Plan Review Details - Permit 04010010
Plan Review Stops For Permit 04010010
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2004-06-03 Cont ID  
Sent By jwitmer Date 2004-06-03 Time 09:47 Rev Time 0.50
Received By jwitmer Date 2004-06-03 Time 09:46 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2004-05-27 Cont ID  
Sent By jwitmer Date 2004-05-27 Time 07:43 Rev Time 1.55
Received By jwitmer Date 2004-05-27 Time 07:43 Sent To  
Notes
2004-05-27 00:00:00PLANS ARE CODE COMPLIANT, REQUIRE
 COUNTY IMPACT FEE ASSESSMENT BEFORE
 APPROVAL.JW
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2004-05-07 Cont ID  
Sent By jwitmer Date 2004-05-07 Time 13:20 Rev Time 1.00
Received By jwitmer Date 2004-05-07 Time 12:56 Sent To  
Notes
2004-05-07 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04010010
 ADD: 320 PINE ST
 CONT: BAINES BUILDING
 TEL: (561)635-6935
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 2ND REVIEW
 ACTION: DENIED
  
 1)CHANGE OF OCCUPANCY: THE ENGINEER TO
 PROVIDE INFORMATION TO BE ABLE TO CERTI-
 FY THE FLOOR LOAD TO 50LBS. PROVIDE
 INFORMATION FOR THE FLOOR JOIST, SIZE,
 SPACING, SPECIES OF LUMBER, GRADE AND
 CLEAR FLOOR SPAN, PROVIDE CALCULATIONS.
  
 2) COMMENT 3 FROM 1ST REVIEW: INDICATE C
 OMPLIANCE WITH ACCESSIBILITY CODE, RAMPS
 FOR THE ACCESSIBLE ENTRANCE.
 2A) PLANS INICATE A RAMP IN THE REAR OF
 PROPERTY WITH ACCESSIBLE PARKING LOT
 AND ACCESS ISLE. THE ACCESS ISLE DOESN'T
 ALIGN WITH THE WALK, HAVING THE PERSON
 WHEEL THROUGH THE AREA FOR THE PARKED
 CAR.
 2B) PLANS DO NOT GIVE RAMP REQUIREMENTS:
 11-4.8.4.(2) LANDINGS. ALL LANDINGS
 ON RAMPS SHALL NOT BE LESS THAN 60"
 CLEAR, & THE BOTTOM OF EACH RAMP SHALL
 HAVE NOT LESS THAN 72" OF STRAIGHT &
 LEVEL CLEARENCE.
 2C) THE PLANS DO NOT GIVE A REAR ELEVA-
 TION. THERE CAN BE NO STAIRS FOR THE ACC
 ESSIBLE ROUTE. THE MOST CHANGE IN GRADE
 CAN BE 1/4" WITHOUT THE USE OF A RAMP.
 2D) FRONT ENTRY SIGNAGE REQUIRED:
 11-4.1.6(H) IF A PARTICULAR
 ENTRANCE IS NOT MADE ACCESSIBLE, APPRO-
 PRIATE ACCESSIBLE SIGNAGE INDICATING THE
 LOCATION OF THE NEAREST ACCESSIBLE
 ENTRANCE(S) SHALL BE INSTALLED AT OR
 NEAR THE INACCESSIBLE ENTRANCE, SUCH
 THAT A PERSON WITH DISABILITIES WILL
 NOT BE REQUIRED TO RETRACE THE APPROACH
 ROUTE FROM THE INNACCESSIBLE ENTRANCE.
  
 3) COMMENT 5 FROM PREVIOUS REVIEW:
 FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) NEW WINDOWS
 B) EXTERIOR DOORS IF REPLACED
 PLANS ON 1ST REVIEW INDICATED NEW WIN-
 DOWS NOTHING IS MENTIONED?
 PLANS ON THE 1ST REVIEW DIDN'T ADDRESS
 IF THE DOORS WERE TO BE REPLACED? PLEASE
 GIVE A RESPONCE!!
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 4) TABLE 803.3 MINIMUM INTERIOR FINISH
 CLASSIFICATION; PROVIDE INFORMATION
 BASED ON INTERIOR FINISH REQUIREMENTS
 BASED ON OCCUPANCY
  
 5)1204.2 SURROUNDING MATERIALS;
 THE WALLS & FLOORS OF ALL PUBLIC REST-
 ROOMS SHALL BE LINED WITH NONABSORBANT
 MATERIALS TO A HEIGTH OF 4'-0" ABOVE THE
 FLOOR.
  
 6)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-04-09 Cont ID  
Sent By jwitmer Date 2004-04-09 Time 10:26 Rev Time 1.00
Received By jwitmer Date 2004-04-09 Time 10:26 Sent To PC
Notes
2004-04-09 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04010010
 ADD: 320 PINE ST
 CONT: BAINES
 TEL: (561)635-6935
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 REVISION
 ACTION: DENIED
  
 1) CHANGE OF OCCUPANCY 3401.2.2.2
 CHANGES IN OCCUPANCY OF ANY EXISTING
 BUILDING SHALL NOT BE MADE UNTIL A REVIS
 ED CERTIFICATE OF OCCUPANCY HAS BEEN
 ISSUED BY THE BUILDING OFFICIAL
 CERTIFYING THAT THE FLOORS ARE SUITABLE
 FOR THE LOADS CHARACTERISTICS OF THE
 PROPOSED OCCUPANCY.
 2) 3401.3 THE BUILDING IS TO CONFORM TO
 THE PROVISIONS OF THE TECHNICAL CODE AND
 OTHER APPLICABLE LAWS AND ORDINANCES
 FOR SUCH OCCUPANCY.
 3) INDICATE COMPLIANCE WITH ACCESSIBIITY
 CODE, RAMPS FOR ACCESSIBLE ENTRANCE.
 4)FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
 5) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) NEW EXTERIOR WINDOWS
 B) EXTERIOR DOORS IF REPLACED?
 6) PLANS INDICATE OCCUPANCY IS FOR R3,
 CHANGE TO BUSINESS.
 7) TABLE 803.3 MINIMUM INTERIOR FINISH
 CLASSIFICATION; PROVIDE INFORMATION
 BASED ON INTERIOR FINISH REQUIREMENTS
 BASED ON OCCUPANCY
 8)1204.2 SURROUNDING MATERIALS;
 THE WALLS & FLOORS OF ALL PUBLIC REST-
 ROOMS SHALL BE LINED WITH NONABSORBANT
 MATERIALS TO A HEIGTH OF 4'-0" ABOVE THE
 FLOOR.
 9)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status N Date 2004-01-05 Cont ID  
Sent By shernand Date 2004-01-05 Time 08:45 Rev Time 0.00
Received By shernand Date 2004-01-05 Time 08:45 Sent To  
Notes
2004-01-05 00:00:00OK PER RYAN N

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-05-28 Cont ID  
Sent By jleahy Date 2004-05-28 Time 11:43 Rev Time 0.45
Received By jleahy Date 2004-05-28 Time 11:42 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-04-28 Cont ID  
Sent By dpalmer Date 2004-04-28 Time 05:47 Rev Time 0.50
Received By dpalmer Date 2004-04-28 Time 05:47 Sent To  
Notes
2004-04-28 00:00:00********** UNSAT *********
  
 PLEASE SEE SOME NOTES FORM FIRST REVIEW
 NOT DONE AND THERE ARE ALOS NEW NOTES.
  
 1)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH A SUBMITTED
 PANEL SCHEDULE.
 PANEL SCHEDULE MUST SHOWS CIRCUIT #'S,
 OCP, AWG ETC.
  
 2)NOTE: PLEASE SEE NEC FOR DERATING
 OF INDIVIDUAL BRANCH CIRCUITS IN 1"
 SCH80 PVC CONDUIT. 240,TABLES ETC.
  
 3)NOTE: PLEASE SHOW A/C EQUIPMENT ON
 ELECTRICAL PLANS ALONG WITH DISC AS
 REQ'D PER 440.11.
  
 4)NOTE: PLEASE SHOW RECEPTS REQ'D UNDER
 210.63 FOR A/C EQUIPMENT.
  
 5)NOTE: PLEASE SEE BLDG USE IS BEING
 CHANGED FROM RESIDENCE TO COMM.
 PLEASE SEE TWO METER SYSTEM MUST BE
 REMOVED AND BE INSTALLED BACK TO SINLGE
 METER INSTALLATION.
 PLEASE ADJUST SERVICE ACCORD.
  
 6)NOTE: PLEASE SEE 700.12E FOR CIRCUIT-
 -ING OF EM/EXT LTS.
  
 7)NOTE: PLEASE HAVE ENGINEER SIGN WITH
 COMPLETE "SIGNATURE" AS SHOWN ON LICENSE
 /RAISED SEAL AS REQ'D UNDER FS 471.025
 INITIALS ARE NOT ACCEPTABLE PER FBPE'S.
 PLEASE ALSO CLARIFY BBC DESIGN ON
 TITLE BLOCK?? 61G15-23.002/ 61G1-16.004?
  
 8)NOTE: PLEASE SEE FBC 104.6.5, VALUE
 FOR SCOPE OF WORK NEEDS TO BE INCREASED
 DUE TO SCOPE PF WORK BEING PERFORMED.
 VALUE IS INCLUDE ALL LABOR AND MATERIALS
 PLEASE SEE BLDG REVIEW COMMENTS.
  
 9)NOTE: PLEASE SEE COPY OF FS 553.80(2)
 (B) FOR PLANS REVIEWED FOR SAME COMMENTS
 IF PLANS COME BACK IN FOR 3RD REVIEW,
 AND ANY OF THE SAME COMMENTS FROM
 PREVIOUS TWO REVIEWS ARE NOT ADDRESSED
 A 4X FEE SHALL BE ISSUED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-03-30 Cont ID  
Sent By csiegber Date 2004-04-27 Time 14:14 Rev Time 0.50
Received By btrobaug Date 2004-03-30 Time 08:05 Sent To  
Notes
2004-03-30 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} SHOW EXIT AND EMERGENCY LIGHTS PER
 NFPA-101 AND ARTICLE 700 NEC.SEE FIRE
 REVIEW COMMENTS.
  
 2} PLEASE SHOW CIRCUIT NUMBERS AT ALL
 LUMINAIRES AND DEVICES.
  
 3} PROVIDE A PANEL SCHEDULE WITH
 CORRESPONDIG CIRCUIT NUMBERS.
  
 4} PLEASE INDICATE THE LOCATION OF THE
 SERVICE EQUIPMENT, INCLUDING PANEL
 LOCATION(S)
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2004-05-20 Cont ID  
Sent By mcarsill Date 2004-05-20 Time 09:40 Rev Time 0.00
Received By mcarsill Date 2004-05-20 Time 09:40 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-04-28 Cont ID  
Sent By mcarsill Date 2004-04-28 Time 13:19 Rev Time 0.00
Received By mcarsill Date 2004-04-28 Time 13:19 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-03-19 Cont ID  
Sent By mcarsill Date 2004-03-19 Time 14:31 Rev Time 0.00
Received By mcarsill Date 2004-03-19 Time 14:31 Sent To  
Notes
2004-03-19 00:00:001) ACCORDING TO PERMIT APPLICATION, THE
 BUILDING WAS FORMERLY RESIDENTIAL AND
 IS BEING CHANGED TO BUSINESS. THIS
 CONVERSION WILL BE CLASSIFIED AS A
 CHANGE OF USE.
  
 2) BUILDING ADDRESS REQUIRED. A MINIMUM
 OF 6" HIGH NUMBERS ARE REQUIRED.
  
 3) HANDRAILS REQUIRED ON BOTH SIDES
 OF ALL STAIRS AND RAMPS.
  
 4) NO EXIT SIGNS OR EMERGENCY LIGHTS
 SHOWN.
  
 5) NO INFORMATION PROVIDED WITH REGARDS
 TO PORTABLE FIRE EXTINGUISHERS.
  
 6) NO INFORMATION PROVIDED WITH REGARDS
 TO PORTABLE FIRE EXTINGUISERS.
  
 7) PLEASE PROVIDE INFORMATION ABOUT
 EXTERIOR DOOR LOCKS.
  
 8) DOOR LEADING FROM OFFICE TO EXTERIOR
 DOOR CANNOT BE SUBJECT TO LOCKING IF
 AN EXIT DOOR IS PRESENT.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-06-02 Cont ID  
Sent By csiegber Date 2004-06-02 Time 07:45 Rev Time 0.00
Received By csiegber Date 2004-06-02 Time 07:45 Sent To  
Notes
2004-06-02 00:00:00TO COMM BD#22

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-05-18 Cont ID  
Sent By csiegber Date 2004-05-18 Time 15:16 Rev Time 0.00
Received By csiegber Date 2004-05-18 Time 15:16 Sent To  
Notes
2004-05-18 00:00:00TO COMM BD#21

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-04-27 Cont ID  
Sent By csiegber Date 2004-04-27 Time 14:14 Rev Time 0.00
Received By csiegber Date 2004-04-27 Time 14:14 Sent To  
Notes
2004-04-27 00:00:00TO COMM BD#7

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-03-19 Cont ID  
Sent By csiegber Date 2004-03-19 Time 12:36 Rev Time 0.00
Received By csiegber Date 2004-03-19 Time 12:36 Sent To  
Notes
2004-03-19 00:00:00TO COMM BD#49

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2004-05-28 Cont ID  
Sent By pkrauss Date 2004-05-28 Time 13:07 Rev Time 0.30
Received By pkrauss Date 2004-05-28 Time 13:07 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2004-05-13 Cont ID  
Sent By pkrauss Date 2004-05-11 Time 11:19 Rev Time 0.30
Received By pkrauss Date 2004-05-11 Time 11:19 Sent To  
Notes
2004-05-11 00:00:00PLANS NEED TO BE STAMPED
 PER MEETING WITH GENERAL CONTRACTOR &
 OWNERS; RESIDENTIAL BUILDING CONVERTED
 TO OFFICE BUILDING.WINDOWS ARE
 OPERABLE & INSTALLED PRIOR TO 1979.
 OUTSIDE AIR PER NATURAL VENTILATION
 402.2.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2004-04-28 Cont ID  
Sent By pkrauss Date 2004-04-28 Time 12:43 Rev Time 0.45
Received By pkrauss Date 2004-04-28 Time 12:16 Sent To  
Notes
2004-04-28 00:00:00DENIED:
 PLAN SHEET M-1 INDICATES FRESH AIR BY
 NATURAL MEANS 402.2.PROVIDE
 CALCULATION SHOWING 4% OF THE FLOOR
 SPACE TO THE OPENABLE AREA OF THE
 WINDOWS & DOORS.PROVIDE TEST RESULTS
 FROM THE TESTING AGENCY INDICATING THE
 ACTUAL FILTRATION RATE.PROVIDE THIS
 INFORMATION FOR EACH WINDOW & DOOR.
 INDICATE CALCUALTION ON THE PLAN SHOWING
 COMPLAINCE WITH 402.2.
  
 PLAN ALSO INDICATES CIRCULATION RATE
 PER F.P.C. (FBC?) 403.3.PLEASE
 INDICATE WHICH MEANS WILL BE USED AND
 SHOW CALCULATION ON THE PLAN.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-04-06 Cont ID  
Sent By pkrauss Date 2004-04-06 Time 11:19 Rev Time 0.35
Received By pkrauss Date 2004-04-06 Time 11:19 Sent To  
Notes
2004-04-06 00:00:00DENIED:
 1.PLEASE PROVIDE OUTSIDE AIR
 CALCULATIONS PER 2001 FBC(M) 403.3.
  
 2.INDICATE OUTSIDE AIR INTAKE, DUCT
 SIZE, MATERIAL AND LAYOUT.
  
 3.PLAN SHEET M-1 INDICATES 3 TON
 SYSTEM, INDICATE IF THE EQUIPMENT IS
 NEW OR EXISTING.
  
 4.AUXILIARY DRAIN PAN WITH OVERFLOW
 PROTECTION REQUIRED PER 2001 FBC(M)
 307.2.3.
  
 5.PLEASE NOTE THE LOCATION OF THE AHU
 SHALL HAVE SUFFICIENT SPACE TO ALLOW FOR
 INSPECTION, SERVICE, REPAIR OR REPLACE-
 MENT.2001 FBC(M) 306.1.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 4 Status P Date 2004-06-03 Cont ID  
Sent By kstevens Date 2004-06-03 Time 13:38 Rev Time 2.00
Received By kstevens Date 2004-06-03 Time 13:38 Sent To  
Notes
2004-06-03 00:00:00REVISION OK - SECOND BATH TO BE ADAPT-
 ABLE. DOOR TO BE CHANGED TO HAVE ACCESS
 FROM SINGLE OFFICE ONLY.

Review Stop P PLUMBING
Rev No 3 Status F Date 2004-05-28 Cont ID  
Sent By kstevens Date 2004-05-28 Time 13:27 Rev Time 0.50
Received By kstevens Date 2004-05-28 Time 13:27 Sent To  
Notes
2004-05-28 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA STATUTES
  
 A) FROM PREVIOUS REVIEWS:
 2) IF TOILET ROOMS ARE PROVIDED, THEN
 EACH PUBLIC AND COMMON USE TOILET ROOM
 SHALL COMPLY WITH 11-4.22. SUBMIT A DE-
 TAIL SHOWING COMPLIANCE WITH 11-4.16,
 11-4.19, AND 11-4.22 AND ALL SUBSECTIONS
 11-4.1.3(11).
 - HEIGHT OF TOILET NOT SHOWN 11-4.16.3,
 CLEAR FLOOR SPACE/TURNING AREA 11-4.16.2
 11-4.22.3. GRAB BARS NOT SHOWN IN TOILET
 ROOM BY KITCHEN 11-4.16.4, CLEAR FLOOR
 SPACE FOR TOILETS 11-4.16.2, CLEAR FLOOR
 SPACE FOR LAV IN TOILET BY KITCHEN AREA
 11-4.19.3, EXPOSED PIPES AND SURFACES
 11-4.19.4, DOORS SHALL NOT SWING INTO
 THE CLEAR FLOOR SPACE OF ANY FIXTURE
 11-4.22.2(1).
 3) SHT E-1 SANITARY RISER DIAGRAM DOES
 NOT MEET CODE, EXTRA VENT LINE OFF LAV
 STACK IS A HORIZONTAL DRY VENT AND IS
 NOT REQUIRED. DELETE FROM RISER DIAGRAM.
 SECTION 905.3 - 704.5
  
 INFORMATIONAL: SEE ATTACHED SHEET FOR
 DESIGN PROFESSIONAL CONCERNING FLORIDA
 STATUTE 553.80(2)(B).
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2004-05-11 Cont ID  
Sent By jleahy Date 2004-05-28 Time 11:43 Rev Time 1.00
Received By kstevens Date 2004-05-11 Time 14:00 Sent To  
Notes
2004-05-11 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 A) FROM PREVIOUS REVIEW: COMMENTS NOT
 ADDRESSED TO CODE SATISFACTION. NUMBER
 OF COMMENT FROM FIRST REVIEW TO STAY THE
 SAME TO AVOID CONFUSION.
 2) IF TOILET ROOMS ARE PROVIDED, THEN
 EACH PUBLIC AND COMMON USE TOILET ROOM
 SHALL COMPLY WITH 11-4.22. SUBMIT A DE-
 TAIL SHOWING COMPLIANCE WITH 11-4.16,
 11-4.19, AND 11-4.22 AND ALL SUBSECTIONS
 - SECTION 11-4.1.3(11). RESPONSE NOTED,
 BUT HEIGHT OF TOILET NOT SHOWN 11-4.16.3
 CLEAR FLOOR SPACE/TURNING AREA 11-4.16.2
 GRAB BARS NOT SHOWN IN TOILET ROOM BY
 KITCHEN 11-4.16.4, CLEAR FLOOR SPACE FOR
 LAV 11-4.19.3, EXPOSED PIPES & SURFACES
 11-4.19.4, DOORS SHALL NOT SWING INTO
 THE CLEAR FLOOR SPACE FOR ANY FIXTURE
 11-4.22.2(1).
 3) SHT E-1 SANITARY RISER DIAGRAM DOES
 NOT REFLECT THE FLOOR PLAN. THE ACCESSI-
 BLE TOILET ROOM SHOULD BE LOCATED ON THE
 LEFT SIDE OF THE BLDG. DRAIN. IF THE
 BUILDING HAS TWO BLDG. DRAINS THEN A C/O
 IS REQUIRED AS EACH BLDG. DRAIN EXITS
 THE BLDG. SECTION 708.3.5 - REMOVE THE
 DRINKING FOUNTAIN FROM THE SANT. RISER
 DIAGRAM, HAND DRAWN CHANGES TO A SIGNED
 AND SEALED SET OF PLANS IS NOT APPROVED.
 4) KITCHEN SINK SHALL COMPLY WITH SECT-
 ION 11-4.24 AND ALL SUBSECTIONS. CLEAR
 FLOOR SPACE FOR SINK IS NOT SHOWN. SEE
 SECTION 11-4.24.5
 NEW COMMENT......................
 1B) ENGINEERS SHALL SIGN PLAN WITH A
 SIGNATURE. PER FBPE'S RULING INITIALS
 ARE NOT ACCEPTABLE.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-03-23 Cont ID  
Sent By kstevens Date 2004-03-23 Time 15:48 Rev Time 1.00
Received By kstevens Date 2004-03-23 Time 15:48 Sent To  
Notes
2004-03-23 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) A DRINKING FOUNTAIN IS REQUIRED PER
 TABLE 403.1
 2) IF TOILET ROOMS ARE PROVIDED, THEN
 EACH PUBLIC AND COMMON USE TOILET ROOM
 SHALL COMPLY WITH 11-4.22. SUBMIT A DE-
 TAIL SHOWING COMPLIANCE WITH 11-4.16,
 11-4.19, AND 11-4.22 AND ALL SUBSECTIONS
 - SECTION 11-4.1.3(11)
 3) SHT E-1 SANITARY RISER DIAGRAM DOES
 NOT REFLECT THE FLOOR PLAN. THE ACCESS-
 IBLE TOILET ROOM SHOULD BE LOCATED ON
 THE LEFT SIDE OF THE BLDG. DRAIN AND
 SHOWS TWO FIXTURES ON THE LAV STACK.
 THE OTHER TOILET ROOM NEAR THE KITCHEN
 SHOWS NO LAV.
 4) KITCHEN SINK SHALL COMPLY WITH SECT-
 ION 11-4.24 AND ALL SUBSECTIONS. SUBMIT
 A DETAIL SHOWING COMPLIANCE.
 5 ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME, ADDRESS AND LICENSE NUMBER ON EACH
 SHEET. FAC 61G1-15.002(2) - FS 471.025
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2004-03-18 Cont ID  
Sent By mmclean Date 2004-03-18 Time 16:09 Rev Time 0.00
Received By mmclean Date 2004-03-18 Time 16:09 Sent To I
Notes
2004-03-18 00:00:00PROVISO: STREET HEDGE AT THREE FEET SIX
 INCHES AROUND THE PARKING LOT IN REAR


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved