 2004-07-12 00:00:00 | PROVISO: | | | PLAN SHEET M-4 INDICATES KEF-1 FROM | | | THE DISHWASHER HOOD TERMINATING AT THE | | | WALL.TERMINATION SHALL COMPLY WITH THE | | | FOLLOWING SECTIONS FROM THE 2001 FBC(M), | | | 506.4.1, 401.5, & 401.5.2. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2004-06-16 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2004-06-16 |
Time |
09:37 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2004-06-16 |
Time |
07:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2004-03-31 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2004-03-31 |
Time |
15:08 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2004-03-31 |
Time |
14:50 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2004-02-02 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2004-02-02 |
Time |
10:53 |
Rev Time |
1.00 |
| Received By |
pkrauss |
Date |
2004-02-02 |
Time |
10:53 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
7 |
Status |
P |
Date |
2004-09-01 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2004-09-01 |
Time |
15:47 |
Rev Time |
1.00 |
| Received By |
kstevens |
Date |
2004-09-01 |
Time |
15:47 |
Sent To |
|
|
| Notes |
| 2004-09-01 00:00:00 | REVISION OK - PIPING FOR KITCHEN AREA | | | AND GAS PIPING OK |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
6 |
Status |
F |
Date |
2004-08-18 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-08-26 |
Time |
15:50 |
Rev Time |
1.25 |
| Received By |
kstevens |
Date |
2004-08-18 |
Time |
16:41 |
Sent To |
|
|
| Notes |
| 2004-08-18 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 FUEL GAS | | | | | | 1) SHTS P7 & P8 HUB DRAIN NOT APPROVED | | | FOR INDIRECT WASTE FOR DISHWASHER. HUB | | | DRAINS ARE APPROVED FOR CLEAR WASTE ONLY | | | AND A FLOOR SINK IS REQUIRED FOR THE | | | DISCHARGE FROM A DISHWASHER. SECTION | | | 802.3 | | | 2) FROM PREVIOUS REVIEW: SHT P8 WATER | | | ISOMETRIC, WATER HAMMER ARRESTORS SHALL | | | BE LOCATED IN AN "EFFECTIVE RANGE" NOT | | | IN THE CEILING AS SHOWN. PDI-WH 201 AND | | | MANUF. INSTALLATION INSTRUCTIONS WHICH | | | FROM THE INFORMATION SUBMITTED STATES, | | | "AS CLOSE TO THE VALVE(S) AS POSSIBLE. | | | RESPONSE NOTED, BUT NOT APPROVED. | | | 3) EMERGENCY HOOD SHUT DOWN SHUT OFF | | | VALVE TO BE BELOW CEILING. MANUAL SHUT | | | OFF VALVE TO BE UPSTREAM. UNION TO BE | | | DOWN STREAM OF MANUAL VALVE. FROM PRE- | | | VIOUS REVIEW: RESPONSE NOTED, BUT NOT | | | APPROVED. | | | 4) SHUT OFF VALVES TO GAS APPLIANCES | | | SHALL BE FULL SIZE AS THE PIPE REQUIRED | | | TO SUPPLY THE APPLIANCE. SEE RED LINE | | | CORRECTIONS FOR SHUT OFF VALVE SIZE. | | | MAKE CORRECTIONS AND RESUBMIT PLANS. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
F |
Date |
2004-07-27 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-08-12 |
Time |
15:23 |
Rev Time |
1.50 |
| Received By |
kstevens |
Date |
2004-07-27 |
Time |
10:11 |
Sent To |
|
|
| Notes |
| 2004-07-27 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 FUEL GAS | | | FBC-2001 CHAPTER 1 | | | CITY CODE | | | | | | 1) SHT P-2 NO REVISION #3 FOUND. PLEASE | | | CLARIFY. | | | 2) SHT P-3 NO REVISION #3 FOUND. PLEASE | | | CLARIFY. | | | 3) SHT P-7 DEMO'D PIPES SHALL BE INSPTE- | | | TED PRIOR TO COVERING. - ALSO IN THE IN- | | | STALLATION OR REMOVAL OF ANY PART OF A | | | DRAINAGE SYSTEM, DEAD ENDS SHALL BE PRO- | | | HIBITED. SECTION 704.5 | | | 4) SHT P-7 DISH WASHERS SHALL BE CONNEC- | | | TED TO SANITARY SYSTEM, NOT GREASE SYST- | | | EM. CITY CODE. | | | 5) SHT P-8 WATER ISOMETRIC, WATER HAMMER | | | ARRESTORS SHALL BE LOCATED IN AN "EFFEC- | | | TIVE RANGE" NOT IN THE CEILING. PDI-WH | | | 201 AND MANUF. INSTALL. INSTRUCTIONS. | | | 6) THE FOLLOWING INFORMATION IS REQUIRED | | | FOR GAS PERMIT. SEPERATE GAS PER REQUIR- | | | ED. | | | A. BTU LOAD OF EACH APPLIANCE AND THE | | | TOTAL BTU LOAD ON THE SYSTEM. REFER TO | | | THE FBC-2001 FUEL GAS CODE SECS. 401.8 | | | THRU 402.5.2 AND TABLES 402(1) THRU | | | 402(34). | | | B. SUBMIT CALCULATIONS FOR COMBUSTION | | | AIR (IF APPLICABLE) PER FBC-2001 FUEL | | | GAS CODE SECTION 304. | | | C. INDICATE THE DELIVERY PRESSURE (PSI) | | | PER FBC-2001 FUEL GAS CODE SEC. 402.2. | | | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. | | | D. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2001 FUEL GAS CODE SEC 402.2 | | | E. EMERGENCY HOOD SHUT DOWN SHUT OFF | | | VALVE TO BE BELOW CEILING. MANUAL SHUT | | | OFF VALVE TO BE UPSTREAM. UNION TO BE | | | DOWN STREAM OF MANUAL VALVE. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
F |
Date |
2004-06-19 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2004-06-19 |
Time |
07:52 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2004-06-19 |
Time |
07:52 |
Sent To |
|
|
| Notes |
| 2004-06-19 00:00:00 | REVISION DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | | | | 1) REVISIONS SHALL BE ROUTED TO THE PALM | | | BEACH COUNTY HEALTH DEPT. DIVISION OF | | | ENVIRONMENTAL HEALTH FOR REVIEW PRIOR TO | | | REVIEW BY CITY WPB. SECTION 101.4.7 | | | 2) REVISIONS STATE "REVISED PER BLDG. | | | DEPT. COMMENTS. WHEN RESUBMITTING PLANS | | | SUBMIT COPY OR BLDG. DEPT. COMMENTS THAT | | | REQUIRED REVISIONS. SECTION 104.2.1. | | | 3) SEPARATE GAS PERMIT WILL BE REQUIRED. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2004-04-15 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2004-04-15 |
Time |
16:57 |
Rev Time |
2.00 |
| Received By |
kstevens |
Date |
2004-04-15 |
Time |
16:57 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2004-03-25 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2004-03-25 |
Time |
16:34 |
Rev Time |
7.00 |
| Received By |
kstevens |
Date |
2004-03-25 |
Time |
16:34 |
Sent To |
|
|
| Notes |
| 2004-03-25 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | FBC-2001 CHAPTER 11 | | | ADA ACCESSIBILITY GUIDELINES | | | BLDG. ELEMENTS DESIGNED FOR | | | CHILDREN'S USE | | | | | | A) COMMENTS FROM PREVIOUS REVIEW HAVE | | | NOT BEEN RESPONDED TO SUFFICIENTLY. THE | | | NUMBER OF THE COMMENT SHALL STAY THE | | | SAME AS ORIGINAL REVIEW TO PREVENT CON- | | | FUSION. | | | 1) SHT A1 SECTION 11-4.1(6) IF TOILET | | | FACILITIES ARE PROVIDED ON A SITE, THEN | | | EACH SUCH PUBLIC OR COMMON USE TOILET | | | FACILITIY SHALL COMPLY WITH 11-4.22. | | | TOILET ROOMS 116, 120, 124, AND 147 | | | SHALL COMPLY WITH 11-4.16, 11-4.18, AND | | | 11-4.22 AND ALL SUBSECTIONS. SUBMIT A | | | DETAIL SHOWING COMPLIANCE. - RESPONSE | | | NOTED. BUILDING OFFICIAL STATED THAT ALL | | | TOILET ROOMS SHALL COMPLY WITH ADA GUID- | | | LINES FOR BUILDING ELEMENTS DESIGNED FOR | | | CHILDREN'S USE. 4.16.7(2) RECOMMENDS W/C | | | SEAT HEIGHT BE 12" FOR AGES 3 AND 4, BUT | | | ATTACHED SHEET SHOWS 10". 4.16.7 RECOMM- | | | ENDS CENTERLINE OF W/C TO BE 12" OFF THE | | | WALL. SECTION 4.16(7) RECOMMENDS A GRAB | | | BAR HEIGHT BETWEEN 18" & 20". ATTACHED | | | SHEET SHOWS 22" AND NOT GRAB BARS ARE | | | SHOWN IN TOILET ROOMS MENTIONED ABOVE. | | | FLUSH CONTROLS SHALL BE A MAXIMUM HEIGHT | | | OF 36" FOR W/C'S SERVING CHILDREN AGES | | | 2 TO 4. 4.16.7(5) TOILET PAPER DISPENS- | | | ERS TO BE 14" TO 19". | | | 2) PLANS SHALL BE ROUTED TO THE PALM | | | BEACH COUNTY HEALTH UNIT DIVISION OF | | | ENVIRONMENTAL HEALTH, 901 EVERNIA STREET | | | WPB 33401. (561) 355-3018 PRIOR TO RE- | | | SUBMITTING TO CITY OF WPB FOR REVIEW. | | | SECTION 101.4.7. - RESPONSE NOTED, BUT | | | NO STAMP FROM THE HEALTH DEPT. WAS FOUND | | | ON SHEET A-1. | | | 3) SHT A4 ACCESSIBLE TOILET DETAILS. | | | SUBMIT INFORMATION ON TA-6 TOILET PAPER | | | DISPENSER SHOWING ADA APPROVAL. PAPER | | | DISPENSER IS ENCHROACHING INTO THE CLEAR | | | FLOOR SPACE FOR W/C. 11-4.18.2 - RESPON- | | | SE NOTED, BUT NO CUT SHEETS WERE FOUND. | | | 11) EACH WATER CLOSET UTILIZED BY THE | | | PUBLIC OR EMPLOYEES SHALL OCCUPY A SEP- | | | ARATE COMPARTMENT WITH A DOOR AND WALLS | | | OR PARTITIONS BETWEEN FIXTURES TO EN- | | | SURE PRIVACY. SECTION 310.4 - RESPONSE | | | NOTED. IS ARTICLE X PHYSICAL FACILITIES, | | | E) TOILET AND BATH FACILITIES, P.37 AN | | | EXEMPTION TO THE CODE? PLEASE PROVIDE | | | THIS INFORMATION. | | | 12) WATER CLOSET COMPARTMENTS SHALL NOT | | | BE LESS THAN 30" WIDE AND 60" DEEP. - | | | RESPONSE NOTED.SEE COMMENT #11. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2004-02-05 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2004-02-05 |
Time |
14:10 |
Rev Time |
6.00 |
| Received By |
kstevens |
Date |
2004-02-05 |
Time |
14:09 |
Sent To |
|
|
| Notes |
| 2004-02-05 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTPER 1 | | | FBC-2001 CHAPTER 11 | | | ADA ACCESSIBILITY GUIDELINES | | | FOR BLDGS AND FACILITIES; | | | BUILDING ELEMENTS DESIGN- | | | ED FOR CHILDRES'S USE | | | | | | 1) SHT A1 SECTION 11-4.1(6) IF TOILET | | | FACILITIES ARE PROVIDED ON A SITE, THEN | | | EACH SUCH PUBLIC OR COMMON USE TOILET | | | FACILITY SHALL COMPLY WITH 11-4.22. | | | TOILET ROOMS 116, 120, 124, AND 147 | | | SHALL COMPLY WITH 11-4.16, 11-4.18, AND | | | 11-4.22 AND ALL SUBSECTIONS. SUBMIT A | | | DETAIL SHOWING COMPLIANCE. | | | 2) PLANS SHALL BE ROUTED TO THE PALM | | | BEACH COUNTY HEALTH UNIT DIVISION OF | | | ENVIRONMENTAL HEALTH, 901 EVERNIA STREET | | | WPB 33401. (561) 355-3018 PRIOR TO RE- | | | SUBMITTING TO CITY OF WPB FOR REVIEW. | | | SECTION 101.4.7 | | | 3) SHT A4 ACCESSIBLE TOILET DETAILS. | | | SUBMIT INFORMATION ON TA-6 TOILET PAPER | | | DISPENSER SHOWING ADA APPROVAL. PAPER | | | DISPENSER IS ENCHOACHING INTO CLEAR | | | FLOOR SPACE FOR W/C. 11-4.16.2 | | | 4) SHT A4 DETAIL 1/A4(B) SHOW URNAL | | | HEIGHT FOR URINAL PER 11-4.18.2. | | | 5) SHT A4 SHOW CLEAR FLOOR SPACE FOR | | | URINAL ON PLAN ENLARGMENT PER SECTION | | | 11-4.18.3. | | | 6) SUBMIT CALCULATIONS FOR MINIMUM FIX- | | | TURES, (FACILITIES), PER TABLE 403.1 IN | | | PLUMBING AND TABLE 1003.1 IN BUILDING. | | | 7) SHT P-1 DEMO NOTES: ALL CAPPED PLUMB- | | | ING LINES SHALL BE INSPECTED PRIOR TO | | | COVERING. | | | 8) SHT P-1 PLUMBING SPECIFICATIONS #4(B) | | | DIELECTRIC UNIONS ARE NOT APPROVED FOR | | | WATER USE. DELET FROM REFERENCE. | | | 9) SHT P-5 WATER ISOMETRIC AT TOILET | | | ROOMS 124, 120 & PUBLIC RESTROOMS. WATER | | | HAMMER ARRESTORS SHALL BE LOCATED NEAR | | | THE FIXTURES IN AN "EFFECTIVE RANGE" NOT | | | IN THE CEILING AS SHOWN. PDI-WH 201 AND | | | MANUF. INSTALLATION INSTRUCTIONS. 604.9 | | | (ALSO SEE #137 IN CORRIDOR). | | | 10) SHT P-6 FLOOR MOUNTED ELECTRIC WATER | | | HEATER DETAIL. THERMAL EXPANSION CONTROL | | | REQUIRED PER SECTION 607.3.2. PROVIDE A | | | DETAIL. | | | 11) EACH WATER CLOSET UTILIZED BY THE | | | PUBLIC OR EMPLOYEES SHALL OCCUPY A SEP- | | | ARATE COMPARTMENT WITH A DOOR AND WALLS | | | OR PARTITIONS BETWEEN DIXTURES TO EN- | | | SURE PRIVACY. SECTION 310.4 | | | 12) WATER COLSET COMPARTMENTS SHALL NOT | | | BE LESS THAN 30" WIDE AND 60" DEEP. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2004-04-08 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2004-04-08 |
Time |
13:46 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2004-04-08 |
Time |
13:46 |
Sent To |
|
|
| Notes |
| 2004-04-08 00:00:00 | 4/8/2004 - APPROVED.JOHN ROACH, | | | PLANNER 659.8031 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2004-03-30 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2004-03-30 |
Time |
12:00 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2004-03-30 |
Time |
12:00 |
Sent To |
|
|
| Notes |
| 2004-03-30 00:00:00 | 3/30/2004 - DENIED: NEW LANDSCAPING MUST | | | BE INSTALLED ACCORDING TO CITY CODE AND | | | EXISTING LANDSCAPING THAT HAS DIED MUST | | | BE REPLACED.PROPOSED SIGN MUST BE | | | APPROVED UNDER A SEPARATE PERMIT. | | | CALLED CONTRACTOR.JOHN ROACH, PLANNER | | | 659.8031 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
2004-02-12 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2004-02-12 |
Time |
11:03 |
Rev Time |
0.00 |
| Received By |
drunnels |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|