Plan Review Details - Permit 04010222
Plan Review Stops For Permit 04010222
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2004-07-12 Cont ID  
Sent By alange Date 2004-07-12 Time 15:28 Rev Time 1.25
Received By alange Date 2004-07-12 Time 15:28 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2004-06-23 Cont ID  
Sent By csiegber Date 2004-07-06 Time 16:25 Rev Time 0.50
Received By alange Date 2004-06-23 Time 08:23 Sent To  
Notes
2004-06-23 00:00:00DENIED
 1.SAME COMMENTS FROM PREVIOUS REVIEW.
  
 SEE ATTACHED REVIEW .
 DISCUSSED ON PHONE WITH MIRELLA THAT
 ROOM ADDITION HAS TO BUILT AT A 13'6"
 ELEVATION AND PLANS NEED TO BE CHANGED
 TO REFLECT THAT.
  
 ANY QUESTIONS CALL ME.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2004-05-14 Cont ID  
Sent By csiegber Date 2004-06-17 Time 14:59 Rev Time 0.75
Received By alange Date 2004-05-14 Time 13:26 Sent To  
Notes
2004-05-14 00:00:00DENIED
 1.BASE FLOOD ELEVATION IS 13FT.
 LOWEST FLOOR ELEVATION IS TO BE 6"
 ABOVE BASE FLOOD ELEVATION.
 THE ELEVATION OF 11.80 FT F.F. IS THAT
 FOR THE NEW ROOM ADDITION.SPECIFY
 FINISH FLOOR (F.F.) ELEVATION ON
 CERTIFICATE OF THE NEW ROOM ADDITION.
  
 2. THE NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY COURTHOUSE
 AND A COPY SUBMITTED TO THIS OFFICE
 BEFORE A PERMIT CAN BE ISSUED.BLANK
 FORMS ARE AVAILABLE FROM THIS OFFICE.
  
 3.BUILDING VALUATION HAS BEEN REVISED
 FROM 76.96 "GOOD" TO $55.12 "AVERAGE"
 THE CURRENT BUILDING VALUATION IS
 $11,244.
  
 ANY QUESTIONS CALL ME.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-04-27 Cont ID  
Sent By csiegber Date 2004-05-14 Time 09:21 Rev Time 0.75
Received By alange Date 2004-04-27 Time 08:57 Sent To  
Notes
2004-04-27 00:00:00DENIED
  
 1.WEST PALM BEACH MUNI-CODE FLOOD
 ZONE PROPERTY IS IN FLOOD ZONE "A"
 LOWEST FLOOR TO BE 6" ABOVE BASE FLOOD
 ELEVATION.SUBMIT AN ELEVATION
 CERTIFICATE.
  
 2. THE NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY
 COURTHOUSEAND A COPY SUBMITTED TO THIS
 OFFICE
 BEFORE A PERMIT CAN BE ISSUED.BLANK
 FORMS ARE AVAILABLE FROM THIS OFFICE.
  
 3.BASE UPON REVISED SQUARE FOOTAGE AND
 CURRENT BUILDING VALUATION DATA FROM
 SBCCI THE BUILDING VALUATION HAS BEEN
 CHANGED TO $15776.00A VALUE OF $76.96
 PER SQUARE FOOT.
  
 ANY QUESTIONS GIVE ME A CALL.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-02-10 Cont ID  
Sent By dpalmer Date 2004-04-23 Time 16:56 Rev Time 1.75
Received By alange Date 2004-02-10 Time 10:05 Sent To  
Notes
2004-02-10 00:00:00DENIED
 1.WPB MUNI-CODE FLOOD ZONE
 PROPERTY IS IN FLOOD ZONE (A) LOWEST
 FLOOR TO BE 6" ABOVE FLOOD BASE
 ELEVATION.SUBMIT AN ELEVATION
 CERTIFICATE.
 2.BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 3. THE NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY
 COURTHOUSEAND A COPY SUBMITTED TO THIS
 OFFICE
 BEFORE A PERMIT CAN BE ISSUED.BLANK
 FORMS ARE AVAILABLE FROM THIS OFFICE.
 4.RADON FEES DUE
 5.WPBFBC 104.2.1.3
 QUALITY OF BUILDING PLANS
 BUILDING PLANS SHALL BE DRAWN TO A
 MINIMUM 1/8" SCALE UPON SUBSTANTIAL
 PAPER.DRAWINGS AND SPECIFICATIONS
 SHALL ALSO COMPLY WITH 104.2.1
 6.PROJECT VALUE TOO LOW OUR ESTIMATED
 VALUE IS $7845 BASED ON $38.48 PER SF
 ADJUST PROJECT VALUE ACCORDINGLY
 7.FBC 1804.1.3 SHOW FOOTING AND SLAB
 DETAILS.DRAWINGS TO INCLUDE THE
 FOLLOWING...DEPTH, GRADE,SIZE, TYPE OF
 REINFORCEMENT, VAPOR BARRIER USED.
 8.SHOW WALL SECTION TO INCLUDE THE
 FOLLOWING...FRAMING, ROOF FRAMING,
 HEADERS, TYPES OF STRAPS USED, SHOW
 METHOD OF TIE-IN TO EXISTING BUILDING.
 SHOW GRADE LEVEL.
 9.HAVE DRAWING SHOW NEW AND EXISTING
 AREAS.SPECIFY NEW AND EXISTING ROOMS.
 ARE YOU PUTTING IN NEW WINDOWS AND
 DOORS.
 10. IMPACT PROTECTION REQUIRED FOR NEW
 WINDOWS.
 11.SUBMIT 2 COPIES OF PRODUCT
 APPROVALS FOR EXTERIOR DOORS, WINDOWS,
 SHUTTERS AND ROOFING MATERIALS.
 12.EXISTING METAL SHED BUILDING
 IS IT GOING TO BE REMOVED.
 13.ROOF SHEATHING SHALL COMPLY WITH
 FBC 2322.2.25/8"
 14.4X FEE STILL DUE FOR WORKING WITH
 OUT A PERMIT FOR BUILDING AND ELECTRICAL
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-04-23 Cont ID  
Sent By dpalmer Date 2004-04-23 Time 15:03 Rev Time 0.33
Received By dpalmer Date 2004-04-23 Time 16:55 Sent To B
Notes
2004-04-23 00:00:00REDLINED,
 IF THERE IS EGRESS FROM HOUSE/LAUNDRY
 RM INTO NEW FAMILY RM. A 3-WAY SWITCH
 MAY BE REQ'D TO BE INSTALLED PER 210.70
 LOCATION?

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-02-04 Cont ID  
Sent By dpalmer Date 2004-02-04 Time 16:37 Rev Time 1.00
Received By dpalmer Date 2004-02-04 Time 16:37 Sent To B
Notes
2004-02-04 00:00:00*************** UNSAT *********
  
 1)NOTE: PLEASE SUBMIT PLAN/DRAWING SHOW-
 -ING ALL MIN REQ'D ELECTRICAL PER 2002
 NEC
  
 2)NOTE: PLEASE SHOW EGRESS LIGHTING INTO
 NEW ROOM AND EGRESS LIGHTING EXITING
 HOUSE TO THE REAR.
  
 3)NOTE: PLEASE SHOW ALL OUTLET SPACING
 PER 210.52 . 2',6',12' RULE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2004-07-06 Cont ID  
Sent By csiegber Date 2004-07-06 Time 16:25 Rev Time 0.00
Received By csiegber Date 2004-07-06 Time 16:25 Sent To B
Notes
2004-07-06 00:00:00TO AL DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-06-17 Cont ID  
Sent By csiegber Date 2004-06-17 Time 14:59 Rev Time 0.00
Received By csiegber Date 2004-06-17 Time 14:58 Sent To B
Notes
2004-06-17 00:00:00TO AL DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-05-14 Cont ID  
Sent By csiegber Date 2004-05-14 Time 09:21 Rev Time 0.00
Received By csiegber Date 2004-05-14 Time 09:21 Sent To B
Notes
2004-05-14 00:00:00TO AL DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-04-23 Cont ID  
Sent By dpalmer Date 2004-04-23 Time 15:02 Rev Time 0.00
Received By dpalmer Date 2004-04-23 Time 15:02 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-04-16 Cont ID  
Sent By csiegber Date 2004-04-16 Time 14:45 Rev Time 0.00
Received By csiegber Date 2004-04-16 Time 14:45 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-01-07 Cont ID  
Sent By csiegber Date 2004-01-07 Time 09:33 Rev Time 0.00
Received By csiegber Date 2004-01-07 Time 09:33 Sent To Z
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2004-04-22 Cont ID  
Sent By sgraham Date 2004-04-22 Time 12:36 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2004-02-04 Cont ID  
Sent By csiegber Date 2004-04-16 Time 14:45 Rev Time 0.00
Received By mmclean Date 2004-02-04 Time 12:58 Sent To  
Notes
2004-02-04 00:00:00DENIED, NOT CLEAR ON SURVEY TO WHERE
 THE CARPORT IS BEING ENCLOSED CALLED
 OWNER FILEA MM

Review Stop Z ZONING
Rev No 1 Status F Date 2004-01-08 Cont ID  
Sent By csiegber Date 2004-01-07 Time 09:33 Rev Time 0.00
Received By mmclean Date 2004-01-08 Time 09:39 Sent To  
Notes
2004-01-08 00:00:00DENIED, NEED 2 COPY OF SURVEY SHOWING
 WORK CALLED LEFT MSG WITH DAUGHTE FILE
 A MM