| Plan Review Stops For Permit 04010359 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2004-07-02 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2004-07-02 |
Time |
11:50 |
Rev Time |
0.50 |
| Received By |
alange |
Date |
2004-07-02 |
Time |
11:50 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2004-06-25 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-07-02 |
Time |
09:38 |
Rev Time |
1.00 |
| Received By |
alange |
Date |
2004-06-25 |
Time |
15:41 |
Sent To |
|
|
| Notes |
| 2004-06-25 00:00:00 | DENIED | | | 1.SKYLIGHT PRODUCT APPROVAL NOT LISTED | | | ON THE DCA PRODUCT APPROVAL SITE. | | | NO PRODUCT APPROVALS SUBMITTED FOR | | | EXTERIOR DOORS. | | | PRODUCT APPROVALS SUBMITTED WITH | | | PERMIT APPLICATION AFTER OCTOBER 1, | | | 2003ARE REQUIRED TO COMPLY WITH THE | | | FLORIDA PRODUCT APPROVAL SYSTEM. FOR | | | INFORMATIONPLEASE SEE THE STATE WEBSITE | | | AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A COVER SHEET THAT LISTS | | | THE PRODUCT IDENTITY NUMBER FROM THE | | | STATE. IF THE PRODUCT DOES NOT HAVE | | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | | SPECIFIC FORM PER RULE 9B-72. SEE | | | ATTACHMENT. WWW.FLORIDABUILDING.ORG | | | | | | 2. THE NOTICE OF COMMENCEMENT SHALL BE | | | RECORDED AT PALM BEACH COUNTY | | | COURTHOUSEAND A COPY SUBMITTED TO THIS | | | OFFICE | | | BEFORE A PERMIT CAN BE ISSUED.BLANK | | | FORMS ARE AVAILABLE FROM THIS OFFICE. | | | | | | 3.MEAN ROOF HEIGHT IS STILL NOT | | | THE SAME THROUGH-OUT THE PLAN. | | | | | | ANY QUESTIONS CALL ME | | | | | | ART LANGE | | | BUILDING PLANS EXAMINER | | | 805-6672 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2004-06-17 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-06-23 |
Time |
21:27 |
Rev Time |
0.50 |
| Received By |
alange |
Date |
2004-06-17 |
Time |
13:14 |
Sent To |
|
|
| Notes |
| 2004-06-17 00:00:00 | DENIED | | | THIS THE 3RD TIME THESE SAME NOTES HAVE | | | BEEN POSTED. | | | | | | 1.SKYLIGHT PRODUCT APPROVAL NOT | | | LISTED ON THE DCA PRODUCT APPROVAL SITE. | | | IF YOU ARE NOT GOING TO HAVE A SKYLIGHT | | | PLEASE REMOVE IT FROM THE PLANS. | | | PRODUCT APPROVALS SUBMITTED WITH | | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 | | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | | PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A COVER SHEET THAT LISTS | | | THE PRODUCT IDENTITY NUMBER FROM THE | | | STATE. IF THE PRODUCT DOES NOT HAVE | | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | | SPECIFIC FORM PER RULE 9B-72. SEE | | | ATTACHMENT. WWW.FLORIDABUILDING.ORG | | | | | | 2. THE NOTICE OF COMMENCEMENT SHALL BE | | | RECORDED AT PALM BEACH COUNTY COURTHOUSE | | | AND A COPY SUBMITTED TO THIS OFFICE | | | BEFORE A PERMIT CAN BE ISSUED.BLANK | | | FORMS ARE AVAILABLE FROM THIS OFFICE. | | | | | | ANY QUESTIONS CALL ME | | | | | | ART LANGE | | | BUILDING PLANS EXAMINER | | | 805-6672 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2004-04-27 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-06-16 |
Time |
17:46 |
Rev Time |
1.00 |
| Received By |
alange |
Date |
2004-04-27 |
Time |
14:57 |
Sent To |
|
|
| Notes |
| 2004-04-27 00:00:00 | DENIED | | | 1. SKYLIGHT PRODUCT APPROVAL NOT LISTED | | | NO THE DCA PRODUCT APPROVAL SITE. | | | PRODUCT APPROVALS SUBMITTED WITH | | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 | | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | | PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A COVER SHEET THAT LISTS | | | THE PRODUCT IDENTITY NUMBER FROM THE | | | STATE. IF THE PRODUCT DOES NOT HAVE | | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | | SPECIFIC FORM PER RULE 9B-72. SEE | | | ATTACHMENT. WWW.FLORIDABUILDING.ORG | | | | | | 2. THE NOTICE OF COMMENCEMENT SHALL BE | | | RECORDED AT PALM BEACH COUNTY COURTHOUSE | | | AND A COPY SUBMITTED TO THIS OFFICE | | | BEFORE A PERMIT CAN BE ISSUED.BLANK | | | FORMS ARE AVAILABLE FROM THIS OFFICE. | | | | | | ANY QUESTIONS GIVE ME A CALL. | | | | | | ART LANGE | | | BUILDING PLANS EXAMINER | | | 805-6672 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2004-01-27 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-04-23 |
Time |
17:45 |
Rev Time |
1.25 |
| Received By |
alange |
Date |
2004-01-27 |
Time |
12:22 |
Sent To |
Z |
|
| Notes |
| 2004-01-27 00:00:00 | UNSAT | | | 1.SUBMIT PRODUCT APPROVAL FOR EXTERIOR | | | DOORS, SKYLIGHT AND SKY LIGHT | | | PROTECTION. | | | 2. THE NOTICE OF COMMENCEMENT SHALL BE | | | RECORDED AT PALM BEACH COUNTY COURTHOUSE | | | AND A COPY SUBMITTED TO THIS OFFICE | | | BEFORE A PERMIT CAN BE ISSUED.BLANK | | | FORMS ARE AVAILABLE FROM THIS OFFICE. | | | 3.SUBMIT A WINDOW AND DOOR BUCK DETAIL | | | 4.SUBMIT A SITE PLAN SHOWING LOCATION | | | OF EXISTING HOUSE IN RELATION TO STORAGE | | | BUILDING.SO THAT TABLE 600 ISSUES CAN | | | BE ADDRESSED. | | | 5.WHAT IS THE MEAN ROOF HEIGHT 8'-10 | | | OR 17'-7"?CORRECT ON PLAN. | | | | | | ART LANGE | | | BUILDING PLANS EXAMINER | | | 805-6672 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
P |
Date |
2004-07-02 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-07-02 |
Time |
09:38 |
Rev Time |
0.25 |
| Received By |
dpalmer |
Date |
2004-07-02 |
Time |
09:38 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
F |
Date |
2004-06-23 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-06-29 |
Time |
16:28 |
Rev Time |
0.25 |
| Received By |
dpalmer |
Date |
2004-06-23 |
Time |
21:27 |
Sent To |
B |
|
| Notes |
| 2004-06-23 00:00:00 | ******* UNSAT ******* | | | | | | PLEASE SEE REVISED ELECTRICAL WOULD BE | | | OK AND STAMPED, HOWEVER RAISED SEAL | | | BY ARCH IS NOT VISABLE AT ALL. | | | PLEASE SEE FS 481.221, SEAL MUST BE | | | RAISED ,CLEAR AND VISBLE. | | | ARCHITECT MAY COME DOWN TO BLDG DEPT | | | AND SEAL PLANS WITHOUT PLANS GOING | | | BACK AGAIN. | | | PLANS ARE BEING SENT TO BLDG REVIEW, | | | ABOVE COMMENT IS PENEDING THIS BEING | | | THE ONLY COMMENT FROM BLDG PLAN REVIEW. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2004-06-16 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-06-23 |
Time |
15:00 |
Rev Time |
0.33 |
| Received By |
dpalmer |
Date |
2004-06-16 |
Time |
17:45 |
Sent To |
B |
|
| Notes |
| 2004-06-16 00:00:00 | ************ UNSAT ********** | | | | | | PLEASE SEE NOTES FROM PREVIOUS TWO | | | REVIEWS. | | | | | | 1)NOTE: PLEASE SEE A SEPARATE 8 1/2X 11 | | | SHEET IS NOW BEING SUBMITTED SHOWING | | | A DIFFERENT RISER. | | | PLANS STILL DO NOT SHOW OR INDICATE IF | | | THIS NOW EXSITNG 60A SUB PANEL IS | | | LOCATED AT THIS DEATCHED GARAGE? | | | RISER NOW SHOWS THIS "EXISTING" 60A SUB- | | | -PANEL FEEDING A COTTAGE. | | | NO EQUIPMENT GRNDS ARE SHOWN, NO GROUND- | | | -ING ELECTRODE? PANEL SCHEDULE AND LOAD | | | FOR ADDED LOAD OF COTTAGE. | | | 215.5,225.31,250.32, ETC | | | PLEASE SUBMIT A RISER TO MEET CODE AND | | | CORRELATE WITH INFORMATION AS REQUESTED | | | ON PREVIOUS REVIEWS. | | | | | | PLEASE SEE COPY OF FS 553.80(2)(B) NOW | | | ATTACHED W/ RESPECT TO DESIGN PROFESSION | | | -AL. IF COMMENTS ARE NOT ADDRESS A 4X | | | FEE SHALL BE ACCESSED. | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | AS OF TODAYS DATE, ARCH/DESIGNER OF | | | RECORD AHS NOT CONTACTED MYSELF WITH | | | ANY QUESTIONS OR CLARIFICATION WHAT IS | | | NEEDED. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2004-04-23 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-06-16 |
Time |
12:02 |
Rev Time |
0.33 |
| Received By |
dpalmer |
Date |
2004-04-23 |
Time |
17:44 |
Sent To |
B |
|
| Notes |
| 2004-04-23 00:00:00 | ************ UNSAT ************ | | | | | | 1)NOTE: PLEASE PROVIDE RISER DIAGRAM | | | WITH FEED TO DETACHED STRUCTURE. | | | EXISTING RISER DOES NOT SHOW ANY INFOR- | | | -MATION ON HOW BLDG WILL BE FED. | | | CONDUITS/CONDCUTORS/ GROUNDING/ PANEL | | | DISC MEANS. ETC . | | | 225.31,250.32,215.5 ETC. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] | | | REVIEW. A RESUB FEE WILL NOT BE DUE. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2004-01-15 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-02-04 |
Time |
10:28 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2004-01-15 |
Time |
07:50 |
Sent To |
B |
|
| Notes |
| 2004-01-15 00:00:00 | | | | PROVISO | | | ~~~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE NOTE THAT AN ELECTRICAL PERMIT | | | IS REQUIRED FOR THIS WORK.THE SEPERATE | | | STRUCTURE MUST COMPLY WITH 225.31 FOR | | | DISCONNECTING MEANS AND 250.32 FOR | | | GROUNDING.IF THIS BUILDING IS NOT IN | | | COMPLIANCE,IT SHALL BE MADE TO COMPLY | | | BY THE ELECTRICAL CONTRACTOR WHOM WILL | | | SUBMIT A RISER DIAGRAM INDICATING | | | COMPLIANCE AT TIME OF APPLICATION. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2004-06-29 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-06-29 |
Time |
16:28 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-06-29 |
Time |
16:28 |
Sent To |
E |
|
| Notes |
| 2004-06-29 00:00:00 | TO DP DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2004-06-23 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-06-23 |
Time |
15:00 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-06-23 |
Time |
15:00 |
Sent To |
E |
|
| Notes |
| 2004-06-23 00:00:00 | TODP DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2004-06-09 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-06-16 |
Time |
11:23 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-06-09 |
Time |
11:24 |
Sent To |
E |
|
| Notes |
| 2004-06-16 00:00:00 | TO DP DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2004-04-20 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-04-20 |
Time |
16:30 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-04-20 |
Time |
16:30 |
Sent To |
Z |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2004-01-09 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2004-02-02 |
Time |
16:58 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-01-09 |
Time |
08:49 |
Sent To |
E |
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2004-04-22 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2004-04-22 |
Time |
12:19 |
Rev Time |
0.25 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2004-02-02 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-04-20 |
Time |
16:30 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2004-02-02 |
Time |
16:57 |
Sent To |
I |
|
| Notes |
| 2004-02-02 00:00:00 | DENIED, NEED TWO COPY OF SURVEY SHOWING | | | THE LOCATION OF THE RENOVATED BLDG | | | CALLED LEFT MSG MM |
|
|