Plan Review Details - Permit 04010304
Plan Review Stops For Permit 04010304
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2004-06-02 Cont ID  
Sent By shill Date 2004-06-02 Time 08:02 Rev Time 0.50
Received By shill Date 2004-06-02 Time 07:35 Sent To  
Notes
2004-06-02 00:00:00REVISED AREA CALCS, SHEET A1 AND SITE
 PLAN

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2004-05-04 Cont ID  
Sent By csiegber Date 2004-05-19 Time 13:30 Rev Time 2.00
Received By shill Date 2004-05-04 Time 15:21 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2004-04-22 Cont ID  
Sent By csiegber Date 2004-04-30 Time 08:59 Rev Time 0.50
Received By shill Date 2004-04-22 Time 09:47 Sent To  
Notes
2004-04-22 00:00:00****CORRECTIONS****
  
 SEE ATTACHED CHECKLIST FOR 04010310;
 SAME COMMENTS.
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-03-19 Cont ID  
Sent By csiegber Date 2004-04-14 Time 16:12 Rev Time 0.00
Received By hpiskura Date 2004-03-19 Time 06:42 Sent To  
Notes
2004-03-19 00:00:00SECOND CHECKLIST
  
 AS PREVIOUSLY NOTED, IMPACT FEES MUST BE
 PAID TO THE COUNTY BEFORE A PERMIT MAY
 BE ISSUED.
  
 THE 2001 FLORIDA BUILDING CODE WITH THE
 2003 REVISIONS IS CURRENTLY INVOKED IN
 THE STATE OF FLORIDA.
  
 WEST PALM BEACH IS IN THE 140 MPH WIND
 ZONE, HOWEVER THE HVHZ IS APPLICABLE
 ONLY TO BROWARD AND DADE COUNTIES.SEE
 FBC 202 DEFINITIONS.
  
 ALSO PLEASE NOTE AND ENSURE COMPLIANCE
 WITH THE MINIMAL DESIGN CRITERIA IN FBC
 1606.1.7.THE IMPORTANCE AND EXPOSURE
 FACTORS ARE STILL ABSENT FROM THE PLANS
 AND WIND PRESSURE ZONES 1,2&3,
 (COMPONENTS AND CLADDING) ARE NOT SHOWN.
  
 PLEASE REMOVE ANY OUTDATED OR
 SUPERFLUOUS PAGES FROM THE PLANS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-02-10 Cont ID  
Sent By pkrauss Date 2004-03-09 Time 16:33 Rev Time 0.00
Received By hpiskura Date 2004-02-10 Time 17:40 Sent To  
Notes
2004-02-10 00:00:00BEFORE A PERMIT TO CONSTRUCT MAY BE
 ISSUED IMPACT FEES MUST BE PAID TO THE
 COUNTY, THE PERMIT PLANS STAMPED BY
 THAT OFFICE AND A COPY OF THE PAID
 RECEIPT ATTACHED TO THE PERMIT
 APPLICATION.CALL 561-233-5025 FOR
 MORE INFORMATION.
  
 A COPY OF THE RECORDED NOTICE OF
 COMMENCEMENT MUST BE PROVIDED BEFORE
 THE PERMIT MAY BE ISSUED.
  
 THE SOUTHERN METAL PRODUCTS SHUTTER NOA
 HAS SOME ILLEGIBLE PAGES AND THE
 COMPONENTS AND FASTENERS HAVE NOT BEEN
 SELECTED.PLEASE CORRECT AS NECESSARY.
  
 THE CODE AND DESIGN CRITERIA ARE NOT
 SHOWN ON THE PLANS.SEE FBC 1606.1.7.
  
 SHOW THE DESIGN LOADS FOR THE DELEGATED
 TRUSS ENGINEERING AND SEE FBC TABLE
 1604.1 DWELLINGS, ATTICS WITH OUT
 STORAGE, MINIMUM 10# LIVE LOAD NOT SHOWN
 ON TRUSS ENGINEERING.
  
 SHOW THE MIN/MAX FINISHED FLOOR
 ELEVATION AND LOT DRAINAGE. SEE FBC
 1804.1.7 AS AMENDED BY THE CITY OF WEST
 PALM BEACH.(COPY ATTACHED)
  
 SHOW A NOTE OR DETAIL FOR TERMINATION OF
 THE #5 IN THE FILLED CELLS AT THE
 FOUNDATION AND TIE BEAM.SEE FBC 104.2.
  
 PLEASE PROVIDE A CALCULATION FOR THE
 ATTIC VENTING, FBC 2309.7, INCLUDE THE
 FREE AREA OF THE SCREENED VENTS.
  
 THE DECLARED PERMIT VALUATION OF
 $60,000.00 IS TOO LOW FOR THIS SCOPE OF
 WORK.THE CITY'S ESTIMATE IS
 $79,901.00.PLEASE PAY AN ADDITIONAL
 $201.00 PERMIT FEE.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-03-03 Cont ID  
Sent By dpalmer Date 2004-03-03 Time 06:56 Rev Time 0.33
Received By dpalmer Date 2004-03-03 Time 06:55 Sent To P
Notes
2004-03-03 00:00:00** NO LOW VOLTAGE ON PLANS***
 SEPARATE PERMIT AND PLANS REQUIRED.
  
 RED LINED REQUIREMENTS PER NFPA-72 8-1.
 4.2
  
 DINING RM RECEPTS SHOWN AS GFCI?

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-01-22 Cont ID  
Sent By csiegber Date 2004-02-25 Time 13:23 Rev Time 1.00
Received By dpalmer Date 2004-01-22 Time 12:05 Sent To M
Notes
2004-01-22 00:00:00********** UNSAT *************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
 SHOWN FOR PANEL ONLY.
  
 2)NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ON EACH LEVEL OF A MULTI-LEVEL DWELLING
 UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER:FBC 905.2, NFPA-72 8-1.4
 SEE INSIDE ALL SLEEPING RMS.
  
 3)NOTE: PLEASE SHOW /CLARIFY METHOD
 OF THE EQUIPMENT GROUNDING BETWEEN
 MAIN MEANS OF DISC AND PANELS/GUTTERS.
 250.110,250.24
 PLEASE SIZE ALL EQUIPMENT GROUNDING
 CONDUCTORS PER 250.122
  
 4)NOTE: PLEASE SHOW SEC'S FOR RISER
 UP TO WEATHER HEAD.
  
 5)NOTE: PLEASE SEE NOTE BELOW LOAD CALCS
 MENTION "CITY IF FT LAUDERDALE"
 PLANS SUBMITTED FOR PERMIT UNDER CITY
 OF WEST PALM BEACH.
  
 6)NOTE: PLEASE VERIFY SIZE OF PANEL.
 SHOWN AS 42 CIRCUIT 150A PANEL. PLEASE
 VERIFY 150A MADE FOR 42 CIRCUITS.
  
 7)NOTE: THE FOLLOWING IS ONLY A FYI
 COMMENT: IF THERE IS GOING TO BE "ANY"
 LV IN HOUSE, IE: TV, PHONE, ETC,
 PLEASE SHOW, OR SEPARATE PLANS WILL BE
 REQ'D AT LATER DATE.
 SEPRATE PERMITS ARE ALSO REQ'D.
  
 8)NOTE: PLEASE PROVIDE ALL LICENSE #'S
 ON TITLE BLOCKS AS REQ'D UNDER FS 481,
 481.219 AND FAC 61G1-16.004.
 PLEASE ALSO SIGN WITH SIGNATURE THAT IS
 VISABLE WITH FIRST AND LAST NAME/ AS ON
 SAID SEAL. INITIALS ARE NOT PERMITTED.
 PLEASE NOTE: THE STATE BOARDS , DBPR AND
 FBPE'S FS/FAC REQUIRES NAME TO BE SIGNED
 AS SIGNED ON LICENSE WITH STATE.
 IF NAME IS SIGNED AS SHOWN , PLEASE
 PROVIDE COPY TO VERIFY. PLEASE DATE WITH
 SIGNATURE AS REQ'D. FS 481.221
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
 PLEASE SEE THAT NOTE #8 IS FOR ALL TRADE
 S WEATHER OR NOT COMMENT IS MADE BY
 OTHER REVIEWERS.

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2004-05-21 Cont ID  
Sent By shill Date 2004-05-21 Time 11:50 Rev Time 0.00
Received By shill Date 2004-05-21 Time 11:50 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-05-19 Cont ID  
Sent By csiegber Date 2004-05-19 Time 13:30 Rev Time 0.00
Received By csiegber Date 2004-05-19 Time 13:30 Sent To B
Notes
2004-05-19 00:00:00TO SH DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-04-30 Cont ID  
Sent By csiegber Date 2004-04-30 Time 08:59 Rev Time 0.00
Received By csiegber Date 2004-04-30 Time 08:59 Sent To B
Notes
2004-04-30 00:00:00TO SH DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-04-14 Cont ID  
Sent By csiegber Date 2004-04-14 Time 16:12 Rev Time 0.00
Received By csiegber Date 2004-04-14 Time 16:12 Sent To B
Notes
2004-04-14 00:00:00TO SH DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-02-25 Cont ID  
Sent By csiegber Date 2004-02-25 Time 13:23 Rev Time 0.00
Received By csiegber Date 2004-02-25 Time 13:22 Sent To E
Notes
2004-02-25 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-02-10 Cont ID  
Sent By mmclean Date 2004-01-09 Time 15:57 Rev Time 0.00
Received By csiegber Date 2004-01-09 Time 07:35 Sent To  
Notes
2004-01-12 00:00:00TO SFD RACK/E
2004-01-09 00:00:00TO Z

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-03-09 Cont ID  
Sent By kstevens Date 2004-03-04 Time 17:49 Rev Time 0.33
Received By pkrauss Date 2004-03-09 Time 16:27 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-01-29 Cont ID  
Sent By dpalmer Date 2004-03-03 Time 06:58 Rev Time 0.50
Received By hmoser Date 2004-01-29 Time 16:40 Sent To P
Notes
2004-01-29 00:00:00PLAN DENIED
 1) REFER TO SECTION 307.2.3 AUXILIARY
 DRAIN PAN.AUXILIARY DRAIN PANS SHALL BE
 INSTALLED UNDER ALL COILS ON WITCH
 CONDENSATION WILL OCCUR.
 2) RETURN AIR REQUIREMENTS TO COMPLY
 WITH THE FLORIDA BUILDING CODE (M) 2003
 CHANGES.CHANGES WENT INTO EFFECT JULY 1
 2003
 PLAN REVIEW BY HAROLD MOSER
 (561)805-6732

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-03-04 Cont ID  
Sent By kstevens Date 2004-03-04 Time 17:48 Rev Time 0.33
Received By kstevens Date 2004-03-04 Time 17:48 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2004-02-03 Cont ID  
Sent By dpalmer Date 2004-03-03 Time 07:01 Rev Time 0.33
Received By jleech Date 2004-02-03 Time 10:27 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2004-01-09 Cont ID  
Sent By shill Date 2004-05-21 Time 11:50 Rev Time 0.00
Received By mmclean Date 2004-01-09 Time 15:57 Sent To I
Notes
***NONE***