Plan Review Details - Permit 04010540
Plan Review Stops For Permit 04010540
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-04-26 Cont ID  
Sent By lmartine Date 2004-04-26 Time 17:16 Rev Time 3.00
Received By lmartine Date   Time   Sent To  
Notes
2004-04-26 00:00:00 
 BUILDING REVIEW COMMENTS
 -------- ------ --------
  
 1]
 ALL PRODUCT APPROVAL SHALL BE LISTED ON
 FLORIDA'S D.C.A WEBSITE. MISSING
 REPORTS INCLUDE, SKYLIGHT, OVERHEAD
 DOOR, AND METAL ROOF.
  
 2]
 FIRE SPRINKLER LAYOUT IS REQUIRED AT
 TIME OF PERMIT.
  
 3]
 COUNTY IMPACT FEE PAYMENT IS REQUIRED
 PRIOR TO PERMIT ISSUE.
  
  
  
  
 LUIS MARTINEZ
 561-805-6710

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-03-09 Cont ID  
Sent By lmartine Date 2004-03-09 Time 17:32 Rev Time 12.00
Received By lmartine Date   Time   Sent To  
Notes
2004-03-09 00:00:00 
 BUILDING REVIEW COMMENTS
 -------- ------ --------
  
 1]
 PROVIDE SOILS INVESTIGATION REPORT, 2
 COPIES SIGNED AND SEALED.
  
 2]
 SUBMIT ALL PRODUCT APPROVAL REPORTS FOR
 EXTERIOR WINDOWS, DOORS, GLAZING, ROOF
 AND WALL COVERINGS.
  
 3]
 PROVIDE SIGNED AND SEALED FIRE
 SPRINKLER DESIGN AND LAYOUT ACCORDING
 TO: FBC 104.3.1.1#5
  
 4]
 SHEET 10.1 WINDOW SCH.-WN1 REFERENCES
 110MPH WIND SPEED. FBC REQUIRES DESIGN
 TO 140MPH.
  
 5]
 CHECK DOOR SCH. #122 AND #202 SHALL BE
 3/4HR RATED PER FBC 1006.2.2
  
 6]
 SHEET S-6,NOTES ACI 318-94 SHALL BE
 ACI 318-02 PER FBC CHAPTER 35.
 SHEET S-6 SHALL BE SIGNED AND DATED BY
 ENGINEER.
  
  
  
  
  
 LUIS MARTINEZ
 561-805-6710

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-04-15 Cont ID  
Sent By dpalmer Date 2004-04-15 Time 17:35 Rev Time 1.00
Received By dpalmer Date 2004-04-15 Time 17:09 Sent To  
Notes
2004-04-15 00:00:00REDLINED, NO EQUIPMENT GROUNDING
 CONDUCTOR FROM METER TO FIRST MEANS
 OF DISC. 250.24

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-01-22 Cont ID  
Sent By dpalmer Date 2004-01-22 Time 16:43 Rev Time 1.50
Received By dpalmer Date 2004-01-22 Time 15:43 Sent To  
Notes
2004-01-22 00:00:00************ UNSAT ***********
  
 ** PLANS ONLY IN FOR PLAN REVIEW AND NOT
 FOR PERMIT***
  
 1)NOTE: PLEASE PROVIDE A BRIEF LOAD
 SUMMARY FOR W/SQ FT KVA LOAD FOR A/C
 SYSTEMS. PER 220CALL FOR INFO.
  
 2)NOTE: PLEASE SHOW/CLARIFY NEW REQ'D
 SIGN CIRCUIT PER 600.5
  
 3)NOTE: PLEASE CLARIFY LOCATION OF GFI
 RECEPT FOR COND UNITS. PER 210.63
 ROOF TOP ALSO.
  
 4)NOTE: PLEASE CLARIFY/ SHOW METHOD
 OF EQUIPMENT GROUNDING FOR ALL FEEDERS/
 CONDUITS ON RISER DIAGRAM. 250.110,
 250.24 ETC. SIZE PER 250.122
  
 5)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
 MAIN NOT SHOWN. NOTED FOR PANELS.
  
 6)NOTE: PLEASE SEE FIRE REVIEW COMMENTS,
 AND COMMENTS FROM OTHER REVIEWERS AS
 THEY MAY OR MAY NOT HAVE AN AFFECT ON
 ELECTRICAL PLANS.
  
 7)NOTE: PLEASE REMOVE ALL OLD/ VOIDED
 SHEETS AND INSERT NEW SHEETS INTO TWO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 SOME REVIEWERS REQUIRE ONE SET OF OLD
 SHEETS FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2004-04-13 Cont ID  
Sent By mamini Date 2004-04-13 Time 09:32 Rev Time 0.50
Received By mamini Date 2004-04-13 Time 09:32 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2004-01-22 Cont ID  
Sent By mamini Date 2004-01-22 Time 10:20 Rev Time 1.00
Received By mamini Date 2004-01-22 Time 10:20 Sent To  
Notes
2004-01-22 00:00:00FAILED:
 1. PLEASE SUBMIT CIVIL PLANS ONLY TO
 THE PUBLIC UTILITIES AND ENGINEERING
 SERVICES, ATT; JIM SPEACH 659-8040 EXT.
 2317 FOR THIER REVIEW AND APPROVAL OF
 CONNECTIONS, BACKFLOWS AND METERS
 LOCATION.
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-04-01 Cont ID  
Sent By nmccray Date 2004-04-01 Time 11:16 Rev Time 0.00
Received By nmccray Date 2004-04-01 Time 11:16 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-01-22 Cont ID  
Sent By mcarsill Date 2004-01-16 Time 16:44 Rev Time 0.00
Received By mcarsill Date 2004-01-16 Time 16:43 Sent To  
Notes
2004-01-16 00:00:001) WET FIRE HYDRANTS ARE REQUIRED
 PRIOR TO, DURING AND AFTER
 CONSTRUCTION.
  
 2) A KNOX-BOX WILL BE REQUIRED.
  
 3) PLEASE ILLUSTRATE ON PLANS ALL
 EMERGENCY LIGHT FIXTURE LOCATIONS
 FOR SECOND FLOOR.
  
 4) FIRE WATER LINES SHOULD BE LOOPED
 WHENEVER POSSIBLE. IT APPEARS THAT
 THE 6" WATER MAIN ON SITE FOR THIS
 PROJECT DEAD-ENDS NEAR THE WAREHOUSE.
  
 5) PLEASE EXPLAIN WHY STAIR # 201 DOES
 NOT HAVE A DOOR AT THE TOP OR BOTTOM
 AND WHY IS IT OPEN TO THE SECOND FLOOR.
  
 6) PLEASE INDICATE INTERIOR FINISH
 FOR WALLS AND CEILINGS.
  
 7) NO FIRE SPRINKLER PLANS PROVIDED.
  
 8) IT WAS ALSO NOTED THAT FUTURE
 EXPANSIONS ARE PLANNED, IS THE
 PLANNED WATER FIRE LINE GOING TO BE
 BIG ENOUGH.
  
 9) PLEASE PROVIDE MORE DETAILS ON 3/4
 HOUR RATED OPENING PROTECTIVES ON
 SOUTH ELEVATION.
  
 10) TACTILE SIGNAGE REQUIRED AT STAIR
 LOCATIONS.
  
 11) ELEVATOR WARNING SIGNS REQUIRED
 AT ELEVATOR.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-03-31 Cont ID  
Sent By alange Date 2004-03-31 Time 14:14 Rev Time 0.00
Received By alange Date 2004-03-31 Time 14:14 Sent To  
Notes
2004-03-31 00:00:00TO COMM. BD "6

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-03-09 Cont ID  
Sent By mmclean Date 2004-01-15 Time 16:00 Rev Time 0.00
Received By csiegber Date 2004-01-13 Time 09:42 Sent To  
Notes
2004-01-16 00:00:00TO COMM BD#18
2004-01-13 00:00:00TO Z

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-04-08 Cont ID  
Sent By pkrauss Date 2004-04-08 Time 08:24 Rev Time 0.45
Received By pkrauss Date 2004-04-08 Time 07:54 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-01-29 Cont ID  
Sent By pkrauss Date 2004-01-29 Time 12:25 Rev Time 1.25
Received By pkrauss Date 2004-01-29 Time 12:25 Sent To  
Notes
2004-01-29 00:00:00DENIED:
 1.PROVIDE OUTSIDE AIR CALCULATIONS PER
 2001 FBC(M) 403.3.
  
 2.PLEASE INDICATE WHAT THE WAREHOUSE
 WILL BE USED FOR.PROVIDE INFORMATION
 ON ANY CHEMICALS OR COMBUSTIBLES THAT
 MAY BE STORED.
  
 3.PLANS DO NOT INDICATE VENTILATION
 FOR THE WAREHOUSE AREA.SHOW COMPLIANCE
 WITH 2001 FBC(M) TABLE 403.3 FOR
 MINIMUM VENTILATION REQUIREMENTS.
  
 4.DUCT SMOKE DETECTORS REQUIRED IN THE
 SUPPLY DUCT OF SYSTEMS WITH THE DESIGN
 CAPACITY GREATER THAN 2,000 CFM.
 PLEASE INDICATE DUCT SMOKE DETECTORS ON
 THE PLAN.
  
 5.PLEASE INDICATE CONDENSATE FOR THE
 ROOF TOP UNITS THAT SERVE THE SECOND
 FLOOR.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 2 Status F Date 2004-04-05 Cont ID  
Sent By kstevens Date 2004-04-05 Time 15:32 Rev Time 1.25
Received By kstevens Date 2004-04-05 Time 15:31 Sent To  
Notes
2004-04-05 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 BUILDING
  
 A) COMMENTS FROM PREVIOUS REVIEW. NUMBER
 TO STAY THE SAME TO AVOID CONFUSION.
 3) SHTS ME4 & ME6 PLUMBING PLAN FIRST
 FLOOR AND SANT. RISER DIAGRAM. WATER
 CLOSET P-2 IN MEN'S ROOM NOT VENTED.
 SECTION 901.2.1. - RESPONSE NOTED, BUT
 THE P-2 W/C VENTED WAS IN THE WOMENS
 TOILET ROOM. P-2 IN MEN'S TOILET ROOM IS
 DOWNSTREAM OF THE SANITARY LINE FROM THE
 2ND FLOOR AND HAS NO VENT TO DRAW FROM.
 8) EMERGENCY OVERFLOW DRAINS HAVE BEEN
 DELETED AND OVERFLOW SCUPPERS ARE SHOWN.
 PROVIDE A DETAIL OF THE OVERFLOW SCUPPER
 (TYPICAL) AND SHOW HEIGHT & WIDTH. MIN.
 38 SF REQUIRED. SHOW COMPLIANCE WITH
 SECTION 1511.6.4.3 (BUILDING) & SECTION
 1107.3 (PLUMBING)
 *****NEW COMMENT***
 1B) SHT ME6 WATER HEATER DETAIL - P/T
 RELIEF VALVE DISCHARGE LINE SHALL NOT
 HAVE ANY TRAPPED SECTIONS, AND SHALL
 HAVE A VISIBLE AIR GAP OR AIR GAP FITT-
 ING LOCATED IN THE SAME ROOM AS THE
 WATER HEATER.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-01-21 Cont ID  
Sent By kstevens Date 2004-01-21 Time 10:02 Rev Time 1.00
Received By kstevens Date 2004-01-20 Time 18:50 Sent To  
Notes
2004-01-21 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1) SUBMIT DETAIL FOR DRINKING FOUNTAIN
 PER SECTION 11-4.15 AND ALL SUBSECTIONS.
 2) SUBMIT DETAIL FOR BREAK ROOM SINK PER
 SECTION 11-4.24 AND ALL SUBSECTIONS.
 3) SHTS ME4 & ME6 PLUMBING PLAN FIRST
 FLOOR AND SANT. RISER DIAGRAM, WATER
 CLOSET P-2 IN MEN'S ROOM NOT VENTED.
 SECTION 901.2.1
 4) SHT ME4 WATER HEATER UNDER SINK SHALL
 BE ACCESSIBLE. SUBMIT A DETAIL. SECTION
 501.4
 5) SHT ME6 AN RPZ BACKFLOW IS REQUIRED
 ON WATER SERVICE. SECTION 608.13.2
 6) SHT ME6 WATER ISOMETRIC, SHOW WATER
 HEATER PAN DRAIN LINE FOR W/H IN BATH-
 ROOM. SECTIONS 504.8.1 & 504.8.2.
 7) SUBMIT A STORM RISER DIAGRAM SHOWING
 PIPE SIZES AND TERMINATION ECT. SECTION
 104.3.1.1
 8) SHT 7.1 CLAIRFY 5" ERD"S.
 9) SUBMIT CALCULATIONS FOR PRIMARY ROOF
 DRAINS. INDICATE SQUARE FOOTAGE OF ROOF
 AND 1/2 AREA OF ALL VERTICAL WALLS IN-
 CLUDING PARAPETS IN CALCULATIONS. SECT-
 IONS 1106 & 1107 AND ALL SUBSECTIONS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2004-01-15 Cont ID  
Sent By mmclean Date 2004-01-15 Time 16:00 Rev Time 0.00
Received By mmclean Date 2004-01-15 Time 16:00 Sent To I
Notes
2004-01-15 00:00:00OK PER JOSH LONG PLANNER 659-8031 MM