Plan Review Details - Permit 04010527
Plan Review Stops For Permit 04010527
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2004-02-05 Cont ID  
Sent By jwitmer Date 2004-02-05 Time 13:31 Rev Time 2.20
Received By jwitmer Date 2004-02-05 Time 11:28 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2004-01-15 Cont ID  
Sent By dpalmer Date 2004-01-15 Time 11:52 Rev Time 0.50
Received By dpalmer Date 2004-01-15 Time 11:39 Sent To  
Notes
2004-01-15 00:00:00HAND WROTE PE # ON TITLE BLOCK FOR
 ENGINEER.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-02-13 Cont ID  
Sent By mcarsill Date 2004-02-13 Time 14:12 Rev Time 0.00
Received By mcarsill Date 2004-02-13 Time 14:11 Sent To  
Notes
2004-02-13 00:00:001) ENSURE TACTILE SIGNAGE IS
 INSTALLED AT BOTH STAIRWELL DOORS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2004-01-15 Cont ID  
Sent By mcarsill Date 2004-01-15 Time 16:06 Rev Time 0.00
Received By mcarsill Date 2004-01-15 Time 16:06 Sent To  
Notes
2004-01-15 00:00:001) IS IT CORRECT TO HAVE DOOR 301 SWING
 INWARD. THIS OFFICE COUNTED OVER 40
 SEATS BUT IT IS NOT CLEAR IF ANY SEATS
 WERE OMITTED FROM THE DRAWING. IF 50
 OR MORE PERSONS CAN OCCUPY 307, THEN
 THIS EXIT ACCESS DOOR 301 SHOULD
 SWING IN THE DIRECTION OF EXIT TRAVEL.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-02-11 Cont ID  
Sent By csiegber Date 2004-02-11 Time 15:48 Rev Time 0.00
Received By csiegber Date 2004-02-11 Time 15:48 Sent To  
Notes
2004-02-11 00:00:00TO COMM BD#13

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-02-05 Cont ID  
Sent By jwitmer Date 2004-02-05 Time 11:28 Rev Time 0.00
Received By jwitmer Date 2004-01-12 Time 11:41 Sent To  
Notes
2004-01-12 00:00:00TO COMM BD#13

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-01-28 Cont ID  
Sent By pkrauss Date 2004-01-28 Time 16:35 Rev Time 0.40
Received By pkrauss Date 2004-01-28 Time 16:32 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-02-23 Cont ID  
Sent By kstevens Date 2004-02-23 Time 08:08 Rev Time 0.60
Received By kstevens Date 2004-02-20 Time 18:43 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-01-24 Cont ID  
Sent By kstevens Date 2004-01-24 Time 05:11 Rev Time 1.25
Received By kstevens Date 2004-01-24 Time 05:11 Sent To  
Notes
2004-01-24 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1) SHT A-4 DETAIL 2/A-4A SHOW CLEAR
 FLOOR SPACE FOR URNAL PER SEC 11-4.18.3
 2) SHT A-4 DETAIL 5/A-4 LOUNGE SINK.
 SHOW KNEE CLEARANCE 11-4.24.3, CLEAR
 FLOOR SPACE 11-4.24.5, & EXPOSED PIPES
 AND SURFACES 11-4.24.6.
 3) SHT A-5 DETAILS 2/A-5, & 3/A-5, SHOW
 HEIGHT OF W/C 11-4.16.3, AND ACCESSIBLE
 LAV TO BE CENTERED MIN. 15" OFF WALL.
 4) SHT A-5 DETAIL 7/A-5 IF DRINKING
 FOUNTAIN IS NOT A HIGH LOW, THEN PROVIS-
 IONS SHALL BE MADE FOR THOSE WHO HAVE
 DIFFICULTY BENDING OR STOOPING PER SEC.
 11-4.1.3(10)(A).
 5) SHT P-1 WATER HEATER DETAIL, THERMAL
 EXPANSION CONTROL REQUIRED PER SEC.
 607.3.2.
 6) SHT P-1 PLUMBING NOTES #'S 1 & 2
 REFER TO STANDARD CODE. THE CODE ADOPTED
 AND IN EFFECT IS THE FLORIDA BUILDING
 CODE PLUMBING. PLEASE CHANGE REFERENCE.
 7) SUBMIT A SANITARY RISER DIAGRAM AND A
 WATER RISER DIAGRAM FOR THE NEW LOUNGE
 SINK PER SEC. 104.3.1.1
 8) SHT P-1 DOMESTIC WATER RISER DIAGRAM,
 WATER HAMMER ARRESTORS AT FIXTURE P-4
 SHALL BE LOCATED NEAR THE FIXTURE IN AN
 "EFFECTIVE RANGE" NOT IN THE CEILING AS
 SHOWN. PDI-WH 201 & MANUF. INSTALLATION
 INSTRUCTIONS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]