Plan Review Details - Permit 04010874
Plan Review Stops For Permit 04010874
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2004-05-12 Cont ID  
Sent By jgomez Date 2004-05-12 Time 15:36 Rev Time 0.33
Received By jgomez Date 2004-05-12 Time 15:36 Sent To PC
Notes
2004-05-12 00:00:00CHECKLIST:
 1-NEED TO APPLY FOR A SEPARATE PERMIT
 FOR FRENCH DOORS WITH SIDELITES AND
 TRANSOM ABOVE SINGLE ASSEMBLY AS
 SHOWN ON PLANS AND AS AGREED ON
 PROVISO DATED 4-2-04.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 805-6712.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-04-02 Cont ID  
Sent By pschmitz Date 2004-05-12 Time 11:48 Rev Time 3.00
Received By lsmith Date 2004-04-02 Time 16:47 Sent To PC
Notes
2004-04-02 00:00:00BUILDING REVIEW PROVISO:
 1-PROVIDE COMPLETE PRODUCT APPROVAL INFO
 FOR FRENCH DOORS WITH TRANSOM ABOVE
 SINGLE ASSEMBLY AS SHOWN ON PLANS AND
 UNDER A SEPARATE PERMIT (AS AGREED W/
 DAWN OVER PHONE CONVERSATION).
 B)PRODUCT APPROVAL FOR FIXED WINDOWS W/
 LARGER SIZES AS SHOWN ON PLANS.(UNDER
 SAME PERMIT AS ABOVE).
  
 2-GARAGE DOORS: PROVIDE LEGIBLE DRAWINGS
 AND PRODUCT APPROVAL INFORMATION FOR
 SELECTED MODEL ONLY.(SEPARATE PERMIT
 NOT REQUIRED SINCE INFORMATION WAS
 SUBMITTED, BUT NOT LEGIBLE).
 3-LIBRARY ROOM SHALL NOT BE USED FOR
 SLEEPING PURPOSES BECAUSE: A)NO EGRESS
 SECTION 1005.4 FBC 2001.
 B)DIRECT ACCESS FROM GARAGE. SEC.411.2.8
 FBC 2001.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-03-18 Cont ID  
Sent By csiegber Date 2004-03-25 Time 14:24 Rev Time 2.00
Received By jgomez Date 2004-03-17 Time 17:52 Sent To PC
Notes
2004-03-18 00:00:00BUILDING REVIEW CHECKLIST:
 1-PAY IMPACT FEES. BRING BACK STAMPED
 DRAWINGS AND PAID RECEIPT.
 2-REVISE ENERGY CALCULATIONS: A)CARDINAL
 DIRECTIONS DON'T MATCH PLANS. SEE
 SURVEY AND REVISE AS REQUIRED.
 B)OVERHANG LENGTH SHOWN ON CALCULATIONS
 DON'T MATCH PLANS. SEE PLANS & REVISE
 OVERHANG LENGTH AND HEIGHT AS REQ'D.
 SEC. 103.3 CHAPTER 13 FBC 2001.
 3-PROVIDE BBQ APPROVAL AND SPECS AS
 REQ'D BY SEC. 2808 FBC 2001.
 4-PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL FOR:A)FRENCH DOORS W/ TRANSOM
 ABOVE ASSEMBLY AS SHOWN ON PLANS.
 B)GARAGE DOORS THAT MEET THE DESIGN
 PRESSURES CALCULATED BY THE ARCHITECT.
 C)ENTRY DOORS W/ MISSILE IMPACT GLAZING
 AS CALLED FOR IN PLANS.
 D)FIXED GLASS WITH LARGER SIZES AS SHOWN
 ON PLANS.
  
 5-CLARIFY IF USING MISSILE IMPACT GLASS
 OR STORM SHUTTERS. BOTH PACKAGES WERE
 SUBMITTED. PROVIDE COMPLETE INFO. FOR
 EITHER OPTION & REVISE PLANS AS REQ'D.
 **SEE COMMENTS ON STORM PANELS PACKAGE
 SUBMITTED FOR REQUIRED INFORMATION.
 6-OWES $613.72 FOR DECLARED LOW VALUE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 805-6712.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-02-25 Cont ID  
Sent By jleech Date 2004-03-13 Time 13:50 Rev Time 3.50
Received By jgomez Date 2004-02-25 Time 08:59 Sent To PC
Notes
2004-02-25 00:00:00BUILDING REVIEW CHECKLIST:
 1-PAY IMPACT FEES. BRING BACK STAMPED
 DRAWINGS AND PAID RECEIPT.
 2-NORTH ARROW ORIENTATION SHOWN ON THE
 SITE PLAN IS INCORRECT. SEE SURVEY AND
 REVISE AS REQUIRED.
 3-ENERGY CALCULATIONS: A)ORIENTATION OF
 BUILDING DOESN'T MATCH PLANS. SEE
 SURVEY AND REVISE CALCULATIONS. OR DO
 WORST CASE SCENARIO.
 B)REVISE UNDER ATTIC AREA. SEE SECTION
 604.1.A.1 OF CHAPTER 13 FBC 2001.
 4-PROVIDE COMPLETE BATHROOM WITH A DOOR
 THAT ALLOWS 29" MIN. CLEAR OPENING.
 SEC. 11-11 FBC 2001.
 5-DESIGN CRITERIA: ADD THE 30PSF/10PSF
 ATTIC LIVE LOAD AS REQUIRED BY TABLE
 1604.1 FBC 2001.
 6-PROVIDE BBQ APPROVAL AND SPECS REQ'D
 BY SEC. 2808 FBC 2001.
 7-SPECIFY SAFETY GLASS AS REQUIRED. SEE
 PLANS FOR COMMENTS. SEC. 2405.2 FBC/01
 8-PROVIDE 2 COPIES, SIGNED AND SEALED,
 OF SOIL TEST REPORT. ONLY 1 SUBMITTED.
 9-PROVIDE COMPLETE FLORIDA OR LOCAL
 PRODUCT APPROVAL FOR(NOTE: PROVIDE
 ONLY PRODUCT APPROVAL FOR ITEMS TO BE
 INSTALLED IN THIS PROJECT TO EXPEDITE
 THE REVIEW PROCESS):
 A)SINGLE HUNG WINDOWS. NEED 2 COPIES.
 B)FRENCH DOORS WITH TRANSOM ABOVE SINGLE
 ASSEMBLY AS SHOWN ON PLANS.
 **CLARIFY IF USING IMPACT GLAZING.
 **PROVIDE LEGIBLE DRAWINGS.
 C)WINDOW MULLIONS. NEED MATCHING DWGS
 AND CLEARLY INDICATE MULLION SIZE AND
 COMPONENTS TO BE USED.
 D)CLARIFY IF SWINGING DOORS PRODUCT
 APPROVAL SUBMITTED IS FOR ENTRY DOORS.
 IF SO, THEN, CLARIFY WHAT IS THE MEANS
 OF ESCAPE PROVIDED WHEN STORM SHUTTERS
 ARE INSTALLED. SEC. 1005.4.5 FBC 2001.
 **NEED LEGIBLE DRAWINGS.
 E)STORM SHUTTERS: **FLORIDA APPROVAL IS
 PENDING. **CLARIFY INSTALLATION SCHED.
 TO IDENTIFY WHAT'S IMPACT GLAZING OR
 NOT. **CLEARLY IDENTIFY THE MEANS OF
 ESCAPE. **WHICH PRODUCT APPROVAL IS
 GOING TO BE USED. THERE ARE 2.
 **DRAWINGS NEED TO HAVE ENGINEER'S
 ORIGINAL SEAL, SIGNATURE, DATE AS
 REQUIRED BY THE ENGINEER. **WIND LOAD
 SCHEDULE DWG NEEDS TO REVISE THE PEAK
 ROOF HEIGHT. SEE EXTERIOR ELEVATIONS
 FOR CORRECT ONE.
 **CHECK ENGINEERED DRAWINGS FOR LIMITATI
 ONS ON MAXIMUM/MINIMUM PANEL SPAN.
 **NEED LEGIBLE DRAWINGS.
  
 F)CLARIFY WHERE IS THE "IMPACT WALL 3000
 SYSTEM GOING TO BE USED. NEED FLORIDA
 OR LOCAL PRODUCT APPROVAL.
 **IF THIS SYSTEM IS TO BE USED ON FIXED
 WINDOWS AS SHOWN ON PLANS, THEN, NEED
 SEPARATE PRODUCT APPROVAL FOR WINDOWS
 BIGGER THAN THOSE COVER IN THIS REPORT
 G)NEED FLORIDA/LOCAL PRODUCT APPROVAL
 FOR GARAGE DOORS.
 **NEED GARAGE DOORS THAT MEET THE DESIGN
 PRESSURES CALCULATED BY ARCHITECT.
  
 10-SPECIFY ROOF TILE FASTENING. SEE SEC.
 1606.3 FBC 2001 AND SEC. 104.2.1.1
 CITY AMENDMENTS TO FBC 2001.
 11-OWES $613.72 FOR LOW DECLARED VALUE &
 RADON FEES.
 12-SPECIFY HOW IS (3)2X12 AT ENTRY PORCH
 PUT TOGETHER TO FORM BEAM.SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 13-SHEET A6.1: A)SPECIFY CONNECTOR FOR
 GIRDER TRUSS. SE PLAN FOR COMMENTS.
 B)PROVIDE COLUMN CAP THAT SUPPORTS TWO
 GIRDER TRUSSES AS SHOWN ON PLAN. SEE
 COMMENTS ON ROOF FRAMING PLAN.
 14-REVISE WINDOW BUCK DETAIL: A) SEE
 SEC. 1707.4.4.2 FBC 2001 FOR PROPER
 BUCK INSTALLATION.
 B)PROVIDE DETAIL THAT CORRECTLY SHOWS
 RELATIONSHIP BETWEEN BUCK AND WALL.
 EG: SEE DOOR DETAIL. DRAWING SHOWS
 BUCK INSTALLED ON A PLAIN WALL WITH
 NO EDGES. SEE COMMENTS ON PLANS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 805-6712.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-04-23 Cont ID  
Sent By dpalmer Date 2004-04-23 Time 19:21 Rev Time 0.33
Received By dpalmer Date 2004-04-23 Time 19:21 Sent To  
Notes
2004-04-23 00:00:00REDLINED MISSING EQUIPMENT GRND FROM
 MAIN PANEL TO 60A SUB PANEL.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2004-02-03 Cont ID  
Sent By alange Date 2004-04-22 Time 13:30 Rev Time 0.50
Received By dpalmer Date 2004-02-03 Time 10:08 Sent To M
Notes
2004-02-03 00:00:00***** NOTES REDLINED. *********
  
 1)NOTE: PLEASE SEE FEEDERS AND SEC'S
 SHOWN RATED FOR 200A'S NOT FOR THE 225A
 SHOWN. PLEASE SEE 310.15B6 FOR MIN
 AWG OF 3/0'S.
  
 PLEASE CORRECT PLANS ALONG WITH ANY
 REVISIONS AND/OR OPTIONS BEFORE ROUGH.

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-04-30 Cont ID  
Sent By csiegber Date 2004-04-30 Time 14:54 Rev Time 0.00
Received By csiegber Date 2004-04-30 Time 14:54 Sent To P
Notes
2004-04-30 00:00:00TO KS BOX/JL RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-04-22 Cont ID  
Sent By alange Date 2004-04-22 Time 13:30 Rev Time 0.00
Received By alange Date 2004-04-22 Time 13:30 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-03-25 Cont ID  
Sent By csiegber Date 2004-03-25 Time 14:23 Rev Time 0.00
Received By csiegber Date 2004-03-25 Time 14:23 Sent To B
Notes
2004-03-25 00:00:00TO JG DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-03-09 Cont ID  
Sent By csiegber Date 2004-03-09 Time 14:02 Rev Time 0.00
Received By csiegber Date 2004-03-09 Time 14:02 Sent To P
Notes
2004-03-09 00:00:00TO KS BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-02-25 Cont ID  
Sent By mmclean Date 2004-01-22 Time 15:06 Rev Time 0.00
Received By csiegber Date 2004-01-21 Time 12:06 Sent To  
Notes
2004-01-23 00:00:00TO SFD RACK/E
2004-01-21 00:00:00TO Z

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-02-21 Cont ID  
Sent By jleech Date 2004-02-09 Time 14:09 Rev Time 0.50
Received By rregueir Date 2004-02-21 Time 07:51 Sent To B
Notes
2004-02-21 00:00:00PROVISO
 ----------------------------------------
 R/A TRANSFER IN GUEST SUITE IS TOO SMALL
 TO COMPLY WITH THE REQUIREMENTS OF FBC,M
 SECTION 601.4. MINIMUM DUCT SIZE FOR
 THIS DUCT WOULD BE 11" ROUND. A 12"
 ROUND DUCT WOULD BE ACCEPTABLE.
  
 RONALD J REGUEIRO 561-805-6734

Review Stop P PLUMBING
Rev No 3 Status P Date 2004-05-12 Cont ID  
Sent By pschmitz Date 2004-05-12 Time 11:37 Rev Time 1.00
Received By pschmitz Date   Time   Sent To B
Notes
2004-05-12 00:00:00REVISION,OK, FEE DUE $60.00 PES

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-03-13 Cont ID  
Sent By csiegber Date 2004-04-30 Time 14:54 Rev Time 0.50
Received By jleech Date 2004-03-13 Time 13:49 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-02-09 Cont ID  
Sent By csiegber Date 2004-03-09 Time 14:02 Rev Time 0.33
Received By jleech Date 2004-02-09 Time 14:08 Sent To M
Notes
2004-02-09 00:00:00DENIED;
 RISER DIAGRAM DOES NOT MATCH FLOOR PLAN.
 MASTER BATH TUB IS MISSING, LAVS. ARE
 NOT ON SAME WALL 2 VENTS REQUIRED,
 HORIZONTAL DRY VENTS NOT PERMITED, W/C.
 KITCHEN SINK SHOULD HAVE MACHANICAL VENT
 K/S CANNOT BE PART OF THE BATHROOM VENT
 SEE FBC PLUMBING SEC. 909.1.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status P Date 2004-01-22 Cont ID  
Sent By mmclean Date 2004-01-22 Time 15:06 Rev Time 0.00
Received By mmclean Date 2004-01-22 Time 15:06 Sent To I
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy