Plan Review Details - Permit 04010301
Plan Review Stops For Permit 04010301
Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-02-12 Cont ID  
Sent By pkrauss Date 2004-02-12 Time 16:01 Rev Time 0.00
Received By pkrauss Date 2004-02-12 Time 16:00 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-01-20 Cont ID  
Sent By csiegber Date 2004-01-20 Time 11:21 Rev Time 0.00
Received By csiegber Date 2004-01-20 Time 11:21 Sent To P
Notes
2004-01-20 00:00:00TO KS BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-01-08 Cont ID  
Sent By csiegber Date 2004-01-08 Time 11:14 Rev Time 0.00
Received By csiegber Date 2004-01-08 Time 11:14 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-01-24 Cont ID  
Sent By pkrauss Date 2004-02-12 Time 16:01 Rev Time 0.60
Received By kstevens Date 2004-01-24 Time 13:03 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-01-15 Cont ID  
Sent By csiegber Date 2004-01-20 Time 11:21 Rev Time 1.00
Received By kstevens Date 2004-01-15 Time 18:42 Sent To  
Notes
2004-01-15 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1) SUBMIT DETAILS FOR DRINKING FOUNTAINS
 PER 11-4.15 AND ALL SUBSECTIONS. ALSO
 SECTION 11-4.1.3(10)(A) PROVISIONS FOR
 THOSE WHO HAVE DIFFICULTY BENDING OR
 STOOPING.
 2) SHOW 5' TURNING AREA IN TOILET ROOMS
 PER 11-4.22.3
 3) SHOW DETAIL KITCHEN SINK PER SECTION
 11-4.24 AND ALL SUBSECTIONS.
 4) SUBMIT A WATER RISER DIAGRAM PER
 SECTION 104.3.1.1
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy