Plan Review Details - Permit 04010563
Plan Review Stops For Permit 04010563
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-04-07 Cont ID  
Sent By csiegber Date 2004-04-07 Time 15:07 Rev Time 0.00
Received By csiegber Date 2004-04-07 Time 15:07 Sent To P
Notes
2004-04-07 00:00:00TO KS BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-01-12 Cont ID  
Sent By csiegber Date 2004-01-12 Time 15:31 Rev Time 0.00
Received By csiegber Date 2004-01-12 Time 15:31 Sent To P
Notes
2004-01-12 00:00:00TO GAS

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-04-16 Cont ID  
Sent By kstevens Date 2004-04-16 Time 07:22 Rev Time 0.50
Received By kstevens Date 2004-04-16 Time 07:22 Sent To  
Notes
2004-04-16 00:00:00 
  
  
  
  
  
  
 IF WATER HEATER ROOM IS A CONFINED SPACE
 OPENINGS REQUIRED PER SECTION 304.3.1 0R
 SECTION 304.3.2 SHALL BE INSTALLED.
 MINIMUM 3,750 CUBIC FEET REQUIRED.
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
 Z

Review Stop P PLUMBING
Rev No 1 Status P Date 2004-01-13 Cont ID  
Sent By csiegber Date 2004-04-07 Time 15:07 Rev Time 0.75
Received By kstevens Date 2004-01-13 Time 15:43 Sent To  
Notes
2004-01-13 00:00:00 
  
  
  
  
  
  
 PER N. MELICK MANUFACTURE INFO
 NOT REQUIRED FOR 1 & 2 FAMILY HOMES.
 JULY 17, 2002 OFFICAL INTERPRETATION.
 THE FIELD INSPECTOR SHALL VERIFY THE
 INSTALLED EQUIPMENT INPUT DOES NOT EX-
 CEED THE PIPE SIZING.
  
  
  
  
  
  
  
  
  
 Z