Plan Review Details - Permit 04010579
Plan Review Stops For Permit 04010579
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-03-04 Cont ID  
Sent By jwitmer Date 2004-03-04 Time 09:47 Rev Time 1.11
Received By jwitmer Date 2004-03-03 Time 13:31 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-02-05 Cont ID  
Sent By jwitmer Date 2004-02-05 Time 09:03 Rev Time 1.00
Received By jwitmer Date 2004-02-05 Time 09:03 Sent To PC
Notes
2004-02-05 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04010579
 ADD: 1801 N FLAGLER# 319
 CONT:G C WORKS INC
 TEL: (305)861-2918
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PLANS ARE TO BE SIGNED WITH A FULL
 SIGNATURE FROM THE ARCHETECT OF RECORD
 PER 481.221 WITH A MINIMUM OF FIRST AND
 LAST NAME AS SHOWN ON THE ARCHITECTS'
 LICENSE, FAC 61G1-16.003
  
 2) HI-RISE TYPE II BUILDINGS, 609.2.1
 ALL BACKING TO BE FIRE RETARDANT WOOD
 OR NON-COMBUSTIBLE.
  
 3)704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 4) 104.2.1.3 THE BUILDING OFFICIAL
 MAY SET STANDARDS THROUGH DEPARTMENTAL
 POLICY STANDARDS FOR PLANS AND SPRCIFICA
 TIONS. "NO WHITE OUT".
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-02-25 Cont ID  
Sent By dpalmer Date 2004-02-25 Time 07:24 Rev Time 0.50
Received By dpalmer Date 2004-02-25 Time 07:18 Sent To  
Notes
2004-02-25 00:00:00********** PROVSIO **************
  
 1)NOTE: PLEASE SEE LOAD FOR LAUNDRY IS
 SHOWN AT 1200VA, PLEASE SEE 220.16 FOR
 MIN LOAD TO BE 1500VA.
  
 2)NOTE: PLEASE SEE PLANS SHOW TWO SIZES
 FOR FEEDERS TO UNIT. ONE NOTE SHOWS 1/0'
 S AND OTHER #1'S.
  
 3)NOTE: PLEASE CORRELATE VOLTAGE INDICAT
 -ED FOR PANEL. SHOWN IN LOAD CALCS AND
 NOTE AS 208, PANEL SHOWS 240V??
  
 PLEASE SUBMIT THE ABOVE AS A REVISION
 BEFORE ANY ROUGH ELECTRICAL INSPECTION
 IS CALLED IN. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-01-14 Cont ID  
Sent By dpalmer Date 2004-01-14 Time 15:47 Rev Time 0.33
Received By dpalmer Date 2004-01-14 Time 15:47 Sent To  
Notes
2004-01-14 00:00:00********* UNSAT ****************
  
 1)NOTE: PLANS TO BE SIGNED WITH A FULL
 SIGNATURE FROM ARCH. PER FS 481.221
 MIN OF FIRST AND LAST NAME AS SHOWN
 ON LICENSE.
  
 2)NOTE: PLANS SHOW NEW PANEL, YET PANEL'
 IS SHOWN AS BEING EXSITNG?
 PLEASE ALSO CLARIFY SIZE OF PANEL, SHOWS
 1/0'S FOR 125A PANEL?
  
  
 3)NOTE: PLEASE SEE MIN LOAD FOR LAUNDRY
 PER 220.16B
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-02-25 Cont ID  
Sent By nmccray Date 2004-02-25 Time 11:02 Rev Time 0.00
Received By nmccray Date 2004-02-25 Time 11:02 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2004-01-20 Cont ID  
Sent By mcarsill Date 2004-01-20 Time 13:46 Rev Time 0.00
Received By mcarsill Date 2004-01-20 Time 13:46 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-08-16 Cont ID  
Sent By csiegber Date 2004-08-16 Time 14:56 Rev Time 0.00
Received By csiegber Date 2004-08-16 Time 14:56 Sent To M
Notes
2004-08-16 00:00:00TO PK BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-03-16 Cont ID  
Sent By csiegber Date 2004-03-11 Time 16:02 Rev Time 0.00
Received By csiegber Date 2004-03-11 Time 16:02 Sent To  
Notes
2004-03-11 00:00:00TO COMM BD#4

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-02-18 Cont ID  
Sent By csiegber Date 2004-02-18 Time 15:09 Rev Time 0.00
Received By csiegber Date 2004-02-18 Time 15:09 Sent To  
Notes
2004-02-18 00:00:00TO COMM BD#57

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-02-05 Cont ID  
Sent By jwitmer Date 2004-02-05 Time 09:03 Rev Time 0.00
Received By jwitmer Date 2004-01-13 Time 08:26 Sent To  
Notes
2004-01-13 00:00:00TO COMM BD#10

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2004-08-27 Cont ID  
Sent By pkrauss Date 2004-08-27 Time 06:47 Rev Time 0.25
Received By pkrauss Date 2004-08-27 Time 06:38 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2004-03-22 Cont ID  
Sent By csiegber Date 2004-08-16 Time 14:56 Rev Time 0.25
Received By pkrauss Date 2004-03-22 Time 06:48 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2004-03-03 Cont ID  
Sent By kstevens Date 2004-03-19 Time 09:32 Rev Time 0.33
Received By pkrauss Date 2004-03-03 Time 06:56 Sent To  
Notes
2004-03-03 00:00:00DENIED:2ND REQUEST
 SEPARATE DRAIN PAN WITH OVERFLOW
 PROTECTION REQUIRED FOR THE AHU.
 PLEASE REVISE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-01-26 Cont ID  
Sent By pkrauss Date 2004-01-26 Time 09:12 Rev Time 0.33
Received By pkrauss Date 2004-01-26 Time 08:28 Sent To  
Notes
2004-01-26 00:00:00DENIED:
 1.PLAN SHEET M-13 C.U. MOUNTING DETAIL
 INDICATES 12" FROM THE ROOF SURFACE TO
 THE BOTTOM OF THE SUPPORT RAIL.SEE THE
 ATTACHED SCHEDULE FOR HEIGHT REQUIREMENT
 PER 2001 FBC 1511.7.
  
 2.AUXILIARY DRAIN PAN REQUIRED WITH
 OVERFLOW PROTECTION BY MEANS OF A FLOAT
 SWITCH OR A SECONDARY DRAIN TERMINATING
 AT A CONSPICUOUS POINT TO SERVE AS AN
 ALARM THAT THE PRIMARY DRAIN IS
 RESTRICTED.2001 FBC 307.2.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 3 Status P Date 2004-03-19 Cont ID  
Sent By csiegber Date 2004-03-11 Time 16:02 Rev Time 0.50
Received By kstevens Date 2004-03-19 Time 09:32 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2004-03-02 Cont ID  
Sent By kstevens Date 2004-03-02 Time 18:32 Rev Time 0.50
Received By kstevens Date 2004-02-27 Time 17:58 Sent To  
Notes
2004-03-02 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 CAST IRON SOVENT DESIGN MAN.
 NUMBER 802
  
 1) WATER HAMMER ARRESTORS LOCATED AT
 KITCHEN SINK SHALL BE LOCATED NEAR THE
 FIXTURES IN AN "EFFECTIVE RANGE" NOT IN
 THE CEILING AS SHOWN.
  
 2) SHT P-2 SANITARY RISER DIAGRAM FOR
 THE BATHROOM GROUPS. SOVENT DESIGN CALLS
 FOR A PRL LINE TO CONNECT TO THE VERTIC-
 AL PORTION OF THE STACK DOWNSTREAM OF
 THE OFFSET. A DE-AERATOR FITTING WILL BE
 REQUIRED AS SHOWN IN ATTACHED SHEET WITH
 PRL LINE TIED INTO IT.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-01-23 Cont ID  
Sent By kstevens Date 2004-01-23 Time 17:02 Rev Time 0.75
Received By kstevens Date 2004-01-23 Time 17:02 Sent To  
Notes
2004-01-23 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FLORIDA ADMIN. CODE
 FLORIDA STATUTES
  
 1) PLANS TO BE SIGNED WITH A FULL SIG-
 NATURE FROM THE ARCH. PER FS 481.221
 WITH A MINIMUM OF FIRST AND LAST NAME AS
 SHOWN ON ARCH. LICENSE. FAC 61G1-16.003.
 2) SHT P-1 WATER HEATER DETAIL:
 A) THERMAL EXPANSION CONTROL REQUIRED
 PER SECTION 607.3.2
 B) DIELECTRIC UNIONS ARE NOT APPROVED
 FOR WATER PIPING. DELETE FROM DETAIL.
 3) SHT P-2 WATER RISER DIAGRAM: WATER
 HAMMER ARRESTORS SHALL BE LOCATED NEAR
 THE FIXTURE IN AN "EFFECTIVE RANGE" NOT
 IN THE CEILING AS SHOWN. PDI-WH 201 AND
 MANUF. INSTALLATION INSTRUCTIONS. 604.9
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]