Plan Review Details - Permit 04010659
Plan Review Stops For Permit 04010659
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-12-30 Cont ID  
Sent By jgomez Date 2004-12-30 Time 15:38 Rev Time 2.50
Received By jgomez Date 2004-12-30 Time 15:38 Sent To PC
Notes
2004-12-30 00:00:00BUILDING PROVISO:
 PROVIDE FOLLOWING INFORMATION PRIOR TO
 CONSTRUCTION OR INSTALLATION:
  
 1-PROVIDE COMPLETE STORM SHUTTERS
 INFORMATION UNDER A SEPARATE PERMIT.
  
 2-PROVIDE COMPLETE PRODUCT APPROVAL FOR
 SINGLE GLAZED AND DOUBLE GLAZED OUT
 SWING DOORS WITH DRAWINGS THAT MATCH
 FLORIDA PRODUCT APPROVAL.FLORIDA
 PRODUCT APPROVAL CALLS FOR "WOOD-EDGE
 STEEL DOOR UNITS", BUT DRAWINGS
 SUBMITTED ARE FOR ""METAL-EDGE STEEL
 DOORS"
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-12-03 Cont ID  
Sent By jgomez Date 2004-12-03 Time 14:27 Rev Time 2.00
Received By jgomez Date 2004-12-03 Time 14:27 Sent To PC
Notes
2004-12-03 00:00:00CHECKLIST:
 1-PROVIDE 2 COMPLETE COPIES OF FLORIDA
 PRODUCT APPROVAL FOR:
 A) FRENCH DOORS TO BE USED.
 B) WINDOW MULLIONS.
 C)STRUCTURAL CONNECTORS (USP OR SIMSON)
 D)SINGLE HUNG WINDOWS(NEED 2 COPIES)
 E)ROOF TILE. NEED REPORT AND DWGS
 SUBMITTED TO FLORIDA BUILDING COMMISSION
 FOR APPROVAL. (NOTE: REPORT SUBMITTED TO
 FLORIDA WAS FROM SBCCI AND IS ONLY GOOD
 FOR 110MPH. THEREFORE PRODUCT IS NOT
 GOOD FOR THIS AREA. REPORT SUBMITTED TO
 THIS OFFICE WAS FROM DADE COUNTY)
 F)FLAT ROOF SYSTEM: NEED NOA REPORT THAT
 MATCHES ONE SUBMITTED TO THE FLORIDA
 BUILDING COMMISSION.
 G) ENTRY DOOR. NEED TWO COPIES.
 H) SIDE SWING DOOR & MECHANICAL RM
 DOOR.
  
 2-PROVIDE 2 COPIES OF SOIL TEST REPORT.
  
 3-ENERGY CALCULATIONS: A) COMPLETE
 INFORMATION ON TOP OF FORM. OWNER,
 BUILDER ETC.
 B) PREPARER TO DATE FORM.
 C)OWNER/AGENT TO SIGN AND DATE FORM.
 D)PROVIDE TWO COPIES.
  
 4-PROVIDE COMPLETE INFORMATION FOR STORM
 SHUTTERS: A) COMPLETE FLORIDA APPROVED
 DRAWINGS.
 B) KEY PLAN AND COMPLETE INSTALLATION
 SCHEDULE. SEE ATTACHED SAMPLE.
 C)INDICATE ON DWGS MOUNTING CONDITIONS
 AND SPECIFIC ANCHOR TYPE AND SPACING TO
 BE USED ACCORDING TO THE DESIGN
 PRESSURES, PANEL SPAN, CONNECTION TYPE,
 EDGE DISTANCE AND STRUCTURE TO BE
 ATTACHED TO (MASONRY OR CONCRETE).
  
 5-CLARIFY INFORMATION ON DWG #3 FOR ROOF
 WALL SHEATHING AND INFORMATION ON DWG 7
 FOR ROOF SHEAR DIAPHRAM AND REVISED
 TABLE 2306.1. CLARIFY SIZE OF FASTENERS,
 SPACING, PLYWOOD THICKNESS & ROOF ZONE.
  
 6-GARAGE DOOR BUCK IS MISSING SIZE OF
 BUCK.
  
 7-CONTRACTOR NEEDS TO APPLY FOR PERMIT
 AND PAY PERMIT FEES.
 **NOTE: IF ALL TRADES SIGN IN THE
 APPLICATION AT TIME OF PERMIT SEPARATE
 FEES FOR EACH TRADE WILL BE SAVED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 805-6712.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-02-12 Cont ID  
Sent By jleech Date 2004-02-04 Time 10:58 Rev Time 2.50
Received By jgomez Date 2004-02-12 Time 13:17 Sent To PC
Notes
2004-02-12 00:00:00BUILDING REVIEW CHECKLIST:
 1-PROVIDE COMPLETE PRODUCT APPROVAL FOR
 ALL DOOR AND WINDOW TYPES, MULLIONS,
 ROOF TILE, FLAT ROOF SYSTEM AND ALL
 STRUCTURAL CONNECTORS.
 **NOTE: VISIT WWW.FLORIDABUILDING.ORG
 FOR OPTIONS AVAILABLE TO PROVIDE THE
 PRODUCT APPROVALS.
 2-PROVIDE ENRGY CALCULATIONS AS REQUIRED
 BY CHAPTER 13 FBC 2001.
 3-NEED RECORDED NOTICE OF COMMENCEMENT.
 4-PAY IMPACT FEES TO PALM BEACH COUNTY.
 BRING BACK STAMPED DWGS & PAID RECEIPT
 5-PROVIDE SOIL TEST REPORT.
 6-DESIGN CRITERIA: LIST ALL ITEMS AS
 REQ'D BY SEC. 1606.1.7 FBC 2001.
 7-SPECIFY SUPPORTS AND SPACING FOR WWM
 IN CONCRETE SLAB. SEE SEC. 1909.3 FBC.
 8-SPECIFY SAFETY GLASS WHERE REQUIRED.
 SEE PLANS AND SEC. 2405.2 FBC 2001.
 9-CLARIFY SIZE OF WINDOWS. FLOOR PLAN
 CALLS FOR SH245 WINDOWS, WHILE EXT.
 ELEVATIONS SHOW 60" HIGH WINDOWS.
 ALSO, KEEP IN MIND THAT SH245 WINDOW
 MAY NOT PROVIDE THE 24" CLEAR HEIGHT
 REQUIRED BY SEC. 1005.4.4 FBC 2001.
 10-PROVIDE DETAIL/SPECS FOR CEILING
 INSTALLATION AT ENTRY PORCH, PORTE
 COCHERE AND REAR LANAI. SEE ASTM C926
 AND 61063. PROVIDE COMPLETE SPECS
 INCLUDING FASTENERS SIZE AND SPACING.
 SEC. 2504.2 FBC 2001.
 11-THERE ARE DIFFERENT SPECS FOR ROOF
 SHEATHING. CLARIFY WHAT SPECS APPLY TO
 THIS PROJECT. SEE SHEETS #3,#7 AND #11
 12-PROVIDE FRAMING DETAIL/SPECS FOR
 ARCHED OPENINGS. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 13-CLARIFY IF USING STORM SHUTTERS OR
 MISSILE IMPACT GLAZING IN DOORS AND
 WINDOWS. IF USING STORM SHUTTERS, THEN
 PROVIDE PRODUCT APPROVAL AND COMPLETE
 INFO. INCLUDING COMPLETE INSTALLATION
 SCHEDULE, KEY PLAN AND CLEARLY INDICA-
 TING ON ENGINEERED DRAWINGS SPECIFIC
 ANCHOR TYPE AND SPACING TO BE USED.
 14-DESIGN CRITERIA TO INCLUDE 30PSF
 ATTIC LOAD FOR AREAS WITH STORAGE OR
 10PSF FOR AREAS WITHOUT STORAGE. SEE
 TABLE 1604.1 FBC 2001.
 15-SHOW LOCATION OF VENTS TO ACHIEVE
 ATTIC CROSS VENTILATION. SEC. 2309.7
 FBC 2001.
 16-CLARIFY SPECIFICATIONS FOR WINDOWS &
 DOORS BUCK DETAILS. SEE COMMENTS ON
 PLANS. CHECK INFO. GIVEN ON DWG #3,#7,
 #8. SPECIFY WHICH ONE APPLIES TO THIS
 PROJECT. SEC. 104.2.1.2 CITY AMENDMENT
 17-PROVIDE COMPLETE DETAILS/SPECS FOR
 SCREENING AT COVERED LANAI OR PROVIDE
 COMPLETE INFORMATION UNDER A SEPARATE
 PERMIT.SEC. 104.2.1.2 CITY AMENDMENTS.
 18-SHEET #7 ROOF SHEATHING DIAPHRAGM:
 REVISE ZONE #3. SEE COMMENTS ON DWG &
 FIGURE 1606.2(C) FBC 2001.
 19-SHEET #*: A)REVISE SPECS FOR GARAGE
 DOOR. NEED ONE FOR 140MPH, NOT 110MPH.
 B)REVISE TIE BEAM ELEVATION. FLAT ROOF
 SYSTEM TO HAVE 1/4" PER FT. SLOPE.
 SEC. 1508.1 FBC 2001. SEE COOMENTS ON
 PLAN.
 C)SPECIFY FIREBLOCKING. SEC. 2305 FBC.
 D)PROVIDE COMPLETE SPECS FOR FASTENING
 OF 2X WOOD LEDGER TO RECEIVE TRUSSES.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 E)CLARIFY SIZE OF GARAGE DOOR. SPECS
 CALL FOR 10' WIDE DOOR, BUT PLANS ARE
 DIMENSIONED FOR 12'WIDE DOOR.
 20-DETAIL F/11: UPDATE/REVISE SPECS FOR
 TRUSS CONNECTOR. HUGHES IS OUT OF
 BUSINESS. SEE COMMENTS ON PLANS.
 21-BUILDING VALUATION WAS ADJUSTED TO
 $148,670, THEREFORE, ADDITIONAL
 FEES MAY BE DUE.
  
  
 NOTES:
 **PLEASE RETURN REVIEWED SET AFTER
 CORRECTIONS ARE DONE TO ORIGINAL DWGS
 TO EXPEDITE REVIEW PROCESS.
 **IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 805-6712.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2005-07-26 Cont ID  
Sent By dpalmer Date 2005-07-26 Time 18:37 Rev Time 0.33
Received By dpalmer Date 2005-07-26 Time 18:27 Sent To  
Notes
2005-07-26 00:00:00250.66, MIN #4

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-12-23 Cont ID  
Sent By dpalmer Date 2004-12-23 Time 06:13 Rev Time 0.33
Received By dpalmer Date 2004-12-23 Time 06:12 Sent To M
Notes
2004-12-23 00:00:00ELECTRICAL PLANS STAMPED.ALL CORRECTED.
  
  
  
 PLANS SENT TO MECH DUE TO NEW MECH PLANS
 SUBMITTED FOR REVIEW.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-11-23 Cont ID  
Sent By dpalmer Date 2004-11-23 Time 06:34 Rev Time 0.40
Received By dpalmer Date 2004-11-23 Time 06:23 Sent To P
Notes
2004-11-23 00:00:00****** UNSAT ********
  
  
 1) NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
 PLEASE SEE RISER SHOWS 5000A/C?? MIN AIC
 IS 10,000 UNLESS USEING CURRENT LIMITING
 5K FUSES.
  
 2)NOTE: PLEASE SEE RISER MENTIONS DISC
 AS REQUIRED? PLEASE SEE RISER ALSO DOES
 NOT INDICATE FEED FROM METER TO MCB
 PANEL AS UNDERGROUND. IF THIS FEED IS
 NOT IN SLAB, A MAIN DISCONNECTING MEANS
 OF SOME SORT WILL BE REQUIRED WITH OCP.
 210.70.
  
 3)NOTE: PLEASE SEE LOAD CALCS, THERE ARE
 MANY ITEMS ON 20A CIRCUITS WHICH EXCEED
 80% (MAX 1920) ON A 20A BRANCH CIRCUIT.
 SOME SHOW 2.2KW? 2.0 KW? ETC
  
 4)NOTE: PLEASE VERIFY OCP FOR AHU (8KW)
 SHOWN AT 60A'S. MIN OCP PER 424.3B IS
 125%, MAX 150%.
 PLEASE ALSO SEE DRYER 5KW ON 40A?
 PLEASE VERIFY KW RATING OF WATER HEATER,
 THIS DOES NOT SEEM TO BE A COMMON KW?
 THIS IS ONLY A NOTE FOR WH.
  
 5)NOTE:PLEASE SEE MISSING RECEPT ON 2'
 OF WALL IN BEDRM. 210.52
  
 6)NOTE: PLEASE SEE MISSING GFI RECEPT ON
 KITCHEN PENINSULAR. 210.52C3, 210.8A6
  
 7)NOTE: PLEASE SEE PANEL SCHEDULE/LOAD
 CALCS INDICATES A GARAGE DOOR OPENER?
  
 8)NOTE: PLEASE PROVIDE INFORMATION ON
 SITE LIGHTING, LANDSCAPE LTS,? POLE
 LTS?
 IF POLE LTS, THEN PROVIDE WIND LOADING
 PER FBC 140 MPH.
  
 PLEASE SEE ONE SET OF PLANS HAS MOST OF
 THE ABOVE ITEMS REDLINED FOR AREAS OF
 COMMENTS.
  
 PLEASE SEE ANY POSSISBLE COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 INSERT ONLY NEW SHEETS INTO COMPLETE
 SETS FOR REVIEW AND STAMPING.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2004-01-23 Cont ID  
Sent By btrobaug Date 2004-01-23 Time 17:50 Rev Time 0.50
Received By btrobaug Date 2004-01-23 Time 17:50 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-07-25 Cont ID  
Sent By adarroug Date 2005-07-25 Time 15:12 Rev Time 0.00
Received By adarroug Date 2005-07-25 Time 15:12 Sent To E
Notes
2005-07-25 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-03-09 Cont ID  
Sent By adarroug Date 2005-03-09 Time 09:54 Rev Time 0.00
Received By adarroug Date 2005-03-09 Time 09:54 Sent To M
Notes
2005-03-09 00:00:00TO PKRAUSS BOX/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-12-22 Cont ID  
Sent By mjacobs Date 2004-12-22 Time 16:20 Rev Time 0.00
Received By mjacobs Date 2004-12-22 Time 16:20 Sent To E
Notes
2004-12-22 00:00:00SENT TO "DP" DESK.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-12-17 Cont ID  
Sent By mjacobs Date 2004-12-17 Time 10:19 Rev Time 0.00
Received By mjacobs Date 2004-12-17 Time 10:19 Sent To Z
Notes
2004-12-17 00:00:00SENT TO "Z" BOX.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-11-17 Cont ID  
Sent By mjacobs Date 2004-11-17 Time 14:09 Rev Time 0.00
Received By mjacobs Date 2004-11-17 Time 14:08 Sent To B
Notes
2004-11-17 00:00:00SENT TO "E" TO DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-11-16 Cont ID  
Sent By mjacobs Date 2004-11-16 Time 14:01 Rev Time 0.00
Received By mjacobs Date 2004-11-16 Time 14:01 Sent To Z
Notes
2004-11-16 00:00:00SENT TO "Z" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-02-12 Cont ID  
Sent By mmclean Date 2004-02-12 Time 14:18 Rev Time 0.00
Received By jgomez Date 2004-01-14 Time 16:37 Sent To PC
Notes
2004-01-16 00:00:001/14/04 TO Z
 TO SFD RACK/E

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2005-03-17 Cont ID  
Sent By pkrauss Date 2005-03-17 Time 15:10 Rev Time 0.30
Received By pkrauss Date 2005-03-17 Time 15:03 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-12-29 Cont ID  
Sent By prafter Date 2004-12-29 Time 08:12 Rev Time 0.45
Received By prafter Date 2004-12-29 Time 08:12 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2004-01-30 Cont ID  
Sent By btrobaug Date 2004-01-23 Time 17:50 Rev Time 0.10
Received By pkrauss Date 2004-01-30 Time 13:10 Sent To P
Notes
2004-01-30 00:00:00PLAN CHECK
  
 NO MECHANICAL PLANS SUBMITTED FOR
 REVIEW.PER NOTE ON SHEET 3, HVAC BY
 OTHERS SUBMIT PLANS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-11-27 Cont ID  
Sent By prafter Date 2004-12-29 Time 08:17 Rev Time 0.33
Received By kstevens Date 2004-11-27 Time 10:18 Sent To B1
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2004-02-04 Cont ID  
Sent By pkrauss Date 2004-01-30 Time 13:20 Rev Time 0.25
Received By jleech Date 2004-02-04 Time 10:57 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2004-12-22 Cont ID  
Sent By mmclean Date 2004-12-22 Time 16:02 Rev Time 0.00
Received By mmclean Date 2004-12-22 Time 16:02 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2004-11-17 Cont ID  
Sent By mmclean Date 2004-11-17 Time 10:17 Rev Time 0.00
Received By mmclean Date 2004-11-17 Time 10:17 Sent To I
Notes
2004-11-17 00:00:00NOTE: NEED TO PROVIDE TWO COPY OF SURVEY
 OR SITEPLAN TO SCALE, SHOWING THE
 SETBACK OF STRUCTURE.CALLED CONTR

Review Stop Z ZONING
Rev No 1 Status F Date 2004-01-15 Cont ID  
Sent By csiegber Date 2004-01-14 Time 16:37 Rev Time 0.00
Received By mmclean Date 2004-01-15 Time 15:04 Sent To I
Notes
2004-01-15 00:00:00DENIED, NEED TO PROVIDE 2 COPY OF SURVEY
 SHOWING SETBACKS CALLED OWNER LEFT MSG M