Plan Review Details - Permit 04010058
Plan Review Stops For Permit 04010058
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-03-01 Cont ID  
Sent By jwitmer Date 2004-03-01 Time 13:55 Rev Time 0.75
Received By jwitmer Date 2004-03-01 Time 10:39 Sent To  
Notes
2004-03-01 00:00:00THIS REVIEW COMPLETED AS BUSSINESS
 OCCUPANCY.JW

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-02-19 Cont ID  
Sent By csiegber Date 2004-02-26 Time 17:06 Rev Time 1.50
Received By jwitmer Date 2004-02-19 Time 14:17 Sent To  
Notes
2004-02-19 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04010058
 ADD: 5601 CORPORATE WAY
 CONT: K & M COMMERCIAL
 TEL: (561)969-7781
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 2ND REVIEW
 ACTION: DENIED
  
 1) FOR UNRESTRAINED OCCUPANCIES THE
 FOLLOWING REQUIREMENTS ARE TO BE MET.
 409.1.1 - 409.1.9.
  
 2) 104.2.1 W.P.B. ADMINISTRATIVE CODE
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR
 OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES.
 SUCH INFORMATION SHALL BE SPECIFIC
 AND THE TECHNICAL CODES "SHALL NOT BE
 CITED AS A WHOLE OR IN PART, NOR THE
 TERM "LEGAL" OR ITS RQUIVALENT BE USED
 AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION".
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-02-04 Cont ID  
Sent By jwitmer Date 2004-02-04 Time 14:48 Rev Time 2.22
Received By jwitmer Date 2004-02-04 Time 14:21 Sent To PC
Notes
2004-02-04 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04010058
 ADD: 5601 CORPORATE WAY# 103
 CONT: K & M COMMERCIAL
 TEL: (561)969-7781
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST REVIEW
 ACTION: DENIED
  
 1) THIS PLAN REVIEW WILL BE AS A GROUP I
 UNRESTRAINED OCCUPANCY. 309.1, BUILDINGS
 OR PORTIONS THEREOF USED FOR MEDICAL,
 SURGICAL, PSYCHIATRIC,NURSING OR CUSTO-
 DIAL CARE ON A 24 HR BASIS OF 4 OR MORE
 BASES.
 IF THIS CLASSIFICATION IS IN CORRECT,
 NOTE ON PLANS WHAT THE USAGE WILL BE.
  
 2) FOR UNRESTRAINED OCCUPANCIES FOLLOW
 ALL REQUIREMENTS OF 409.1.1/1.9.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-02-09 Cont ID  
Sent By dpalmer Date 2004-02-09 Time 16:17 Rev Time 0.33
Received By dpalmer Date 2004-02-09 Time 16:17 Sent To  
Notes
2004-02-09 00:00:00*** NOTE REDLINED**
  
 WIRING OF EM/EXT LTS TO BE AHEAD OF
 SWITCHING FOR LOCAL BRANCH CIRCUITS.
 NOT AHEAD OF MAIN.
  
 700.12E

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-01-09 Cont ID  
Sent By dpalmer Date 2004-01-09 Time 11:34 Rev Time 0.33
Received By dpalmer Date 2004-01-09 Time 11:34 Sent To  
Notes
2004-01-09 00:00:00************** UNSAT *************
  
 1)NOTE: PLEASE BE SURE PLANS ARE SEALED
 W/ RAISED/EMBOSSED SEAL IS CLEAR AND
 VISABLE.
  
 2)NOTE: PLEASE CLARIFY CIRCUITING FOR
 LIGHTING . PLEASE ALSO SEE 700.12E FOR
 EM/EXT LTS.
  
 3)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS
 AT 125% PER 215.3,230.42 ETC.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2004-01-09 Cont ID  
Sent By mcarsill Date 2004-01-09 Time 12:31 Rev Time 0.00
Received By mcarsill Date 2004-01-09 Time 12:31 Sent To  
Notes
2004-01-09 00:00:001) NO COMBUSTIBLES ALLOWED IN A RETURN
 AIR PLENUM.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-02-26 Cont ID  
Sent By csiegber Date 2004-02-26 Time 17:06 Rev Time 0.00
Received By csiegber Date 2004-02-26 Time 17:06 Sent To B
Notes
2004-02-26 00:00:00TO JW DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-02-06 Cont ID  
Sent By csiegber Date 2004-02-06 Time 14:41 Rev Time 0.00
Received By csiegber Date 2004-02-06 Time 14:41 Sent To  
Notes
2004-02-06 00:00:00TO COMM BD#23

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-02-04 Cont ID  
Sent By jwitmer Date 2004-02-04 Time 14:21 Rev Time 0.00
Received By jwitmer Date 2004-01-05 Time 14:25 Sent To  
Notes
2004-01-05 00:00:00TO COMM BD#26

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2004-01-26 Cont ID  
Sent By pkrauss Date 2004-01-26 Time 10:46 Rev Time 0.20
Received By pkrauss Date 2004-01-26 Time 10:46 Sent To  
Notes
2004-01-26 00:00:00NO MECHANICAL PLANS OR WORK INDICATED
 WITH BUILDING PERMIT.ADDITIONAL PERMIT
 REQUIRED FOR FUTURE MECHANICAL WORK THAT
 MAY BE DONE.PLEASE PROVIDE PLANS WITH
 MECHANICAL PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-02-09 Cont ID  
Sent By kstevens Date 2004-02-09 Time 10:39 Rev Time 0.33
Received By kstevens Date 2004-02-09 Time 10:39 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-01-22 Cont ID  
Sent By kstevens Date 2004-01-22 Time 17:37 Rev Time 0.33
Received By kstevens Date 2004-01-22 Time 17:36 Sent To  
Notes
2004-01-22 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 1
 FLORIDA ADMIN. CODE
 FLORIDA STATUTES
  
 1) A WATER RISER DIAGRAM IS REQUIRED PER
 SECTION 104.3.1.1.
 2) SEE COMMENT #1 OF ELECTRICAL REVIEW
 CONCERNING RAISED SEAL.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692