Plan Review Details - Permit 04010875
Plan Review Stops For Permit 04010875
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2004-07-16 Cont ID  
Sent By jgomez Date 2004-07-16 Time 10:22 Rev Time 0.50
Received By jgomez Date 2004-07-16 Time 10:22 Sent To PC
Notes
2004-07-16 00:00:00FIREPLACE REVISION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2004-07-02 Cont ID  
Sent By csiegber Date 2004-07-14 Time 14:44 Rev Time 0.50
Received By jgomez Date 2004-07-02 Time 13:59 Sent To PC
Notes
2004-07-02 00:00:00REVISION SECOND CHECKLIST:
 1-FIREPLACE PAKCAGE SUBMITTED IS FOR
 INSIDE FIREPLACE. NEED COMPLETE
 PACKAGE FOR APPROVED UL "OUTDOOR"
 FIREPLACE.
 2-FRAMED CHIMNEY BASE DETAIL ON SHEET A4
 IS INCOMPLETE. THERE ARE NO SPECS FOR
 FASTENERS (TOP AND BOTTOM, ETC). SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC.
 3-DETAIL 2 ON SHEET A-4 CALLS FOR 42"
 FIREPLACE. REVISE DIMENSIONS ON FLOOR
 PLAN & FOUNDATION TO MATCH DIMENSIONS
 REQUIRED FOR THAT MODEL. SEE FIREPLACE
 SPECIFICATIONS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 805-6712.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2004-06-16 Cont ID  
Sent By csiegber Date 2004-07-01 Time 16:31 Rev Time 0.75
Received By jgomez Date 2004-06-16 Time 09:47 Sent To PC
Notes
2004-06-15 00:00:00REVISION CHECKLIST:
 1-PROVIDE COMPLETE INFORMATION FOR PRE-
 FABRICATED MASONRY FIREPLACE TO BE
 USED OUTDOORS AS REQUIRED BY SECTION
 2806 FBC 2001. (PROVIDE LISTING AND
 COMPLETE SPECS/INSTALLATION PACKAGE)
 **ARCHITECT TO REVIEW AND APPROVE PRE-
 FABRICATED FIREPLACE PACKAGE PRIOR TO
 SUBMITTAL TO THIS OFFICE.
 2-PROVIDE COMPLETE SECTION DETAIL TRU
 FIREPLACE AND CHIMNEY THAT REFLECTS
 ACTUAL FIELD CONDITIONS. REVISE ROOF
 FRAMING PLAN TO SHOW CHIMNEY AND FLUE
 LOCATION TO VERIFY FOR CLEARANCES
 (AS REQUIRED BY THE FLUE LISTING AND
 SPECIFICATIONS) SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 3-SPECIFY AND SHOW LOCATION OF FIRE-
 BLOCKING AS REQUIRED BY SEC. 2305.1.3
 AND 2305.1.4 FBC 2001.
  
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-04-02 Cont ID  
Sent By mjacobs Date 2004-06-15 Time 12:11 Rev Time 3.00
Received By jgomez Date 2004-04-02 Time 14:35 Sent To PC
Notes
2004-04-01 00:00:00BUILDING REVIEW PROVISO:
 1-PROVIDE COMPLETE FLORIDA OR LOCAL
 PRODUCT APPROVAL INFORMATION UNDER A
 SEPARATE PERMIT (AS AGREED WITH DAWN
 FROM DESARATA BLDG CORP.) FOR:
 A)FRENCH DOORS WITH TRANSOM ABOVE SINGLE
 ASSEMBLY AS SHOWN ON PLANS.
 B)SLIDING GLASS DOORS WITH TRANSOM ABOVE
 AS SHOWN ON PLANS.
 C)BUTT GLAZING SYSTEM AS SHOWN ON PLANS.
 D)ALL STRUCTURAL CONNECTORS USED.
 E)STORM SHUTTERS WITH COMPLETE INSTALLA-
 TION SCHEDULE THAT MATCHES PLANS. WITH
 LEGIBLE DRAWINGS. MATCHING FLORIDA
 APPROVED DRAWINGS.
 F)MISSILE IMPACT FIXED WINDOWS FOR
 LARGER SIZES AS SHOWN ON PLANS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-03-09 Cont ID  
Sent By csiegber Date 2004-03-25 Time 14:32 Rev Time 3.00
Received By jgomez Date 2004-03-09 Time 17:47 Sent To PC
Notes
2004-03-09 00:00:00BUILDING REVIEW CHECKLIST:
 1-PAY IMPACT FEES. BRING BACK STAMPED
 DRAWINGS AND PAID RECEIPT.
 2-NOTICE OF COMMENCEMENT IS VOID. NO
 WORK WITHING 90 DAYS OF RECORDATION.
 3-DESIGN CRITERIA: NEED TO ADD 30PSF OR
 10PSF ATTIC LIVE LOAD AS REQUIRED BY
 TABLE 1604.1 FBC 2001. THESE LOADS
 NEED TO BE SPECIFIED FOR ATTIC AREA
 (BOTTOM CHORD OF TRUSS). INFORMATION
 GIVEN ON SHEET A-9 DOESN'T ADDRESS THE
 ATTIC AREA, BUT ROOF LIVE LOAD ONLY.
 4-NEED COMPLETE FLORIDA OR LOCAL PRODUCT
 APPROVAL INFORMATION FOR BUTT GLAZING
 SYSTEM TO BE USED. USE UPDATED FORM&
 PROVIDE ALL INFO. REQUESTED ON IT.
 **NOTE: ENGINEER TO PROVIDE ALL INFO. AS
 AS REQUESTED ON RULE 9B-72 SECTION
 9B-72.040(5). SEE ATTACHED COPY. ALSO,
 SEE WWW.FLORIDABUILDING.ORG.
 5-PROVIDE FLORIDA/LOCAL PRODUCT APPROVAL
 FOR FRENCH DOORS WITH TRANSOM ABOVE
 UNIT AS SHOWN ON PLANS.
 6-PROVIDE FLORIDA/LOCAL PRODUCT APPROVAL
 FOR SLIDING GLASS DOORS WITH TRANSOM
 ABOVE SINGLE UNIT AS SHOWN ON PLANS.
 7-CLARIFY WHERE ARE TRUSSES RESTING AT
 ENTRY PORCH ROOF. ONE SIDE WAS CLARI-
 FIED BUT THE OTHER SIDE DOESN'T SHOW
 A GIRDER BELOW. SEE COMMENTS ON PLANS.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 8-OWES $628.11 FOR LOW VALUE DECLARED
 ON APPLICATION AND RADON FEES.
 9-SUBMIT FLORIDA OR LOCAL PRODUCT APPROV
 AL FOR ALL DOORS & WINDOWS TO BE INSTA
 LLED IN THIS HOUSE TO AVOID CONFUSION
 AND EXPEDITE THE REVIEW PROCESS.
 **CLEARLY IDENTIFY WHEN USING IMPACT GLA
 ZING PRODUCTS.
 10-CLARIFY IF PROVIDING STORM SHUTTERS
 OR MISSILE IMPACT GLAZING ON DOORS AND
 WINDOWS. BOTH PACKAGES WERE SUBMITTED
 AND IS UNCLEAR WHAT AREAS ARE TO BE
 PROTECTED WITH SHUTTERS OR NOT SINCE
 SHUTTERS INSTALLATION SCHEDULE COVERS
 ALL OPENINGS. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 11-IF USING STORM SHUTTERS: A)PROVIDE
 KEY PLAN & INSTALLATION SCHEDULE THAT
 MATCHES FLOOR PLAN.
 B)NEED APPROVED FLORIDA PRODUCT APPROVAL
 AND DRAWINGS THAT MATCH SUCH APPROVAL.
 C)REVISE THE "PEAK ROOF HEIGHT" SHOWN ON
 SUBMITTED DRAWINGS. SEE HOW THE PEAK
 ROOF HEIGHT IS MEASURED AND REVISE IT.
 D)PROVIDE LEGIBLE DRAWINGS.
 E)CHECK DRAWINGS FOR PANEL LIMITATIONS.
 F)CLEARLY INDICATE THE EGRESS OPENING AS
 REQUIRED BY SEC. 1005.4.5 FBC 2001.
 G)CLEARLY INDICATE MOUNTING CONDITIONS
 AND ANCHOR TYPE AND SPACING TO BE USED
 ACCORDING TO THE DESIGN PRESSURES,EDGE
 DISTANCE, PANEL SPAN, CONNECTION TYPE
 AND STRUCTURE TO BE ATTACHED TO (MASON
 RY OR CONCRETE).
 12-NEED FLORIDA/LOCAL PRODUCT APPROVAL
 FOR GARAGE DOOR (LARGER DOOR).
 13-CLARIFY IF ENTRY DOORS ARE IMPACT OR
 NOT IMPACT. NEED TO CHECK FOR EGRESS.
 SEC. 1026 FBC 2001.
 14-NEED FL. OR LOCAL PRODUCT APPROVAL
 FOR ROOF TILE.
 15-PROVIDE APPROVED FLORIDA OR APPLY FOR
 LOCAL PRODUCT APPROVAL FOR GLASS BLOCK
 16-PROVIDE PRODUCT APPROVAL FOR FIXED
 WINDOWS WITH SIZES AS SHOWN ON PLANS.
 17-NEED FL. OR LOCAL PRODUCT APPROVAL
 FOR WINDOW MULLIONS.
 **CLEARLY MARK ON DWGS SPECIFIC MULLION
 SIZE AND COMPONENTS TO BE USED. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 18-NEED FL. OR LOCAL PRODUCT APPROVAL
 FOR ALL STRUCTURAL CONNECTORS.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CALL
 JULIO GOMEZ AT 805-6712.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-02-18 Cont ID  
Sent By csiegber Date 2004-03-03 Time 09:34 Rev Time 4.00
Received By jgomez Date 2004-02-18 Time 11:21 Sent To PC
Notes
2004-02-18 00:00:00BUILDING REVIEW CHECKLIST:
 1-PAY IMPACT FEES BRING BACK STAMPED
 DRAWINGS AND PAID RECEIPT.
 2-DESIGN CRITERIA: NEED TO ADD 30PSF OR
 10PSF ATTIC LIVE LOAD ACCORDING TO FBC
 2001 TABLE 1604.1.
 3-ENGINEER TO SIGN, SEAL DWGS AS REQ'D
 BY CHAPTER 471 FLORIDA STATUTES.
 4-DESIGN JOINTS OR SPECIFY WWM SUPPORTS
 AND SPACING ON CONCRETE SLAB AS REQ'D
 SEC. 1909.3 FBC 2001.
 5-SPECIFY SIZE OF ATTIC ACCESS. SECTION
 2309.6 FBC 2001.
 6-NEED COMPLETE BATHROOM WITH DOORS THAT
 ALLOWS 29" MIN. CLEAR OPENING AS REQ'D
 BY SEC. 11-11 FBC 2001.
 7-PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL FOR BUTT GLAZING SYSTEMS USED
 8-PROVIDE PRODUCT APPROVAL FOR FRENCH
 DOORS W/ TRANSOM ABOVE SINGLE ASSEMBLY
 AS SHOWN ON PLANS.
 9-PROVIDE PRODUCT APPROVAL FOR SLIDING
 GLASS DOORS WITH TRANSOM ABOVE SINGLE
 ASSEMBLY AS SHOWN ON PLANS.
 10-PROVIDE DETAIL/SPECS FOR CEILING
 INSTALLATION AT ENTRY & REAR PORCHES.
 SEE ASTM C-926 AND ASTM C-1063.
 SEC. 2504.2 FBC 2001.
 11-PROVIDE DETAILS FOR CONSTRUCTION/
 INSTALLATION OF BEAM BOX OUT AT REAR
 PORCHES. SEC. 104.2.1.2 CITY AMENDMENT
 TO FBC 2001.
 12-PROVIDE COMPLETE DETAIL/SECTION FOR
 INSTALLATION OF HANGING AIR HANDLING
 UNITS. SPECIFY ALL FASTENERS. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 13-UPDATE TRUSS ANCHOR SCHEDULE AND ALL
 DETAILS THAT ARE AFFECTED BY SECTION
 1609.4.3 FBC 2001, WHICH DOESN'T ALLOW
 THE STEEL STRESS TO BE INCREASED.
 PROVIDE ENGINEERING FOR UPLIFT AND
 FASTENERS THAT DIFFER FROM THOSE THAT
 WERE TESTED AND PUBLISHED BY USP.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 14-SHEET A-5: A)REVISE ROOF LAYOUT
 SHOWING ROOF ZONES. SEE ASCE 7-98
 FIGURE 6-5B.
 B)THERE ARE SOME CONNECTORS THAT DON'T
 RESIST THE LOADS CALCULATED ON THE
 ROOF FRAMING PLAN. SEE PLANS FOR
 COMMENTS AND REVISE AS REQUIRED.
 C)CLARIFY WHERE ARE TRUSSES RESTING AT
 ENTRY PORCH. SEE PLAN FOR COMMENTS.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
  
 15-CLARIFY WHAT ARE DETAILS ON DWG A-10
 FOR?. WHERE ARE THEY APPLIED IN THIS
 PROJECT. SEC. 104.2.1.2 CITY AMENDMENT
 16-PROVIDE 2 COPIES SIGNED AND SEALED.
 ONLY ONE WAS SUBMITTED.
 17-OWES $628.11 FOR DECLARED LOW VALUE
 AND RADON FEES.
 18-ONLY PROVIDE PRODUCT APPROVAL FOR
 ITEMS THAT ARE USED IN THIS PROJECT.
 19-CLARIFY IF PROVIDING STORM SHUTTERS
 OR MISSILE IMPACT GLAZONG ON DOORS AND
 WINDOWS. BOTH PACKAGES WERE SUBMITTED
 **IF USING STORM SHUTTERS, THEN, PROVIDE
 UPDATED KEY PLAN THAT MATCHES PLAN
 SUBMITTED. ALSO, NEED DWGS THAT MATCH
 FLORIDA PRODUCT APPROVAL AND THAT ARE
 LEGIBLE.
 **CLEARLY INDICATE THE REQUIRED MEANS OF
 ESCAPE REQ'D BY SEC. 1005.4.5 FBC 2001
 20-PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL FOR GARAGE DOORS. RULE 9B-72.
 21-PROVIDE LEGIBLE DRAWINGS FOR SWINGING
 EXTERIOR DOORS.
 22-CLARIFY WHERE IS THE "IMPACT WALL
 3000" ALUMINUM WINDOW GOING TO BE
 INSTALLED. PROVIDE FLORIDA OR LOCAL
 PRODUCT APPROVAL WITH LEGIBLE DRAWINGS
 23-WINDOW MULLION PRODUCT APPROVAL:
 A)NEED DRAWINGS THAT MATCH FLORIDA
 PRODUCT APPROVAL REPORT.
 B)CLEARLY MARK ON DRAWINGS THE SPECIFIC
 COMPONENTS TO BE USD IN THIS PROJECT.
 24-SITE PLAN ON SHEET A-4 SHOW WRONG
 ORIENTATION. REVISE NORTH ARROW.
 SEE SURVEY.
 25-WALL SECTIONS ON SHEET A-7: SHOW MIN.
 FINISH FLOOR ELEVATION IN RELATION TO
 THE GRADE. SEC. 1804.1.7 CITY
 AMENDMENTS TO FBC 2001.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 805-6712.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-06-07 Cont ID  
Sent By btrobaug Date 2004-06-07 Time 14:21 Rev Time 0.50
Received By btrobaug Date 2004-06-07 Time 12:15 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2004-01-29 Cont ID  
Sent By csiegber Date 2004-06-03 Time 16:29 Rev Time 0.50
Received By btrobaug Date 2004-01-29 Time 17:09 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2004-07-14 Cont ID  
Sent By csiegber Date 2004-07-14 Time 14:44 Rev Time 0.00
Received By csiegber Date 2004-07-14 Time 14:44 Sent To B
Notes
2004-07-14 00:00:00TO JG DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2004-07-01 Cont ID  
Sent By csiegber Date 2004-07-01 Time 16:31 Rev Time 0.00
Received By csiegber Date 2004-07-01 Time 16:31 Sent To B
Notes
2004-07-01 00:00:00TO JG DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2004-06-15 Cont ID  
Sent By mjacobs Date 2004-06-15 Time 12:11 Rev Time 0.00
Received By mjacobs Date 2004-06-15 Time 12:11 Sent To B
Notes
2004-06-15 00:00:00TO JG DESK/SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-06-03 Cont ID  
Sent By csiegber Date 2004-06-03 Time 16:29 Rev Time 0.00
Received By csiegber Date 2004-06-03 Time 16:29 Sent To E
Notes
2004-06-03 00:00:00TO BT DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-04-30 Cont ID  
Sent By csiegber Date 2004-04-30 Time 14:57 Rev Time 0.00
Received By csiegber Date 2004-04-30 Time 14:57 Sent To P
Notes
2004-04-30 00:00:00TO KS BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-03-25 Cont ID  
Sent By csiegber Date 2004-03-25 Time 14:32 Rev Time 0.00
Received By csiegber Date 2004-03-25 Time 14:32 Sent To B
Notes
2004-03-25 00:00:00TO JG DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-03-03 Cont ID  
Sent By csiegber Date 2004-03-03 Time 09:34 Rev Time 0.00
Received By csiegber Date 2004-03-03 Time 09:34 Sent To B
Notes
2004-03-03 00:00:00TO JG DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-02-18 Cont ID  
Sent By mmclean Date 2004-01-22 Time 15:20 Rev Time 0.00
Received By jgomez Date 2004-01-21 Time 11:09 Sent To PC
Notes
2004-01-23 00:00:00TO SFD RACK/E
2004-01-21 00:00:00TO Z

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2004-06-14 Cont ID  
Sent By pkrauss Date 2004-06-14 Time 12:28 Rev Time 0.15
Received By pkrauss Date 2004-06-14 Time 12:26 Sent To B
Notes
2004-06-14 00:00:00PROVISO:
 PROVIDE MANUFACTURER INSTALLATION DATA
 FOR THE PRE-FAB FIRE PLACE.NO OTHER
 MECHANICAL PLANS SUBMITTED FOR REVIEW.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-02-18 Cont ID  
Sent By jleech Date 2004-06-12 Time 07:19 Rev Time 0.33
Received By pkrauss Date 2004-01-30 Time 14:16 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2004-06-12 Cont ID  
Sent By jleech Date 2004-06-12 Time 07:19 Rev Time 0.33
Received By jleech Date 2004-06-12 Time 07:19 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-05-11 Cont ID  
Sent By btrobaug Date 2004-06-07 Time 14:21 Rev Time 0.75
Received By pschmitz Date   Time   Sent To  
Notes
2004-05-11 00:00:00REVISION:ADD ISLAND SINK. PES

Review Stop P PLUMBING
Rev No 1 Status P Date 2004-02-03 Cont ID  
Sent By csiegber Date 2004-04-30 Time 14:57 Rev Time 0.33
Received By jleech Date 2004-02-03 Time 15:04 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2004-01-22 Cont ID  
Sent By mmclean Date 2004-01-22 Time 15:20 Rev Time 0.00
Received By mmclean Date 2004-01-22 Time 15:20 Sent To I
Notes
***NONE***