| 2004-02-13 00:00:00 | DENIED |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) FBC* 1804.2.2AREA OF QUESTIONABLE |
| | SOIL.SUBMIT A GEOTECHNICAL REPORT |
| | TO VERIFY THE SAFE BEARING CAPACITY OF |
| | THE SOIL. |
| | |
| | 3)FBC 2405.2THE OVAL FIXED GLASS |
| | WINDOW IN THE MASTER BATH IS IN A |
| | 'HAZARDOUS LOCATION' AND IS REQUIRED TO |
| | BE SAFETY GLASS. INDICATE ON THE PLAN. |
| | |
| | 4) INDICATE THE LOCATION AND SIZE OF THE |
| | ATTIC ACCESS ON THE FLOOR PLAN. SEE |
| | FBC 2309.6. |
| | |
| | 5)1609.4.3 LOAD REDUCTION. |
| | WHEN STRUCTURAL EFFECTS DUE TO TWO OR |
| | MORE LOADS IN COMBINATION WITH DEAD LOAD |
| | ARE INVESTIGATED IN LOAD COMBINATIONS OF |
| | 1609.4.1 OR 1609.4.2, THE COMBINED |
| | EFFECTS DUE TO THE TWO OR LOADS MULTI- |
| | PLIED BY 0.75 PLUS EFFECTS DUE TO DEAD |
| | LOADS SHALL NOT BE LESS THAN THE EFFECTS |
| | FROM THE LOAD COMBINATION OF THE DEAD |
| | LOAD PLUS THE LOAD PRODUCING THE LARGEST |
| | EFFECTS. INCREAS IN ALLOWABLE STRESS SPE |
| | CIFIED IN THE MATERIALS SECTIONS OF THIS |
| | CODE OR A REFRENCED STANDARD SHALL NOT |
| | BE USED WITH THESE LOAD COMBINATIONS |
| | EXCEPT THAT A DURATION OF LOAD INCREASE |
| | SHALL BE PERMITTED IN ACCORDANCE WITH |
| | CHAPTER 23. |
| | REVISE THE TRUSS ANCHOR SCHEDULE ON |
| | SHEET 6. SEE CURRENT USP CATALOG FOR |
| | DOUBLE ANCHOR VALUES. SUBMIT STATE |
| | PRODUCT APPROVALS FOR THE TRUSS ANCHORS |
| | SPECIFIED ON THE PLANS. |
| | |
| | 6)PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | FORMS ATTACHMENTED. SUBMIT PROPER FORM |
| | FOR COLLIER GARAGE DOOR. QUALITY |
| | ASSURANCE IS REQUIRED. |
| | |
| | 7) THE SMALL GARAGE DOOR IS NOT COVERED |
| | BY THE PRODUCT APPROVAL THAT WAS |
| | SUBMITTED. IT IS SMALLER THAN THE |
| | MINIMUM DOOR SIZE LISTED ON THE DRAWING. |
| | |
| | 8) SPECIFY THE MOUNT TYPE AND ANCHORS |
| | THAT WILL BE USED FOR THE STORM PANELS. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |