Plan Review Details - Permit 04010577
Plan Review Stops For Permit 04010577
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-03-03 Cont ID  
Sent By jwitmer Date 2004-03-03 Time 14:37 Rev Time 0.50
Received By jwitmer Date 2004-03-03 Time 14:37 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-02-05 Cont ID  
Sent By jwitmer Date 2004-02-05 Time 08:13 Rev Time 0.75
Received By jwitmer Date 2004-02-05 Time 08:07 Sent To  
Notes
2004-02-05 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04010577
 ADD: 1801 N FLAGLER# 219
 CONT: GC WORKS
 TEL: (305)861-2918
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PLANS ARE TO BE SIGNED WITH A FULL
 SIGNATURE FROM THE ARCHETECT OF RECORD
 PER 481.221 WITH A MINIMUM OF FIRST AND
 LAST NAME AS SHOWN ON THE ARCHITECTS'
 LICENSE, FAC 61G1-16.003
  
 2) HI-RISE TYPE II BUILDING, 609.2.1.
 ALL BACKING TO BE FIRE RETARDANT WOOD
 OR NON-COMBUSTIBLE.
  
 3)704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 4) 104.2.1.3 THE BUILDING OFFICIAL
 MAY SET STANDARDS THROUGH DEPARTMENTAL
 POLICY STANDARDS FOR PLANS AND SPRCIFICA
 TIONS. "NO WHITE OUT".
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-02-25 Cont ID  
Sent By dpalmer Date 2004-02-25 Time 06:37 Rev Time 0.50
Received By dpalmer Date 2004-02-25 Time 06:37 Sent To  
Notes
2004-02-25 00:00:00********* PROVSIO *****
  
 1)NOTE: PLEASE SEE 220.16, LOAD FOR
 LAUNDRY CIRCUIT STILL NOT SHOWN AS REQ'D
 1500VA.
  
 2)NOTE: PLEASE CORRELATE FEEDER CONDUCT-
 -OR SIZES. ONE NOTE MENTIONS, 1/0'S
 OTHER MENTIONS #1'S.
  
 PLEASE SUBMIT THE ABOVE AS A REVISION
 BEFORE ANY ROUGH ELECTRICAL INSPECTION
 IS CALLED IN.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-01-14 Cont ID  
Sent By dpalmer Date 2004-01-14 Time 13:28 Rev Time 0.33
Received By dpalmer Date 2004-01-14 Time 13:28 Sent To  
Notes
2004-01-14 00:00:00*********** UNSAT ******************
  
 1)NOTE: PLEASE HAVE PLANS "SIGNED" BY
 THE ARCH OF RECORD AS SHOWN ON LICENSE.
 PLEASE NOTE, SIGNATURE MUST CONTAIN A
 MIN OF FIRST AND LAST NAME.
 FS 481.025
 WE HAVE BEEN INFORMED, INITIALS ARE
 NOT ACCEPTABLE.
  
 2)NOTE: PLEASE SEE PLANS, SHOWS NEW
 PANEL B2, HOWEVER, PANEL SCHEDULE SHOWS
 EXST? PLEASE CLARIFY THIS.
  
 3)NOTE: PLEASE SEE 220.16B FOR MIN LOAD
 FOR LAUNDRY.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
 REVIEW.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-02-25 Cont ID  
Sent By mcarsill Date 2004-02-25 Time 13:29 Rev Time 0.00
Received By mcarsill Date 2004-02-25 Time 13:29 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2004-01-20 Cont ID  
Sent By mcarsill Date 2004-01-20 Time 13:51 Rev Time 0.00
Received By mcarsill Date 2004-01-20 Time 13:51 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-08-16 Cont ID  
Sent By csiegber Date 2004-08-16 Time 14:56 Rev Time 0.00
Received By csiegber Date 2004-08-16 Time 14:56 Sent To M
Notes
2004-08-16 00:00:00TO PK BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-03-11 Cont ID  
Sent By csiegber Date 2004-03-11 Time 16:02 Rev Time 0.00
Received By csiegber Date 2004-03-11 Time 16:02 Sent To P
Notes
2004-03-11 00:00:00TO KS BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-02-18 Cont ID  
Sent By csiegber Date 2004-02-18 Time 16:10 Rev Time 0.00
Received By csiegber Date 2004-02-18 Time 16:09 Sent To  
Notes
2004-02-18 00:00:00TO COMM BD#8

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-02-05 Cont ID  
Sent By jwitmer Date 2004-02-05 Time 08:06 Rev Time 0.00
Received By jwitmer Date 2004-01-13 Time 09:13 Sent To  
Notes
2004-01-13 00:00:00TO COMM BD#28

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2004-08-27 Cont ID  
Sent By pkrauss Date 2004-08-27 Time 06:30 Rev Time 0.30
Received By pkrauss Date 2004-08-27 Time 06:25 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2004-03-22 Cont ID  
Sent By csiegber Date 2004-08-16 Time 14:56 Rev Time 0.25
Received By pkrauss Date 2004-03-22 Time 06:31 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-02-25 Cont ID  
Sent By kstevens Date 2004-03-19 Time 10:07 Rev Time 0.40
Received By pkrauss Date 2004-02-25 Time 16:26 Sent To  
Notes
2004-02-25 00:00:00PROVISO:
 AUXILIARY DRAIN PAN WITH OVERFLOW
 PROTECTION REQUIRED PER 2001 FBC(M)
 307.2.3.PLEASE PROVIDE SEPARATE PAN
 FOR THE AHU.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-01-30 Cont ID  
Sent By pkrauss Date 2004-01-30 Time 06:55 Rev Time 0.33
Received By pkrauss Date 2004-01-30 Time 06:54 Sent To  
Notes
2004-01-30 00:00:00PROVISO:
 1.CONDENSING UNIT STAND SHALL COMPLY
 WITH 2001 FBC 1511.7, SEE THE SCHEDULE
 BELOW FOR PROPER HEIGHT REQUIREMENT.
  
 2.AUXILIARY DRAIN PAN WITH OVERFLOW
 PROTECTION REQURIED PER 2001 FBC(M)
 307.2.3.A SEPARATE DRAIN IS REUQIRED F
 ROM THE AUXILIARY DRAIN PAN TERMINATING
 AT CONSPICUOUS POINT TO SERVE AS AN
 ALARM THEAT THE PRIMARY DRAIN IS
 RESTRICTED.A FLOAT SWITCH MAY BE USED
 IN LIEU OF SEPARATE DRAIN.

Review Stop P PLUMBING
Rev No 3 Status P Date 2004-03-19 Cont ID  
Sent By kstevens Date 2004-03-19 Time 10:07 Rev Time 1.00
Received By kstevens Date 2004-03-19 Time 10:07 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2004-03-02 Cont ID  
Sent By csiegber Date 2004-03-11 Time 16:02 Rev Time 0.50
Received By kstevens Date 2004-03-02 Time 18:19 Sent To  
Notes
2004-03-02 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 CAST IRON SOVENT DESIGN MAN.
 NUMBER 802
  
 1) WATER HAMMER ARRESTORS LOCATED AT
 KITCHEN SINK SHALL BE LOCATED NEAR THE
 FIXTURES IN AN "EFFECTIVE RANGE" NOT IN
 THE CEILING AS SHOWN.
  
 2) SHT P-2 SANITARY RISER DIAGRAM FOR
 THE BATHROOM GROUPS. SOVENT DESIGN CALLS
 FOR A PRL LINE TO CONNECT TO THE VERTIC-
 AL PORTION OF THE STACK DOWNSTREAM OF
 THE OFFSET. A DE-AERATOR FITTING WILL BE
 REQUIRED AS SHOWN IN ATTACHED SHEET WITH
 PRL LINE TIED INTO IT.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-01-23 Cont ID  
Sent By kstevens Date 2004-01-23 Time 17:59 Rev Time 0.33
Received By kstevens Date 2004-01-23 Time 17:54 Sent To  
Notes
2004-01-23 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FLORIDA ADMIN. CODE
 FLORIDA STATUTES
  
 1) PLANS TO BE SIGNED WITH A FULL SIG-
 NATURE FROM THE ARCH. PER FS 481.221
 WITH A MINIMUM OF FIRST AND LAST NAME AS
 SHOWN ON ARCH. LICENSE. FAC 61G1-16.003.
 2) SHT P-1 WATER HEATER DETAIL:
 A) THERMAL EXPANSION CONTROL REQUIRED
 PER SECTION 607.3.2.
 B) DIELECTRIC UNIONS ARE NOT APPROVED
 FOR WATER PIPING. DELETE FROM DETAIL.
 3) SHT P-2 WATER RISER DIAGRAM: WATER
 HAMMER ARRESTORS SHALL BE LOCATED NEAR
 THE FIXTURE IN AN "EFFECTIVE RANGE" NOT
 IN THE CEILING AS SHOWN. PDI-WH 201 AND
 MANUF. INSTALLATION INSTRUCTIONS. 604.9
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]