Plan Review Details - Permit 04010028
Plan Review Stops For Permit 04010028
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-04-29 Cont ID  
Sent By alange Date 2004-04-29 Time 10:30 Rev Time 0.33
Received By alange Date 2004-04-29 Time 10:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-02-20 Cont ID  
Sent By pkrauss Date 2004-04-29 Time 06:58 Rev Time 0.50
Received By alange Date 2004-02-20 Time 16:23 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-01-27 Cont ID  
Sent By dpalmer Date 2004-02-19 Time 06:27 Rev Time 1.50
Received By alange Date 2004-01-27 Time 08:44 Sent To  
Notes
2004-01-27 00:00:001.PLEASE SIGN ENERGY CALCULATIONS AND
 RESUBMIT.
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2004-04-23 Cont ID  
Sent By dpalmer Date 2004-04-23 Time 16:07 Rev Time 0.33
Received By dpalmer Date 2004-04-23 Time 16:07 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-03-05 Cont ID  
Sent By alange Date 2004-04-22 Time 11:14 Rev Time 0.33
Received By dpalmer Date 2004-03-05 Time 05:25 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-02-19 Cont ID  
Sent By csiegber Date 2004-02-26 Time 17:04 Rev Time 0.33
Received By dpalmer Date 2004-02-19 Time 06:16 Sent To B
Notes
2004-02-19 00:00:00************ UNSAT *******************
  
 1)NOTE: PLEASE SEE LOAD SHOWN FOR AHU
 ON PANEL SCHEDULE, SHOWS 5KW, YET LOAD
 CALCULATIONS DO NOT CORRELATE.
  
 2)NOTE: PLEASE SHOW LOAD CALC FOR EACH
 PANEL AND THEN SERVICE.
 PLEASE SEE LOAD SHOWN FOR WAHT APPEARS
 TO BE EACH PANEL @ 113 A'S, YET OCP IS
 100A'S?
  
 3)NOTE: PLEASE SEE PANELS, SHOWN AS 42
 CIR, 150A PANELS ARE NOT MADE W/ 42 CIR.
  
 4)NOTE: PLEASE SEE MISSING FRONT AND
 REAR RECEPTS PER 210.52E
  
 5)NOTE: PLEASE SEE MISSING RECEPT FOR
 A/C COND UNIT. 210.63. RECEPT FOR REAR
 OF DWELLING MAY MEET REQUIREMENT.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-01-12 Cont ID  
Sent By csiegber Date 2004-02-09 Time 10:46 Rev Time 1.00
Received By dpalmer Date 2004-01-12 Time 13:25 Sent To M
Notes
2004-01-12 00:00:00************ UNSAT ****************
  
 1)NOTE: PLEASE SEE THAT NO MAINS ARE
 SHOWN 225.31.
 MAINS ARE TO BE GROUPED PER 230.72
  
 2)NOTE: PLEASE INCLUDE EQUIPMENT GROUND-
 -ING FROM MAINS TO PANELS. 250.110,
 250.24, 250.122
  
 3)NOTE: PLEASE SEE 2002 NEC FOR RQUIRE-
 -MENT FOR ARC FAULT PROTECTION.
  
 4)NOTE: PLEASE SUBMIT AIC RATING FOR NEW
 MAINS/ PANELS ETC. 110.9
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-04-22 Cont ID  
Sent By alange Date 2004-04-22 Time 11:14 Rev Time 0.00
Received By alange Date 2004-04-22 Time 11:14 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-02-26 Cont ID  
Sent By csiegber Date 2004-02-26 Time 17:04 Rev Time 0.00
Received By csiegber Date 2004-02-26 Time 17:04 Sent To E
Notes
2004-02-26 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-02-09 Cont ID  
Sent By csiegber Date 2004-02-09 Time 10:46 Rev Time 0.00
Received By csiegber Date 2004-02-09 Time 10:46 Sent To E
Notes
2004-02-09 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-01-05 Cont ID  
Sent By csiegber Date 2004-01-05 Time 11:16 Rev Time 0.00
Received By csiegber Date 2004-01-05 Time 11:16 Sent To E
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2004-04-29 Cont ID  
Sent By pkrauss Date 2004-04-29 Time 06:57 Rev Time 0.30
Received By pkrauss Date 2004-04-29 Time 06:44 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-03-10 Cont ID  
Sent By dpalmer Date 2004-04-23 Time 16:13 Rev Time 0.30
Received By pkrauss Date 2004-03-10 Time 08:29 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-01-15 Cont ID  
Sent By dpalmer Date 2004-02-19 Time 06:16 Rev Time 0.35
Received By pkrauss Date 2004-01-15 Time 12:04 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2004-01-15 Cont ID  
Sent By dpalmer Date 2004-04-23 Time 16:07 Rev Time 0.33
Received By kstevens Date 2004-01-15 Time 17:53 Sent To B
Notes
2004-01-15 00:00:00NO PLUMBING PLANS SUBMITTED - 1 AUTO-
 MATIC CLOTHES WASHER CONNECTION PER
 DWELLING REQD. OR 1 CONNECTION FOR UP TO
 20 UNITS IN COMMON AREA.