Plan Review Details - Permit 04010614
Plan Review Stops For Permit 04010614
Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status P Date 2004-09-01 Cont ID  
Sent By jgomez Date 2004-09-01 Time 09:08 Rev Time 0.25
Received By jgomez Date 2004-09-01 Time 09:08 Sent To PC
Notes
2004-09-01 00:00:00GARAGE DOOR PRODUCT APPROVAL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2004-08-20 Cont ID  
Sent By lmartine Date 2004-08-20 Time 17:04 Rev Time 6.00
Received By lmartine Date   Time   Sent To  
Notes
2004-08-20 00:00:00APPROVAL OF ENTRY DOOR SITE SPECIFIC

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status F Date 2004-08-04 Cont ID  
Sent By jgomez Date 2004-08-04 Time 16:41 Rev Time 1.00
Received By jgomez Date 2004-08-04 Time 16:41 Sent To M
Notes
2004-08-04 00:00:00PRODUCT APPROVAL CHECKLIST:
 1-PROVIDE GARAGE DOOR PRODUCT APPROVAL
 THAT MATCHES DOOR SPECIFIED ON PLANS
 OR REVISE PLANS TO MATCH PRODUCT
 APPROVAL SUBMITTED.(RESUBMIT DOORS).
 2-PROVIDE COMPLETE FLORIDA OR LOCAL
 PRODUCT APPROVAL FOR MULLIONS TO BE
 USED BETWEEN DOORS AND TRANSOMS AND
 **NOTE: CLEARLY IDENTIFY MULLION SIZE
 AND FASTENERS TO BE USED.
 3-SUBMITTED STAIR DETAILS:
 A)WHAT'RE THEY SUBMITTED FOR?. ARE THERE
 ANY REVISIONS TO STAIRS?.
 B)DETAILS DON'T MATCH PLANS.
 C)DETAILS ARE MISSING:(CHAPTER 481 F.S.)
 *ARCHITECT'S TITLE BLOCK.
 **ARCHITECT'S SEAL,SIGNATURE AND DATE.
 ***IDENTIFICATION OF PROJECT.
 D)UPDATE SPECIFICATIONS: HUGHES IS OUT
 OF BUSINESS AND S.F.B.C DOESN'T APPLY
 TO THIS AREA AND IS NO LONGER IN USE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 805-6712.

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2004-07-07 Cont ID  
Sent By csiegber Date 2004-07-27 Time 14:51 Rev Time 2.00
Received By jgomez Date 2004-07-07 Time 11:10 Sent To PC
Notes
2004-07-07 00:00:00ENTRY DOOR SECOND CHECKLIST:
 1-ARCHITECT TO PROVIDE ALL REQUIREMENTS
 OF CHAPTER 481 FLORIDA STATUTES WHEN
 SUBMITTING INFORMATION FOR PUBLIC
 RECORDS (INFORMATION NEED TO BE IN ALL
 DRAWINGS SUBMITTED).
 2-PROVIDE COMPLETE DESIGN PACKAGE
 INCLUDING SPECIFICATIONS FOR HINGES
 AND LOCKING HARDWARE DESIGNED TO MEET
 THE CALCULATED WIND LOADS. REFERENCE
 SPECIFIC SECTION AND SUBSECTION OF THE
 CODE USED FOR THE DESIGN.SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 3-DESIGN PAKCAGE DOESN'T PROVIDE ANY
 SPECIFICATIONS FOR DOOR JAMB AND HOW
 IS IT ATTACHED TO THE STRUCTURAL BUCK.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 4-PROVIDE COMPLETE DOOR DETAILS AND
 SPECS SHOWING GLASS INSTALLATION. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 5-SPECIFY HOW IS GLASS PROTECTED FROM
 HURRICANE MISSILE IMPACT. DADE COUNTY
 PRODUCT APPROVAL SUBMITTED FOR GLASS
 SAYS NO RATING FOR MISSILE IMPACT.
 6-IF USING STORM SHUTTERS, THEN PROVIDE
 COMPLETE INFORMATION INCLUDING STORM
 SHUTTERS PRODUCT APPROVAL AND HOW IS
 IT INSTALLED.
 7-DADE COUNTY LAMINATED GLASS PRODUCT
 APPROVAL. SEE PAGE 1 OF 1 PRODUCT
 DESCRIPTION LAST NOTE AND PROVIDE
 INFORMATION AS REQUIRED.
 8-SPECIFY HOW IS DOOR MANUFACTURED TO
 COMPLY WITH ENERGY CALCULATIONS.
 WEATHER STRIPPING ETC. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 9-PROVIDE ALL INFORMATION REQUESTED ON
 PROVISO DATED 4-14-04 TO AVOID ANY
 DELAYS OR CONFLICTS DURING INSPECTION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 805-6712.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2004-06-15 Cont ID  
Sent By csiegber Date 2004-07-01 Time 14:21 Rev Time 2.00
Received By jgomez Date 2004-06-14 Time 13:31 Sent To PC
Notes
2004-06-14 00:00:00ENTRY DOOR PRODUCT APPROVAL CHECKLIST:
 1-AS PER MEETING WITH ASSISTANT BUILDING
 OFFICIAL, BILL STAPLES, SITE SPECIFIC
 PRODUCT APPROVAL WITHOUT TESTING
 REQUIRES SIGNED AND SEALED LETTER FROM
 ARCHITECT OR ENGINEER CERTIFYING THAT
 DOOR WAS BUILT AS PER SPECS & ANOTHER
 LETTER CERTIFYING THAT DOOR WAS
 INSTALLED AS PER SPECS.
 2-DRAWINGS SUBMITTED:
 A)DWGSSUBMITTED NEED TO HAVE ALL
 ARCHITECTS INFORMATION AND ORIGINAL
 SEAL AND SIGNATURE AS REQ'D BY CHAPTER
 481 FLORIDA STATUTES WHEN SUBMITTING
 INFO. FOR PUBLIC RECORDS (PROVIDE 2
 COMPLETE COPIES)
 B)DRAWINGS NEED TO REFERENCE THE DESIGN
 CRITERIA USED.
 FULLY REVIEW SEC. 1707.4 FBC 2001 TO
 PROPERLY MAKE REFERENCE OF DESIGN
 CRITERIA REQUIRED FOR THIS DESIGN.
 **ALSO, SEE SEC. 1606.1.7 FBC 2001 FOR
 MINIMUM REQUIRED INFORMATION.
 C)PROVIDE COMPLETE INFORMATION SHOWING
 HOW THE GLASS IN THE DOOR IS GOING TO
 BE PROTECTED FROM IMPACT AS REQ'D BY
 SEC. 1606.1.4 FBC 2001.
 3-PROVIDE COMPLETE DESIGN PACKAGE
 WITH ALL CALCULATIONS, DETAILS, SPECS,
 ETC. AS REQ'D ON RULE CHAPTER 9B-72,
 CHAPTER 16 AND 17 FBC 2001. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 **INFORMATION SUBMITTED IS COMING FROM 2
 DIFFERENT SOURCES INSTEAD OF BEING A
 COMPLETE SINGLE DESIGN PACKAGE.
 4-ARCHITECT'S DESIGNPACKAGE:
 A)TABLE 1610.1 DOESN'T APPLY FOR THE
 DESIGN OF DOORS. SEE SEC 1606 & 1707.4
 FBC 2001 FOR CORRECT APPLICATION.
 B)ARE HINGES & LOCKING HARDWARE DESIGNED
 FOR EXTERIOR DOORS FOR WIND LOADS?.
 SHOW DESIGN CRITERIA. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
  
  
 **REMAINDER:
 PROVIDE ALL INFORMATION REQUESTED ON
 PROVISO DATED 4-14-04 PRIOR TO INSTA-
 LLATION TO AVOID ANY CONFLICT/DELAYS.
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 805-6712.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2004-05-10 Cont ID  
Sent By csiegber Date 2004-06-08 Time 15:25 Rev Time 0.33
Received By jgomez Date 2004-05-07 Time 17:19 Sent To Z
Notes
2004-05-07 00:00:00FOUNDATION REVISION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2004-04-29 Cont ID  
Sent By csiegber Date 2004-05-06 Time 16:20 Rev Time 0.25
Received By jgomez Date 2004-04-29 Time 12:04 Sent To PC
Notes
2004-04-29 00:00:00REVISION CHECKLIST:
 1-PROVIDE DRAWINGS SHOWING LOCATION OF
 GRADE BEAMS. AND, PROVIDE COMPLETE
 WALL SECTION DETAIL SHOWING ATTACHMENT
 OF GRADE BEAM TO THE EXTERIOR WALL.
 SECTION 104.2.1.2 OF CITY AMENDMENTS
 TO FBC 2001.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 805-6712.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-04-14 Cont ID  
Sent By jgomez Date 2004-04-14 Time 11:59 Rev Time 2.50
Received By jgomez Date 2004-04-14 Time 11:59 Sent To PC
Notes
2004-04-14 00:00:00BUILDING REVIEW PROVISO: PROVIDE THIS
 INFORMATION PRIOR TO CONSTRUCTION:
 1-DESIGNER OF RECORD TO SPECIFY ROOF
 TILE FASTENERS AS REQUIRED BY SECTION
 104.2.1.1 CITY AMENDMENTS TO FBC 2001.
 2-PROVIDE COMPLETE FLORIDA OR LOCAL
 PRODUCT APPROVAL INFORMATION FOR:
 A)ENTRY DOOR (COMPLETE PACKAGE).
 B)FRENCH DOORS WITH TRANSOM ABOVE SINGLE
 ASSEMBLY AS SHOWN ON PLANS AND WITH
 LEGIBLE DRAWINGS.
 C)FIXED WINDOWS WITH LEGIBLE DRAWINGS.
 D)CASEMENT WINDOWS WITH LEGIBLE DRAWINGS
 E)GARAGE DOORS THAT MATCH ARCHITECTURAL
 PLANS OR REVISE ARCHITECTURAL PLANS TO
 MATCH PRODUCT APPROVAL SELECTED.
 F)WINDOW MULLIONS WITH LEGIBLE DRAWINGS.
 G)ALL STRUCTURAL CONNECTORS.
 H)RAILINGS.(REQ'D BY RULE 9B-72)
  
 3-PROVIDE COMPLETE INFORMATION FOR
 OUTDOOR HOOD. UL LISTING AND SPECS.
 4-SHEET A-1: ARCHITECT TO UPDATE NOTES.
 SEE CHAPTER 35 FBC 2001 FOR CORRECT
 EDITION OF ACI 318 AND 530 TO BE USED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-02-27 Cont ID  
Sent By pkrauss Date 2004-04-05 Time 12:24 Rev Time 3.00
Received By jgomez Date 2004-02-27 Time 17:11 Sent To PC
Notes
2004-02-27 00:00:00BUILDING REVIEW CHECKLIST:
 1-NEED RECORDED NOTICE OF COMMENCEMENT.
 2-PAY IMPACT FEES AND BRING BACK STAMPED
 DRAWINGS AND PAID RECEIPT.
 3-SEE ELECTRICAL COMMENTS REGARDING
 INFORMATION ON DRAINGS TITLE BLOCK.
 CHAPTER 481 FLORIDA STATUTES.
 4-PROVIDE SOIL TEST REPORT.
 5-DESIGN CRITERIA: ADD 30PSF/10PSFFOR
 ATTIC LIVE LOAD AS REQUIRED BY TABLE
 1604.1 FBC 2001.
 6-PROVIDE SPECIFICATIONS FOR ROOF TILE
 FASTENING. SEE SEC. 1606.3 FBC 2001 &
 SEC. 104.2.1.1 CITY AMENDMENTS TO FBC.
 7-SPECIFY SUPPORTS AND SPACING FOR WWM
 IN CONCRETE SLAB AS REQ'D BY SECTION
 1909.3 FBC 2001.
 8-REVISE SPECS FOR ROOF SHEATHING: A)SEE
 TABLE 2306.1 CITY AMENDMENTS TO FBC
 2001 FOR MIN. FASTENER TYPE & SPACING
 REQ'D ACCORD'G TO THE MEAN ROOF HEIGHT
 GREATER THAN 25'.
 B)REVISE ROOF ZONES SHOWN ON FRAMING
 PLANS. SEE FIGURE 1606.2(C) TO INCLUDE
 ROOF ZONE 3.
  
 9-PROVIDE APPROVAL AND SPECS FOR BBQ AS
 REQ'D BY SEC. 2808 FBC 2001.
 10-PROVIDE DETAIL/SPECS FOR INSTALLATION
 OF CEILING AT FAMILY LOGGIA. SEE ASTM
 C-926 AND ASTM C1063 FOR MIN. STUCCO
 THICKNESS AND FASTENER TYPE & SPACING.
 SECTION 2504.2 FBC 2001.
 11-PROVIDE COMPLETE FLORIDA OR LOCAL
 PRODUCT APPROVAL PACKAGE FOR:
 A)FRENCH DOORS WITH TRANSOM ABOVE SINGLE
 ASSEMBLY AS SHOWN ON PLANS.
 B)ALL STRUCTURAL CONNECTORS.
 C)ENTRY DOOR SITE SPECIFIC COMPLETE
 ENGINEERING PACKAGE. SEE CITY OF WPB
 FORM FOR INFORMATION REQUIRED.
 **DRAWINGS FOR FRENCH DOOR-IMPACT BY "LA
 FINESTRA" SHOW WINDOWS, NOT DOORS.
 CLARIFY AS REQUIRED.
 D)FIXED WINDOWS. NEED FLORIDA OR LOCAL
 PRODUCT APPROVAL PACKAGE.
 E)CASEMENT WINDOWS NEED FLORIDA 0R LOCAL
 PRODUCT APPROVAL PACKAGE WITH DRAWINGS
 MATCHING THE REPORT.
 F)PROVIDE FLORIDA OR LOCAL PRODUCT APPRO
 VAL FOR GARAGE DOORS. (CYPRESS CLAD?).
 G)PROVIDE FLORIDA OR LOCAL PRODUCT APPRO
 VAL FOR EXT. SWING DOOR AT GARAGE.
 H)SWINGING DOORS BY "JELD-WEN":PLANS
 CALL FOR IMPACT GLAZING. THIS PRODUCT
 IS FOR NON IMPACT GLASS. CLARIFY.
 **NEED MANUFACTURER'S COMPLETE DRAWINGS.
 **CLARIFY WHERE ARE THESE DOORS GOING TO
 BE INSTALLED.
 **NEED FRENCH DOORS WITH TRANSOM ABOVE
 ALSO AS SHOWN ON PLANS.
 I)NEED FLORIDA OR LOCAL PRODUCT APPROVAL
 PACKAGE FOR ROOF TILE.
 J)QUATROFOIL WINDOW NEED FLORIDA/ LOCAL
 PRODUCT APPROVAL PACKAGE.
 K)NEED FLORIDA OR LOCAL PRODUCT APPROVAL
 FOR WINDOW MULLIONS. SEE PLANS.
 L)NEED FLORIDA OR LOCAL PRODUCT APPROVAL
 FOR RAILINGS.
  
 12-PROVIDE COMPLETE FRAMING DETAIL/SPECS
 FOR QUATROFOIL WINDOWS. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 13-OWES $679.71 FOR UPDATED VALUATION
 AND RADON FEES.
 14-ENERGY CALCULATIONS: A)ORIENTATION &
 NUMBER OF OPENINGS DON'T MATCH PLANS.
 B)OVERHANG LENGTH DON'T MATCH PLANS.
  
 15-SHEET A-1: REVISE/UPDATE NOTES. SEE
 COMMENTS ON PLANS.
 16-SHEET A-5: A)CONNECTOR FOR GIRDER
 TRUSS SHOWN DON'T WORK. SEE PLAN FOR
 COMMENTS.
 B)REVISE NAILING PATTERN SCHEDULE. SEE
 FIGURE 1606.2(C) FBC 2001 AND TABLE
 2306.1 CITY AMENDMENTS TO FBC 2001 FOR
 ZONE 3 & MIN. FASTENER TYPE & SPACING
 WHEN MEAN ROOF HEIGHT IS MORE THAN 25'
 17-SHEET A-6: A)PROVIDE DETAIL SHOWING
 INSTALLATION OF 3 CONNECTORS AT ONE
 POINT AS SPECIFIED FOR CONNECTOR C+D.
 SEE PLANS FOR COMMENTS. CLARIFY WHY
 USING WOOD TO WOOD CONNECTOR FOR WOOD
 TO MASONRY CONNECTION.
 B)UPDATE/REVISE TRUSS ANCHOR SCHEDULE.
 SEE SIMPSON 2004 CATALOGUE OR PROVIDE
 ENGINEERING CALCS FOR FASTENER TYPE &
 NUMBER OTHER THAN THOSE TESTED AND
 PUBLISHED BY SIMPSON.
 C)CLARIFY CONNECTORS SPECIFIED ON
 CONNECTOR NOTES. SEE COMMENTS ON PLANS
  
 18-SHEET A-11: CLARIFY INSTALLATION OF
 JOIST HANGER. SEE COMMENTS ON PLANS.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 805-6712.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-10-19 Cont ID  
Sent By btrobaug Date 2004-10-19 Time 10:11 Rev Time 0.50
Received By btrobaug Date 2004-10-19 Time 09:33 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-03-27 Cont ID  
Sent By csiegber Date 2004-10-18 Time 15:39 Rev Time 0.50
Received By btrobaug Date 2004-03-27 Time 11:57 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-01-23 Cont ID  
Sent By csiegber Date 2004-03-25 Time 15:22 Rev Time 1.50
Received By dpalmer Date 2004-01-23 Time 15:31 Sent To M
Notes
2004-01-23 00:00:00**************** UNSAT *************
  
 1)NOTE: PLEASE INCLUDE FIRM LICENSE #
 ON TITLE BLOCK AS REQ'D UNDER FS 481.219
 # SHOWN DOES NOT CORRELATE TO DBPR.
  
 2)NOTE: PLEASE SEE MISSING SD OUTSIDE
 BEDROOMS 2,3,4. NFPA-72
  
 3)NOTE: PLEASE SEE LOAD SHOWN FOR GAS
 WATER HEATER AT 2200 VA. PLEASE SEE THAT
 THIS SEEMS A BIT HIGH
  
 4)NOTE: PLEASE SEE A/C SYSTEM #3 IS
 MISSING FROM PANEL SCHEDULES AND FROM
 LOAD CALCULATIONS. ?? PLEASE SEE TOTAL
 LOAD FIGURED FOR SERVICE. IF LOAD FOR
 A/C SYSTEM #3 IS ADDED, IT WILL BE OVER
 THE 200A SERVICE SHOWN. PLEASE ALSO SEE
 THIS WILL LEAVE NO ROOM FOR ANY FUTURE
 LOADS.
  
 5)NOTE: PLEASE SHOW HOW SUB-PANEL IS
 BEING FED??? RISER SHOWS PANEL FROM
 MAIN PANEL, YET NOTHING IS LISTED FOR
 SUB-PANEL ON MAIN PANEL. PLEASE SHOW
 OCP FOR THIS AND PLEASE VERIFY SIZE OF
 CONDUCTORS SHOWN ON RISER FOR 125A PANEL
  
 6)NOTE: PLEASE SEE LOAD FOR WASHER/
 LAUNDRY TO BE A MIN OF 1500 VA.220.16B
  
 7)NOTE: PLEASE SEE PANEL SCHEDULE, ONLY
 SHOWS TWO CIRCUITS FOR ARC FAULT.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2004-10-18 Cont ID  
Sent By csiegber Date 2004-10-18 Time 15:39 Rev Time 0.00
Received By csiegber Date 2004-10-18 Time 15:39 Sent To E
Notes
2004-10-18 00:00:00TO BT DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2004-08-31 Cont ID  
Sent By csiegber Date 2004-08-31 Time 14:07 Rev Time 0.00
Received By csiegber Date 2004-08-31 Time 14:07 Sent To M
Notes
2004-08-31 00:00:00TO PK BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2004-08-12 Cont ID  
Sent By csiegber Date 2004-08-12 Time 15:26 Rev Time 0.00
Received By csiegber Date 2004-08-12 Time 15:26 Sent To M
Notes
2004-08-12 00:00:00TO PK DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2004-07-27 Cont ID  
Sent By csiegber Date 2004-07-27 Time 14:51 Rev Time 0.00
Received By csiegber Date 2004-07-27 Time 14:50 Sent To B
Notes
2004-07-27 00:00:00TO JG DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2004-07-01 Cont ID  
Sent By csiegber Date 2004-07-01 Time 14:21 Rev Time 0.00
Received By csiegber Date 2004-07-01 Time 14:21 Sent To B
Notes
2004-07-01 00:00:00TO JG DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-06-08 Cont ID  
Sent By csiegber Date 2004-06-08 Time 15:25 Rev Time 0.00
Received By csiegber Date 2004-06-08 Time 15:25 Sent To B
Notes
2004-06-08 00:00:00TO JG DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-06-03 Cont ID  
Sent By csiegber Date 2004-06-03 Time 08:22 Rev Time 0.00
Received By csiegber Date 2004-06-03 Time 08:22 Sent To B
Notes
2004-06-03 00:00:00TO JG DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-05-06 Cont ID  
Sent By csiegber Date 2004-05-06 Time 16:20 Rev Time 0.00
Received By csiegber Date 2004-05-06 Time 16:20 Sent To B
Notes
2004-05-06 00:00:00TO JG DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-03-25 Cont ID  
Sent By csiegber Date 2004-03-25 Time 15:21 Rev Time 0.00
Received By csiegber Date 2004-03-25 Time 15:22 Sent To E
Notes
2004-03-25 00:00:00TO BT DESK/RESUB DP

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-02-27 Cont ID  
Sent By mmclean Date 2004-01-14 Time 10:15 Rev Time 0.00
Received By jgomez Date 2004-01-13 Time 14:04 Sent To PC
Notes
2004-01-14 00:00:00TO SFD RACK/E
2004-01-13 00:00:00TO Z

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2004-09-15 Cont ID  
Sent By pkrauss Date 2004-09-15 Time 07:16 Rev Time 0.30
Received By pkrauss Date 2004-09-15 Time 07:02 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2004-08-17 Cont ID  
Sent By csiegber Date 2004-08-31 Time 14:07 Rev Time 0.35
Received By pkrauss Date 2004-08-17 Time 15:36 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status N Date 2004-08-06 Cont ID  
Sent By csiegber Date 2004-08-12 Time 15:26 Rev Time 0.35
Received By pkrauss Date 2004-08-05 Time 16:19 Sent To  
Notes
2004-08-06 00:00:00PROVISO:
 INSTALLATION OF THE OUTDOOR RANGE AND
 HOOD SHALL BE PER MANUFACTURER'S
 SPECIFICATION.SUFFICIENT AIR REQUIRED
 FOR COMBUSTION AIR.
  
 PLANS SUBMITTED WERE NOT APPROVED.
 PLEASE REMOVE ARCHITECTS TITLE BLOCK.
 ARCHITECT IS NOT REQUIRED FOR MECHANICAL
 BUT PER THE FLORIDA STATUTE IF A TITLE
 BLOCK IS INDICATED ON THE PLAN IT MUST
 BE SIGNED, SEALED AND DATED. FS 481.221.
  
 PLEASE RESUBMIT AS A MECHANICAL REVISION
 WITH EITHER THE ARCHITECT'S SEAL OR
 REMOVE TITLE BLOCK.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-04-05 Cont ID  
Sent By jgomez Date 2004-08-05 Time 14:09 Rev Time 0.40
Received By pkrauss Date 2004-04-05 Time 11:56 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-02-21 Cont ID  
Sent By btrobaug Date 2004-03-27 Time 12:10 Rev Time 0.50
Received By rregueir Date 2004-02-21 Time 08:21 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2004-02-04 Cont ID  
Sent By jleech Date 2004-02-04 Time 13:23 Rev Time 0.33
Received By jleech Date 2004-02-04 Time 13:23 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status F Date 2004-06-15 Cont ID  
Sent By mmclean Date 2004-06-15 Time 09:03 Rev Time 0.00
Received By mmclean Date 2004-06-15 Time 09:03 Sent To  
Notes
2004-06-15 00:00:00DENIED, REVISION FOR WALL
 NEED TO APPLY FOR A SEPARATE PERMIT FOR
 WALL AND PROVIDE A UTILITY EASEMENT
 APPROVAL FROM UTILITY DEPT.CALLED &
 LEFT MSG ON ROSEMARY VOICE MAIL FOR SUSI
 FILE UNDER S FOR P/U MM

Review Stop Z ZONING
Rev No 2 Status P Date 2004-05-10 Cont ID  
Sent By mmclean Date 2004-05-10 Time 13:28 Rev Time 0.00
Received By mmclean Date 2004-05-10 Time 13:28 Sent To  
Notes
2004-05-10 00:00:00PASS REVISION TO CHANGE IN ELEVATION &
 SETBACKS. GIVEN TO PHYLLIS TOCALL FOR
 P/U MM

Review Stop Z ZONING
Rev No 1 Status P Date 2004-01-14 Cont ID  
Sent By jgomez Date 2004-05-10 Time 07:57 Rev Time 0.00
Received By mmclean Date 2004-01-14 Time 10:15 Sent To I
Notes
***NONE***