Plan Review Details - Permit 04010359
Plan Review Stops For Permit 04010359
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2004-07-02 Cont ID  
Sent By alange Date 2004-07-02 Time 11:50 Rev Time 0.50
Received By alange Date 2004-07-02 Time 11:50 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2004-06-25 Cont ID  
Sent By dpalmer Date 2004-07-02 Time 09:38 Rev Time 1.00
Received By alange Date 2004-06-25 Time 15:41 Sent To  
Notes
2004-06-25 00:00:00DENIED
 1.SKYLIGHT PRODUCT APPROVAL NOT LISTED
 ON THE DCA PRODUCT APPROVAL SITE.
 NO PRODUCT APPROVALS SUBMITTED FOR
 EXTERIOR DOORS.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1,
 2003ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATIONPLEASE SEE THE STATE WEBSITE
 AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 2. THE NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY
 COURTHOUSEAND A COPY SUBMITTED TO THIS
 OFFICE
 BEFORE A PERMIT CAN BE ISSUED.BLANK
 FORMS ARE AVAILABLE FROM THIS OFFICE.
  
 3.MEAN ROOF HEIGHT IS STILL NOT
 THE SAME THROUGH-OUT THE PLAN.
  
 ANY QUESTIONS CALL ME
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2004-06-17 Cont ID  
Sent By dpalmer Date 2004-06-23 Time 21:27 Rev Time 0.50
Received By alange Date 2004-06-17 Time 13:14 Sent To  
Notes
2004-06-17 00:00:00DENIED
 THIS THE 3RD TIME THESE SAME NOTES HAVE
 BEEN POSTED.
  
 1.SKYLIGHT PRODUCT APPROVAL NOT
 LISTED ON THE DCA PRODUCT APPROVAL SITE.
 IF YOU ARE NOT GOING TO HAVE A SKYLIGHT
 PLEASE REMOVE IT FROM THE PLANS.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 2. THE NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY COURTHOUSE
 AND A COPY SUBMITTED TO THIS OFFICE
 BEFORE A PERMIT CAN BE ISSUED.BLANK
 FORMS ARE AVAILABLE FROM THIS OFFICE.
  
 ANY QUESTIONS CALL ME
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-04-27 Cont ID  
Sent By dpalmer Date 2004-06-16 Time 17:46 Rev Time 1.00
Received By alange Date 2004-04-27 Time 14:57 Sent To  
Notes
2004-04-27 00:00:00DENIED
 1. SKYLIGHT PRODUCT APPROVAL NOT LISTED
 NO THE DCA PRODUCT APPROVAL SITE.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 2. THE NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY COURTHOUSE
 AND A COPY SUBMITTED TO THIS OFFICE
 BEFORE A PERMIT CAN BE ISSUED.BLANK
 FORMS ARE AVAILABLE FROM THIS OFFICE.
  
 ANY QUESTIONS GIVE ME A CALL.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-01-27 Cont ID  
Sent By dpalmer Date 2004-04-23 Time 17:45 Rev Time 1.25
Received By alange Date 2004-01-27 Time 12:22 Sent To Z
Notes
2004-01-27 00:00:00UNSAT
 1.SUBMIT PRODUCT APPROVAL FOR EXTERIOR
 DOORS, SKYLIGHT AND SKY LIGHT
 PROTECTION.
 2. THE NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY COURTHOUSE
 AND A COPY SUBMITTED TO THIS OFFICE
 BEFORE A PERMIT CAN BE ISSUED.BLANK
 FORMS ARE AVAILABLE FROM THIS OFFICE.
 3.SUBMIT A WINDOW AND DOOR BUCK DETAIL
 4.SUBMIT A SITE PLAN SHOWING LOCATION
 OF EXISTING HOUSE IN RELATION TO STORAGE
 BUILDING.SO THAT TABLE 600 ISSUES CAN
 BE ADDRESSED.
 5.WHAT IS THE MEAN ROOF HEIGHT 8'-10
 OR 17'-7"?CORRECT ON PLAN.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2004-07-02 Cont ID  
Sent By dpalmer Date 2004-07-02 Time 09:38 Rev Time 0.25
Received By dpalmer Date 2004-07-02 Time 09:38 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2004-06-23 Cont ID  
Sent By csiegber Date 2004-06-29 Time 16:28 Rev Time 0.25
Received By dpalmer Date 2004-06-23 Time 21:27 Sent To B
Notes
2004-06-23 00:00:00******* UNSAT *******
  
 PLEASE SEE REVISED ELECTRICAL WOULD BE
 OK AND STAMPED, HOWEVER RAISED SEAL
 BY ARCH IS NOT VISABLE AT ALL.
 PLEASE SEE FS 481.221, SEAL MUST BE
 RAISED ,CLEAR AND VISBLE.
 ARCHITECT MAY COME DOWN TO BLDG DEPT
 AND SEAL PLANS WITHOUT PLANS GOING
 BACK AGAIN.
 PLANS ARE BEING SENT TO BLDG REVIEW,
 ABOVE COMMENT IS PENEDING THIS BEING
 THE ONLY COMMENT FROM BLDG PLAN REVIEW.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2004-06-16 Cont ID  
Sent By csiegber Date 2004-06-23 Time 15:00 Rev Time 0.33
Received By dpalmer Date 2004-06-16 Time 17:45 Sent To B
Notes
2004-06-16 00:00:00************ UNSAT **********
  
 PLEASE SEE NOTES FROM PREVIOUS TWO
 REVIEWS.
  
 1)NOTE: PLEASE SEE A SEPARATE 8 1/2X 11
 SHEET IS NOW BEING SUBMITTED SHOWING
 A DIFFERENT RISER.
 PLANS STILL DO NOT SHOW OR INDICATE IF
 THIS NOW EXSITNG 60A SUB PANEL IS
 LOCATED AT THIS DEATCHED GARAGE?
 RISER NOW SHOWS THIS "EXISTING" 60A SUB-
 -PANEL FEEDING A COTTAGE.
 NO EQUIPMENT GRNDS ARE SHOWN, NO GROUND-
 -ING ELECTRODE? PANEL SCHEDULE AND LOAD
 FOR ADDED LOAD OF COTTAGE.
 215.5,225.31,250.32, ETC
 PLEASE SUBMIT A RISER TO MEET CODE AND
 CORRELATE WITH INFORMATION AS REQUESTED
 ON PREVIOUS REVIEWS.
  
 PLEASE SEE COPY OF FS 553.80(2)(B) NOW
 ATTACHED W/ RESPECT TO DESIGN PROFESSION
 -AL. IF COMMENTS ARE NOT ADDRESS A 4X
 FEE SHALL BE ACCESSED.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
 AS OF TODAYS DATE, ARCH/DESIGNER OF
 RECORD AHS NOT CONTACTED MYSELF WITH
 ANY QUESTIONS OR CLARIFICATION WHAT IS
 NEEDED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-04-23 Cont ID  
Sent By csiegber Date 2004-06-16 Time 12:02 Rev Time 0.33
Received By dpalmer Date 2004-04-23 Time 17:44 Sent To B
Notes
2004-04-23 00:00:00************ UNSAT ************
  
 1)NOTE: PLEASE PROVIDE RISER DIAGRAM
 WITH FEED TO DETACHED STRUCTURE.
 EXISTING RISER DOES NOT SHOW ANY INFOR-
 -MATION ON HOW BLDG WILL BE FED.
 CONDUITS/CONDCUTORS/ GROUNDING/ PANEL
 DISC MEANS. ETC .
 225.31,250.32,215.5 ETC.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
 REVIEW. A RESUB FEE WILL NOT BE DUE.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2004-01-15 Cont ID  
Sent By csiegber Date 2004-02-04 Time 10:28 Rev Time 0.50
Received By btrobaug Date 2004-01-15 Time 07:50 Sent To B
Notes
2004-01-15 00:00:00 
 PROVISO
 ~~~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE NOTE THAT AN ELECTRICAL PERMIT
 IS REQUIRED FOR THIS WORK.THE SEPERATE
 STRUCTURE MUST COMPLY WITH 225.31 FOR
 DISCONNECTING MEANS AND 250.32 FOR
 GROUNDING.IF THIS BUILDING IS NOT IN
 COMPLIANCE,IT SHALL BE MADE TO COMPLY
 BY THE ELECTRICAL CONTRACTOR WHOM WILL
 SUBMIT A RISER DIAGRAM INDICATING
 COMPLIANCE AT TIME OF APPLICATION.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-06-29 Cont ID  
Sent By csiegber Date 2004-06-29 Time 16:28 Rev Time 0.00
Received By csiegber Date 2004-06-29 Time 16:28 Sent To E
Notes
2004-06-29 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-06-23 Cont ID  
Sent By csiegber Date 2004-06-23 Time 15:00 Rev Time 0.00
Received By csiegber Date 2004-06-23 Time 15:00 Sent To E
Notes
2004-06-23 00:00:00TODP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-06-09 Cont ID  
Sent By csiegber Date 2004-06-16 Time 11:23 Rev Time 0.00
Received By csiegber Date 2004-06-09 Time 11:24 Sent To E
Notes
2004-06-16 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-04-20 Cont ID  
Sent By csiegber Date 2004-04-20 Time 16:30 Rev Time 0.00
Received By csiegber Date 2004-04-20 Time 16:30 Sent To Z
Notes
2004-04-20 00:00:00RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-01-09 Cont ID  
Sent By mmclean Date 2004-02-02 Time 16:58 Rev Time 0.00
Received By csiegber Date 2004-01-09 Time 08:49 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2004-04-22 Cont ID  
Sent By sgraham Date 2004-04-22 Time 12:19 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2004-02-02 Cont ID  
Sent By csiegber Date 2004-04-20 Time 16:30 Rev Time 0.00
Received By mmclean Date 2004-02-02 Time 16:57 Sent To I
Notes
2004-02-02 00:00:00DENIED, NEED TWO COPY OF SURVEY SHOWING
 THE LOCATION OF THE RENOVATED BLDG
 CALLED LEFT MSG MM