| Plan Review Stops For Permit 04010058 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2004-03-01 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2004-03-01 |
Time |
13:55 |
Rev Time |
0.75 |
| Received By |
jwitmer |
Date |
2004-03-01 |
Time |
10:39 |
Sent To |
|
|
| Notes |
| 2004-03-01 00:00:00 | THIS REVIEW COMPLETED AS BUSSINESS | | | OCCUPANCY.JW |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2004-02-19 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-02-26 |
Time |
17:06 |
Rev Time |
1.50 |
| Received By |
jwitmer |
Date |
2004-02-19 |
Time |
14:17 |
Sent To |
|
|
| Notes |
| 2004-02-19 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT: 04010058 | | | ADD: 5601 CORPORATE WAY | | | CONT: K & M COMMERCIAL | | | TEL: (561)969-7781 | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | | | | 2ND REVIEW | | | ACTION: DENIED | | | | | | 1) FOR UNRESTRAINED OCCUPANCIES THE | | | FOLLOWING REQUIREMENTS ARE TO BE MET. | | | 409.1.1 - 409.1.9. | | | | | | 2) 104.2.1 W.P.B. ADMINISTRATIVE CODE | | | DRAWINGS & SPECIFICATIONS SHALL CONTAIN | | | INFORMATION, IN THE FORM OF NOTES OR | | | OTHERWISE, AS TO THE QUALITY OF | | | MATERIALS, WHERE QUALITY IS ESSENTIAL TO | | | CONFORMITY WITH THE TECHNICAL CODES. | | | SUCH INFORMATION SHALL BE SPECIFIC | | | AND THE TECHNICAL CODES "SHALL NOT BE | | | CITED AS A WHOLE OR IN PART, NOR THE | | | TERM "LEGAL" OR ITS RQUIVALENT BE USED | | | AS A SUBSTITUTE FOR SPECIFIC | | | INFORMATION". | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2004-02-04 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2004-02-04 |
Time |
14:48 |
Rev Time |
2.22 |
| Received By |
jwitmer |
Date |
2004-02-04 |
Time |
14:21 |
Sent To |
PC |
|
| Notes |
| 2004-02-04 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT: 04010058 | | | ADD: 5601 CORPORATE WAY# 103 | | | CONT: K & M COMMERCIAL | | | TEL: (561)969-7781 | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | | | | 1ST REVIEW | | | ACTION: DENIED | | | | | | 1) THIS PLAN REVIEW WILL BE AS A GROUP I | | | UNRESTRAINED OCCUPANCY. 309.1, BUILDINGS | | | OR PORTIONS THEREOF USED FOR MEDICAL, | | | SURGICAL, PSYCHIATRIC,NURSING OR CUSTO- | | | DIAL CARE ON A 24 HR BASIS OF 4 OR MORE | | | BASES. | | | IF THIS CLASSIFICATION IS IN CORRECT, | | | NOTE ON PLANS WHAT THE USAGE WILL BE. | | | | | | 2) FOR UNRESTRAINED OCCUPANCIES FOLLOW | | | ALL REQUIREMENTS OF 409.1.1/1.9. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2004-02-09 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-02-09 |
Time |
16:17 |
Rev Time |
0.33 |
| Received By |
dpalmer |
Date |
2004-02-09 |
Time |
16:17 |
Sent To |
|
|
| Notes |
| 2004-02-09 00:00:00 | *** NOTE REDLINED** | | | | | | WIRING OF EM/EXT LTS TO BE AHEAD OF | | | SWITCHING FOR LOCAL BRANCH CIRCUITS. | | | NOT AHEAD OF MAIN. | | | | | | 700.12E |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2004-01-09 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-01-09 |
Time |
11:34 |
Rev Time |
0.33 |
| Received By |
dpalmer |
Date |
2004-01-09 |
Time |
11:34 |
Sent To |
|
|
| Notes |
| 2004-01-09 00:00:00 | ************** UNSAT ************* | | | | | | 1)NOTE: PLEASE BE SURE PLANS ARE SEALED | | | W/ RAISED/EMBOSSED SEAL IS CLEAR AND | | | VISABLE. | | | | | | 2)NOTE: PLEASE CLARIFY CIRCUITING FOR | | | LIGHTING . PLEASE ALSO SEE 700.12E FOR | | | EM/EXT LTS. | | | | | | 3)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS | | | AT 125% PER 215.3,230.42 ETC. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2004-01-09 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2004-01-09 |
Time |
12:31 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2004-01-09 |
Time |
12:31 |
Sent To |
|
|
| Notes |
| 2004-01-09 00:00:00 | 1) NO COMBUSTIBLES ALLOWED IN A RETURN | | | AIR PLENUM. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2004-02-26 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-02-26 |
Time |
17:06 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-02-26 |
Time |
17:06 |
Sent To |
B |
|
| Notes |
| 2004-02-26 00:00:00 | TO JW DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2004-02-06 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-02-06 |
Time |
14:41 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-02-06 |
Time |
14:41 |
Sent To |
|
|
| Notes |
| 2004-02-06 00:00:00 | TO COMM BD#23 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2004-02-04 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2004-02-04 |
Time |
14:21 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2004-01-05 |
Time |
14:25 |
Sent To |
|
|
| Notes |
| 2004-01-05 00:00:00 | TO COMM BD#26 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2004-01-26 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2004-01-26 |
Time |
10:46 |
Rev Time |
0.20 |
| Received By |
pkrauss |
Date |
2004-01-26 |
Time |
10:46 |
Sent To |
|
|
| Notes |
| 2004-01-26 00:00:00 | NO MECHANICAL PLANS OR WORK INDICATED | | | WITH BUILDING PERMIT.ADDITIONAL PERMIT | | | REQUIRED FOR FUTURE MECHANICAL WORK THAT | | | MAY BE DONE.PLEASE PROVIDE PLANS WITH | | | MECHANICAL PERMIT APPLICATION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2004-02-09 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2004-02-09 |
Time |
10:39 |
Rev Time |
0.33 |
| Received By |
kstevens |
Date |
2004-02-09 |
Time |
10:39 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2004-01-22 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2004-01-22 |
Time |
17:37 |
Rev Time |
0.33 |
| Received By |
kstevens |
Date |
2004-01-22 |
Time |
17:36 |
Sent To |
|
|
| Notes |
| 2004-01-22 00:00:00 | DENIED | | | REFERENCE: FBC-2001 CHAPTER 1 | | | FLORIDA ADMIN. CODE | | | FLORIDA STATUTES | | | | | | 1) A WATER RISER DIAGRAM IS REQUIRED PER | | | SECTION 104.3.1.1. | | | 2) SEE COMMENT #1 OF ELECTRICAL REVIEW | | | CONCERNING RAISED SEAL. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|