Plan Review Details - Permit 04010310
Plan Review Stops For Permit 04010310
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2004-06-02 Cont ID  
Sent By shill Date 2004-06-02 Time 07:47 Rev Time 0.50
Received By shill Date 2004-06-02 Time 07:38 Sent To  
Notes
2004-06-02 00:00:00REVISED AREA CALCS, 2 PAGES

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2004-05-14 Cont ID  
Sent By csiegber Date 2004-05-19 Time 13:13 Rev Time 0.50
Received By shill Date 2004-05-14 Time 15:57 Sent To  
Notes
2004-05-14 00:00:00**PROVISO**SUBMIT REVISED A1 SHOWING
 CORRECT AREA CALCULATIONS

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2004-05-14 Cont ID  
Sent By shill Date 2004-05-14 Time 07:37 Rev Time 1.50
Received By shill Date 2004-05-14 Time 07:37 Sent To  
Notes
2004-05-14 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)THE SQUARE FOOTAGE ON THE ENERGY
 CALCS IS INCORRECT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2004-04-20 Cont ID  
Sent By csiegber Date 2004-05-03 Time 09:26 Rev Time 2.00
Received By shill Date 2004-04-20 Time 14:44 Sent To  
Notes
2004-04-20 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)BEDROOMS ARE TO COMPLY WITH
 EMERGENCY EGRESS REQUIREMENTS,
 FBC1005.4.A SINGLE HUNG 24 DOES NOT
 COMPLY.
  
 2.)FLORIDA STATEWIDE, LOCAL OR
 SITE SPECIFIC PRODUCT APPROVALS
 REQUIRED IN ADDITION TO THE TEST
 REPORTS PROVIDED.WWW.FLORIDABUILDING.
 ORG.
  
 3.)PRODUCT APPROVALS FOR THE ARCHED
 WINDOW, MULLION, AND EXTERIOR DOOR HAVE
 NOT BEEN PROVIDED.SEPARATE PERMITS
 WILL BE REQUIRED IF THEY ARE NOT
 SUBMITTED BEFORE PERMIT ISSUANCE.
  
 4.)THE PRINTED LICENSE NUMBER OF THE
 PERSON SEALING THE PLAN IS TO BE ON
 EACH SHEET, FAC61G1-16.003, 004.
  
 5.)THE NOTICE OF COMMENCEMENT IS
 EXPIRED (90 DAYS WITHOUT COMMENCING
 WORK), FS713.13.
  
 ***NO RESUB FEE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-03-19 Cont ID  
Sent By csiegber Date 2004-04-13 Time 10:01 Rev Time 0.00
Received By hpiskura Date 2004-03-19 Time 07:12 Sent To  
Notes
2004-03-19 00:00:00A COPY OF THE COMMENTS FOR PERMIT
 #04010304 IS ATTACHED, SINCE THEY ARE
 COMPANION APPLICATIONS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-02-10 Cont ID  
Sent By pkrauss Date 2004-03-08 Time 14:51 Rev Time 0.00
Received By hpiskura Date 2004-02-10 Time 18:37 Sent To  
Notes
2004-02-10 00:00:00A COPY OF THE COMMENTS FROM PERMIT
 APPLICATION 04010304 IS ATTACHED SINCE
 THEY ARE THE SAME AND COMPANION PERMIT
 APPLICATIONS.
  
 ALSO, THERE IS A HOLD FOR UNPAID
 DEMOLITON FEES TO BE ADDRESSED.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-03-03 Cont ID  
Sent By dpalmer Date 2004-03-03 Time 07:32 Rev Time 0.50
Received By dpalmer Date 2004-03-03 Time 07:21 Sent To P
Notes
2004-03-03 00:00:00*** NO LOW VOLTAGE INCLUDED***
  
 REDLINED SD'S, TO BE INSTALLED PER
 NFPA-72 8-1.4.2

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-01-22 Cont ID  
Sent By csiegber Date 2004-02-25 Time 12:46 Rev Time 1.00
Received By dpalmer Date 2004-01-22 Time 13:25 Sent To M
Notes
2004-01-22 00:00:00***************** UNSAT ****************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
 SHOWN FOR PANEL , NOT FOR MAIN.
  
 2)NOTE:SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ON EACH LEVEL OF A MULTI-LEVEL DWELLING
 UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER:FBC 905.2, NFPA-72 8-1.4
 MISSING INSIDE BEDROOMS.
  
 3 )NOTE: PLEASE SHOW /CLARIFY METHOD
 OF THE EQUIPMENT GROUNDING BETWEEN
 MAIN MEANS OOF DISC AND PANELS/GUTTERS.
 250.110,250.24
 PLEASE SIZE ALL EQUIPMENT GROUNDING
 CONDUCTORS PER 250.122
  
 4)NOTE; PLEASE SHOW SEC'S ON RISER TO
 WEATHERHEAD.
  
 5)NOTE: PLEASE SEE NOTES BELOW RISER/
 PANEL SCHEDULE. SHOWS CITY OF FT LAUDER-
 -DALE. PLEASE ADJUST TO CITY OF WPB.
  
 6)NOTE: PLEASE VERIFY SIZE OF PANEL,
 SHOWN AS 42 CIR, AND 150A. PLEASE SEE
 IF 150A PANELS ARE MADE AS 42 CIR.
  
 7)NOTE: PLEASE SEE THE FOLLOWING IS ONLY
 AN FYI NOTE: IF THERE IS GOING TO BE
 ANY LV IN HOUSE(TV/PHONE) ETC. PLEASE
 SHOW ON PLANS, OR SEPARATE PLANS WILL
 BE REQ'D AT LATER DATE.
 SEPARATE LV PERMIT WILL BE REQ'D.
  
 8)NOTE: PLEASE PROVIDE ALL LICENSE #'S
 ON TITLE BLOCK AS REQD' UNDER FS/ FAC
 PLEASE ALSO SIGN WITH A MIN OF A VISABLE
 FIRST AND LAST NAME AS SHOWN ON SAID
 SEAL. IT HAAS BEEN TRANSLATED TO THIS
 OFFICE THAT INITAILS ARE NOT PERMITTED.
 481.221, 61G1-16.004
 SIGNATURE WOULD NEED TO MATCH LICENSE
 SIGNED W/ STATE.
 481.221,
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2004-05-21 Cont ID  
Sent By shill Date 2004-05-21 Time 13:00 Rev Time 0.00
Received By shill Date 2004-05-21 Time 13:00 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2004-05-19 Cont ID  
Sent By csiegber Date 2004-05-19 Time 13:13 Rev Time 0.00
Received By csiegber Date 2004-05-19 Time 13:13 Sent To B
Notes
2004-05-19 00:00:00TO SH DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2004-05-03 Cont ID  
Sent By csiegber Date 2004-05-03 Time 09:26 Rev Time 0.00
Received By csiegber Date 2004-05-03 Time 09:26 Sent To B
Notes
2004-05-03 00:00:00TO SH DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-04-30 Cont ID  
Sent By mmclean Date 2004-04-30 Time 17:53 Rev Time 0.00
Received By csiegber Date 2004-04-30 Time 08:58 Sent To Z
Notes
2004-04-30 00:00:00RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-04-13 Cont ID  
Sent By csiegber Date 2004-04-13 Time 10:01 Rev Time 0.00
Received By csiegber Date 2004-04-13 Time 10:01 Sent To B
Notes
2004-04-13 00:00:00TO SH DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-04-06 Cont ID  
Sent By mmclean Date 2004-04-09 Time 16:24 Rev Time 0.00
Received By csiegber Date 2004-04-06 Time 14:09 Sent To Z
Notes
2004-04-06 00:00:00RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-02-25 Cont ID  
Sent By csiegber Date 2004-02-25 Time 12:40 Rev Time 0.00
Received By csiegber Date 2004-02-25 Time 12:40 Sent To E
Notes
2004-02-25 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-02-10 Cont ID  
Sent By mmclean Date 2004-02-25 Time 12:40 Rev Time 0.00
Received By csiegber Date 2004-01-09 Time 07:41 Sent To  
Notes
2004-01-12 00:00:001/9/04 TO Z
 TO SFD RACK/E

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-03-08 Cont ID  
Sent By kstevens Date 2004-03-04 Time 18:02 Rev Time 0.25
Received By pkrauss Date 2004-03-08 Time 12:37 Sent To B
Notes
2004-03-08 00:00:00PROVISO:
 THE TRANSFER AIR GRILLE FROM THE MASTER
 BEDROOM IS NOT SIZED PROPERLY.ALL AIR
 INTO THE MASTER SUITE (INCLUDE BATHROOM)
 FOR A "TOTAL" OF SUPPLY AIR.TRANSFER
 IS TO BE SIZED 50 SQ IN TO 100 CFM OF
 SUPPLY AIR.PLEASE SIZE ACCORDINGLY.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-01-30 Cont ID  
Sent By dpalmer Date 2004-01-22 Time 13:25 Rev Time 0.33
Received By pkrauss Date 2004-01-30 Time 07:31 Sent To P
Notes
2004-01-30 00:00:00DENIED:
 2001 FBC(M) 601.4 BALANCED RETURN AIR
 EXCEPTION 1 THROUGH 3:
  
 RETURN AIR FROM THE BEDROOM AREAS
 REQURIED.SEE THE ATTACHED SCHEDULE
 FOR PROPER SIZING.INDICATE ON THE
 WHICH RETURN AIR METHOD WILL BE USED -
 DUCTED, RETURN AIR JUMPER OR TRANSFER
 GRILLES.INDICATE DUCT AND GRILLE SIZE
 ON THE PLAN.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-03-04 Cont ID  
Sent By dpalmer Date 2004-03-03 Time 07:33 Rev Time 0.33
Received By kstevens Date 2004-03-04 Time 18:02 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2004-02-03 Cont ID  
Sent By pkrauss Date 2004-01-30 Time 07:34 Rev Time 0.25
Received By jleech Date 2004-02-03 Time 09:33 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2004-04-30 Cont ID  
Sent By shill Date 2004-05-21 Time 13:00 Rev Time 0.00
Received By mmclean Date 2004-04-30 Time 17:53 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2004-04-09 Cont ID  
Sent By csiegber Date 2004-04-30 Time 08:58 Rev Time 0.00
Received By mmclean Date 2004-04-09 Time 16:24 Sent To I
Notes
2004-04-09 00:00:00DENIED, NEED TO REDUCE CONCRETE WALK &
 DRIVEWAY TO MEET THE ZONING REQUIRMENT
 FOR LANDSCAPE.EG: REDUCE CONRETE
 WALK TO 2FT & DRIVEWAY TO 8FT).CALLED
 CONTR LEFT MSG MM

Review Stop Z ZONING
Rev No 1 Status F Date 2004-01-09 Cont ID  
Sent By csiegber Date 2004-04-06 Time 14:09 Rev Time 0.00
Received By mmclean Date 2004-01-09 Time 15:49 Sent To I
Notes
2004-01-09 00:00:00DENIED, NEED TO MEET THE FRONT & REAR
 SETBACK CALLED CONTR LEFT MSG MM


Account Summary | Usage Policy | Privacy Policy