| 2004-02-24 00:00:00 | DENIED |
| | |
| | 1)RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) SUBMIT A SIGNED AND SEALED COPY OF A |
| | SOIL BORING TEST REPORT AS REQUIRED BY |
| | FBC 1804.2.2. |
| | |
| | 3) FBC TABLE 1604.1 REQUIRES ATTICS WITH |
| | STORAGE TO HAVE A 30 PSF LIVE LOAD AND |
| | ATTICS WITHOUT STORAGE TO HAVE 10 PSF |
| | LIVE LOAD. SPECIFY ON THE PLANS. |
| | |
| | 4) THE WINDOW SCHEDULE ON SHEET 3 |
| | SPECIFIES A 3617 AWNING WINDOW AND THE |
| | ELEVATION ON SHEET 1 SHOWS A 3020 |
| | HORIZONTAL ROLLING WINDOW. PLEASE |
| | CORRECT. |
| | |
| | 5) THE TRANSOM WINDOW ABOVE THE ENTRY |
| | DOORS IS NOT LISTED IN THE WINDOW |
| | SCHEDULE. |
| | |
| | 6) SPECIFY THE WINDLOAD PRESSURES FOR |
| | THE EXTERIOR SWING DOORS AND THE TRANSOM |
| | WINDOW ABOVE ENTRY DOORS. |
| | |
| | 7) THE TITLES FOR THE LEFT AND RIGHT |
| | ELEVATIONS ON SHEET 1 ARE REVERSED. |
| | PLEASE CORRECT. |
| | |
| | 8) SPECIFY THE LOCATION AND MATERIALS |
| | FOR THE DRAFTSTOPPING OF THE FLOOR/ |
| | CEILING ASSEMBLY INTO AREAS LESS THAN |
| | 500 SQFT AS REQUIRED BY FBC 2305.2.2. |
| | |
| | 9) SUBMIT COMPLETED FORM FOR LOCAL |
| | PRODUCT APPROVAL FOR THE COLLIER GARAGE |
| | DOORS. SPECIFY THE QUALITY ASSURANCE |
| | ENTITY ON THE FORM. SEE RULE 9B-72. |
| | THE DRAWINGS SUBMITTED ARE LIMITED TO A |
| | MINIMUM SIZE OF 10'X 6' AND DOES NOT |
| | APPLY TO THE 8'X7' GARAGE DOOR ON THE |
| | PLAN. SUBMIT ADDITIONAL INSTALLATION |
| | DRAWINGS FOR THE SMALL DOOR. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |