Plan Review Details - Permit 04010513
Plan Review Stops For Permit 04010513
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2004-01-22 Cont ID  
Sent By btrobaug Date 2004-01-22 Time 11:51 Rev Time 0.50
Received By lsmith Date 2004-01-22 Time 13:20 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2004-01-22 Cont ID  
Sent By kstevens Date 2004-01-17 Time 14:01 Rev Time 0.33
Received By btrobaug Date 2004-01-22 Time 11:33 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-01-12 Cont ID  
Sent By csiegber Date 2004-01-12 Time 10:03 Rev Time 0.00
Received By csiegber Date 2004-01-12 Time 10:03 Sent To Z
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-01-22 Cont ID  
Sent By kstevens Date 2004-01-22 Time 14:39 Rev Time 0.25
Received By kstevens Date 2004-01-22 Time 14:39 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-01-17 Cont ID  
Sent By mmclean Date 2004-01-13 Time 12:58 Rev Time 0.50
Received By kstevens Date 2004-01-17 Time 14:01 Sent To E
Notes
2004-01-17 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
  
 SUBMITTAL REQUIRED:
 1) FBC-2001 424.2.14.2 WATER RETENTION,
 PROVIDE A POSITIVE MEANS OF RETAINING
 WATER IN THE HEATER WHEN PUMP IS SHUT
 OFF. (MANUFACTURE CUT SHEETS SUBMITTAL)
 2) FBC-2001 424.2.14.1 SWIMMING POOL
 WATER HEATERS SHALL BEAR THE LABEL OF A
 RECOGNIZED TESTING AGENCY. MANUFACTURE
 SHEETS REQUIRED. (SUBMITTAL)
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2004-01-13 Cont ID  
Sent By csiegber Date 2004-01-12 Time 10:03 Rev Time 0.00
Received By mmclean Date 2004-01-13 Time 12:58 Sent To P
Notes
***NONE***