Plan Review Details - Permit 04010056
Plan Review Stops For Permit 04010056
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-02-12 Cont ID  
Sent By kstevens Date 2004-01-16 Time 11:33 Rev Time 2.25
Received By alange Date 2004-02-12 Time 08:02 Sent To  
Notes
2004-02-12 00:00:00DENIED
 1.BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 2. THE NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY
 COURTHOUSEAND A COPY SUBMITTED TO THIS
 OFFICE
 BEFORE A PERMIT CAN BE ISSUED.BLANK
 FORMS ARE AVAILABLE FROM THIS OFFICE.
 3.WINDOW BUCKS SHALL COMPLY WITH FBC
 1717.4.4.2 BUCK SHALL EXTEND BEYOND THE
 INTERIOR FACE OF THE WINDOW OR DOOR
 FRAME. TO PROVIDE FULL SUPPORT OF THE
 FRAME.
 4.BUILDING PERMIT VALUATION
 WPB AMMENDMENTS TO THE FBC 104.6.5
 PERMIT VALUATION HAS BEEN CHANGED TO
 $94,038 ADDITION PERMIT FEES ARE DUE.
 5.SIGNATURE REQUIRED ON TWO COPIES
 OF ENERGY CALCULATIONS.
 6.PRODUCT APPROVALS FOR POMA SHUTTERS
 NOT ON THE FBC PRODUCT APPROVAL SITE.
 PRODUCT APPROVALS FOR EXT. DOOR MISSING.
 SUBMIT 2 COPIES.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
 7.SUBMIT A SITE PLAN
  
 ANY QUESTIONS PLEASE CALL
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-01-13 Cont ID  
Sent By btrobaug Date 2004-01-13 Time 17:29 Rev Time 0.75
Received By btrobaug Date 2004-01-13 Time 17:28 Sent To M
Notes
2004-01-13 00:00:00 
 UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE NOTE, ALL PLANS DRAWN
 BY AN ARCHITECT/ENGINEER CONTAIN-
 -ING A TITLE BLOCK: MUST BE SIGNED,
 DATED AND SEALED BY THAT ARCH/ENG.
 PER FS 481.221 471.025
 FAC 61G15-23.002, 61G1-16.004
  
 2} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING
 INSTALL-ED. MAINS/BRKRS AND PANELS ARE
 ALL TO BERATED FOR THE AVAILABLE FAULT
 CURRENT.
 PER 110.9/215.5
  
 3} PLEASE LIST ALL THE REQ'D
 DEDICATED BATH(S) CIRCUIT(S) ON PANEL
 SCHEDULE. PER 210.52D, 210.11C3
  
 4} PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CURCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
  
 5} PLEASE CORRECT NOTE #3 TO COMPLY WITH
 210.8(A)(6), ALL COUNTERTOP RECEPTACLES
  
 4} NOTE #4 INDICATING SMOKE DETECTOR
 BRANCH CIRCUITS DOES NOT INDICATE
 COMPLIANCE WITH 210.12.
  
 5} THE REFERENCE TO LAKE WORTH UTILITY
 IN NOTE #6 IS INCORRECT.
  
 6} NOTE # 7 IS AN INCORRECT REFERENCE.
 SEE 2002 NEC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-02-12 Cont ID  
Sent By csiegber Date 2004-05-06 Time 16:38 Rev Time 0.00
Received By csiegber Date 2004-01-05 Time 14:35 Sent To  
Notes
2004-01-09 00:00:00TO SFD RACK/E
2004-01-05 00:00:00TO Z

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-01-15 Cont ID  
Sent By btrobaug Date 2004-01-13 Time 17:29 Rev Time 0.50
Received By hmoser Date 2004-01-15 Time 18:05 Sent To P
Notes
2004-01-15 00:00:00PLAN DENIED
 1) REFER TO SECTION 307.2.3 AUXILIARY
 DRAIN PAN.AUXILIARY DRAIN PANS SHALL BE
 INSTALLED UNDER ALL COILS ON WITCH
 CONDENSATION WILL OCCUR.
 2) RETURN AIR REQUIREMENTS TO COMPLY
 WITH THE FLORIDA BUILDING CODE (M) 2003
 CHANGES.CHANGES WENT INTO EFFECT JULY 1
 2003
 3) MECHANICAL PLAN MUST BE STAMPED BY
 ENGINEER IF THE PLAN IS ON ENGINEER
 PAPER
 PLAN REVIEW BY HAROLD MOSER
 (561)805-6732

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-01-16 Cont ID  
Sent By hmoser Date 2004-01-15 Time 18:05 Rev Time 0.33
Received By kstevens Date 2004-01-16 Time 11:02 Sent To B
Notes
2004-01-16 00:00:00DENIED
 REFERENCE: FLA. ADMIN. CODE
 FLA. STATUTES
  
 1) A PROFESSIONAL ENGINEER SHALL SIGN
 HIS NAME AND AFFIX HIS SEAL TO ALL PLANS
 PROVIDED TO THE OWNER OR OWNER'S REPRE-
 SENTATIVE BEING FILED FOR PUBLIC RECORD.
 THE DATE THAT THE SIGNATURE AND SEAL IS
 AFFIXED AS PROVIDED HEREIN SHALL BE EN-
 TERED ON SAID PLANS IMMEDIATELY UNDER
 THE SIGNATURE OF THE PROFESSIONAL ENGIN-
 EER. FAC 61G15-23.002(1) & FS 471.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2004-01-08 Cont ID  
Sent By mmclean Date 2004-01-08 Time 16:44 Rev Time 0.00
Received By mmclean Date 2004-01-08 Time 16:44 Sent To  
Notes
2004-01-08 00:00:00DENIED, NEED 2 COPY OF SURVEY SHOWING
 THE LOCATION OF HOUSE WITH SETBACKS
 (SURVEY MUST BE FROM A LICENSED SURVEYOR
 CALLED OWNER FILE M