Plan Review Details - Permit 04010808
Plan Review Stops For Permit 04010808
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-05-05 Cont ID  
Sent By rmcdouga Date 2004-05-05 Time 07:40 Rev Time 0.00
Received By rmcdouga Date 2004-05-05 Time 07:40 Sent To  
Notes
2004-05-05 00:00:00SUBMITTED PRODUCT APPROVAL FOR COLLIER
 GARAGE DOORS IS OK.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-03-17 Cont ID  
Sent By rmcdouga Date 2004-03-17 Time 13:50 Rev Time 2.00
Received By rmcdouga Date 2004-03-17 Time 13:50 Sent To  
Notes
2004-03-17 00:00:00BUILDING PROVISO
 1) SUBMIT STATE PRODUCT APPROVAL COVER
 SHEET INDICATING THAT COLLIER GARAGE
 DOOR HAS BEEN UPDATED FROM VALIDATED TO
 APPROVED, PRIOR TO INSTALLING.
 2) SUBMIT STATE PRODUCT APPROVAL FOR
 8'X 7' GARAGE DOOR WHICH IS SMALLER THAN
 THE 10'X 6' MINIMUM SIZE LISTED ON
 DRAWING CFL2WLP-168.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-02-24 Cont ID  
Sent By csiegber Date 2004-03-08 Time 12:44 Rev Time 2.50
Received By rmcdouga Date 2004-02-24 Time 08:47 Sent To  
Notes
2004-02-24 00:00:00DENIED
  
 1)RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) SUBMIT A SIGNED AND SEALED COPY OF A
 SOIL BORING TEST REPORT AS REQUIRED BY
 FBC 1804.2.2.
  
 3) FBC TABLE 1604.1 REQUIRES ATTICS WITH
 STORAGE TO HAVE A 30 PSF LIVE LOAD AND
 ATTICS WITHOUT STORAGE TO HAVE 10 PSF
 LIVE LOAD. SPECIFY ON THE PLANS.
  
 4) THE WINDOW SCHEDULE ON SHEET 3
 SPECIFIES A 3617 AWNING WINDOW AND THE
 ELEVATION ON SHEET 1 SHOWS A 3020
 HORIZONTAL ROLLING WINDOW. PLEASE
 CORRECT.
  
 5) THE TRANSOM WINDOW ABOVE THE ENTRY
 DOORS IS NOT LISTED IN THE WINDOW
 SCHEDULE.
  
 6) SPECIFY THE WINDLOAD PRESSURES FOR
 THE EXTERIOR SWING DOORS AND THE TRANSOM
 WINDOW ABOVE ENTRY DOORS.
  
 7) THE TITLES FOR THE LEFT AND RIGHT
 ELEVATIONS ON SHEET 1 ARE REVERSED.
 PLEASE CORRECT.
  
 8) SPECIFY THE LOCATION AND MATERIALS
 FOR THE DRAFTSTOPPING OF THE FLOOR/
 CEILING ASSEMBLY INTO AREAS LESS THAN
 500 SQFT AS REQUIRED BY FBC 2305.2.2.
  
 9) SUBMIT COMPLETED FORM FOR LOCAL
 PRODUCT APPROVAL FOR THE COLLIER GARAGE
 DOORS. SPECIFY THE QUALITY ASSURANCE
 ENTITY ON THE FORM. SEE RULE 9B-72.
 THE DRAWINGS SUBMITTED ARE LIMITED TO A
 MINIMUM SIZE OF 10'X 6' AND DOES NOT
 APPLY TO THE 8'X7' GARAGE DOOR ON THE
 PLAN. SUBMIT ADDITIONAL INSTALLATION
 DRAWINGS FOR THE SMALL DOOR.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2004-01-23 Cont ID  
Sent By dpalmer Date 2004-01-23 Time 16:03 Rev Time 0.50
Received By dpalmer Date 2004-01-23 Time 16:03 Sent To M
Notes
2004-01-23 00:00:00****** NOTES REDLINED ****
 MISSING RECEPTS PER 210.52
 BR#2, BR#5

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-03-08 Cont ID  
Sent By csiegber Date 2004-03-08 Time 12:44 Rev Time 0.00
Received By csiegber Date 2004-03-08 Time 12:44 Sent To B
Notes
2004-03-08 00:00:00TO RM DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-02-24 Cont ID  
Sent By mmclean Date 2004-01-21 Time 15:43 Rev Time 0.00
Received By csiegber Date 2004-01-16 Time 12:18 Sent To  
Notes
2004-01-22 00:00:00TO SFD RACK/E
2004-01-20 00:00:00TO Z

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-01-30 Cont ID  
Sent By dpalmer Date 2004-01-23 Time 16:03 Rev Time 0.33
Received By pkrauss Date 2004-01-30 Time 13:55 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2004-02-04 Cont ID  
Sent By pkrauss Date 2004-01-30 Time 13:55 Rev Time 0.25
Received By jleech Date 2004-02-04 Time 10:30 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2004-01-21 Cont ID  
Sent By mmclean Date 2004-01-21 Time 15:43 Rev Time 0.00
Received By mmclean Date 2004-01-21 Time 15:43 Sent To I
Notes
***NONE***