| Plan Review Stops For Permit 04010010 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2004-06-03 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2004-06-03 |
Time |
09:47 |
Rev Time |
0.50 |
| Received By |
jwitmer |
Date |
2004-06-03 |
Time |
09:46 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2004-05-27 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2004-05-27 |
Time |
07:43 |
Rev Time |
1.55 |
| Received By |
jwitmer |
Date |
2004-05-27 |
Time |
07:43 |
Sent To |
|
|
| Notes |
| 2004-05-27 00:00:00 | PLANS ARE CODE COMPLIANT, REQUIRE | | | COUNTY IMPACT FEE ASSESSMENT BEFORE | | | APPROVAL.JW | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2004-05-07 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2004-05-07 |
Time |
13:20 |
Rev Time |
1.00 |
| Received By |
jwitmer |
Date |
2004-05-07 |
Time |
12:56 |
Sent To |
|
|
| Notes |
| 2004-05-07 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT: 04010010 | | | ADD: 320 PINE ST | | | CONT: BAINES BUILDING | | | TEL: (561)635-6935 | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | | | | 2ND REVIEW | | | ACTION: DENIED | | | | | | 1)CHANGE OF OCCUPANCY: THE ENGINEER TO | | | PROVIDE INFORMATION TO BE ABLE TO CERTI- | | | FY THE FLOOR LOAD TO 50LBS. PROVIDE | | | INFORMATION FOR THE FLOOR JOIST, SIZE, | | | SPACING, SPECIES OF LUMBER, GRADE AND | | | CLEAR FLOOR SPAN, PROVIDE CALCULATIONS. | | | | | | 2) COMMENT 3 FROM 1ST REVIEW: INDICATE C | | | OMPLIANCE WITH ACCESSIBILITY CODE, RAMPS | | | FOR THE ACCESSIBLE ENTRANCE. | | | 2A) PLANS INICATE A RAMP IN THE REAR OF | | | PROPERTY WITH ACCESSIBLE PARKING LOT | | | AND ACCESS ISLE. THE ACCESS ISLE DOESN'T | | | ALIGN WITH THE WALK, HAVING THE PERSON | | | WHEEL THROUGH THE AREA FOR THE PARKED | | | CAR. | | | 2B) PLANS DO NOT GIVE RAMP REQUIREMENTS: | | | 11-4.8.4.(2) LANDINGS. ALL LANDINGS | | | ON RAMPS SHALL NOT BE LESS THAN 60" | | | CLEAR, & THE BOTTOM OF EACH RAMP SHALL | | | HAVE NOT LESS THAN 72" OF STRAIGHT & | | | LEVEL CLEARENCE. | | | 2C) THE PLANS DO NOT GIVE A REAR ELEVA- | | | TION. THERE CAN BE NO STAIRS FOR THE ACC | | | ESSIBLE ROUTE. THE MOST CHANGE IN GRADE | | | CAN BE 1/4" WITHOUT THE USE OF A RAMP. | | | 2D) FRONT ENTRY SIGNAGE REQUIRED: | | | 11-4.1.6(H) IF A PARTICULAR | | | ENTRANCE IS NOT MADE ACCESSIBLE, APPRO- | | | PRIATE ACCESSIBLE SIGNAGE INDICATING THE | | | LOCATION OF THE NEAREST ACCESSIBLE | | | ENTRANCE(S) SHALL BE INSTALLED AT OR | | | NEAR THE INACCESSIBLE ENTRANCE, SUCH | | | THAT A PERSON WITH DISABILITIES WILL | | | NOT BE REQUIRED TO RETRACE THE APPROACH | | | ROUTE FROM THE INNACCESSIBLE ENTRANCE. | | | | | | 3) COMMENT 5 FROM PREVIOUS REVIEW: | | | FL BLD CODE 1606.1.5: COMPONENTS & | | | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- | | | OLD OR RESIDENT INSPECTOR) OF PRODUCT | | | TESTING REPORTS,MISSING REPORTS ARE AS | | | FOLLOWS: | | | A) NEW WINDOWS | | | B) EXTERIOR DOORS IF REPLACED | | | PLANS ON 1ST REVIEW INDICATED NEW WIN- | | | DOWS NOTHING IS MENTIONED? | | | PLANS ON THE 1ST REVIEW DIDN'T ADDRESS | | | IF THE DOORS WERE TO BE REPLACED? PLEASE | | | GIVE A RESPONCE!! | | | PRODUCT APPROVALS SUBMITTED WITH | | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 | | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | | PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A COVER SHEET THAT LISTS | | | THE PRODUCT IDENTITY NUMBER FROM THE | | | STATE. IF THE PRODUCT DOES NOT HAVE | | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | | SPECIFIC FORM PER RULE 9B-72. SEE | | | ATTACHMENT. WWW.FLORIDABUILDING.ORG | | | | | | 4) TABLE 803.3 MINIMUM INTERIOR FINISH | | | CLASSIFICATION; PROVIDE INFORMATION | | | BASED ON INTERIOR FINISH REQUIREMENTS | | | BASED ON OCCUPANCY | | | | | | 5)1204.2 SURROUNDING MATERIALS; | | | THE WALLS & FLOORS OF ALL PUBLIC REST- | | | ROOMS SHALL BE LINED WITH NONABSORBANT | | | MATERIALS TO A HEIGTH OF 4'-0" ABOVE THE | | | FLOOR. | | | | | | 6)BEFORE A PERMIT TO CONSTRUCT, MAY | | | BE ISSUED, IMPACT FEES MUST BE PAID TO | | | PALM BEACH COUNTY. THE ACTUAL PERMIT | | | SET OF PLANS MUST BE STAMPED BY THAT | | | OFFICE, AND A COPY OF THE PAID RECEIPT | | | ATTACHED TO THE PERMIT APPLICATION. | | | PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | | | | LOOK FOR COMMENTS BY THE OTHER PLAN | | | REVIEW DISCIPLINES THAT MAY BE WRITTEN | | | ON THE APPLICATION, PLANS, OR ATTACHED | | | SEPARATELY. WHEN RESUBMITTING PLANS | | | PLEASE CLEARLY INDICATE THE REVISION AND | | | REMOVE AND REPLACE ANY PAGES AS NECESS- | | | ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH | | | THE PLANS WHEN RESUBMITTING PLANS. A | | | TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW NUMBER, WITH A DESCRIPTION OF THE | | | REVISION MADE, IDENTIFYING THE SHEET OR | | | SPECIFICATION PAGE WHERE THE CHANGES CAN | | | BE FOUND, WILL HELP TO EXPEDITE YOUR | | | PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | JIM WITMER | | | BUILDING PLAN REVIEW | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2004-04-09 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2004-04-09 |
Time |
10:26 |
Rev Time |
1.00 |
| Received By |
jwitmer |
Date |
2004-04-09 |
Time |
10:26 |
Sent To |
PC |
|
| Notes |
| 2004-04-09 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT: 04010010 | | | ADD: 320 PINE ST | | | CONT: BAINES | | | TEL: (561)635-6935 | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | | | | REVISION | | | ACTION: DENIED | | | | | | 1) CHANGE OF OCCUPANCY 3401.2.2.2 | | | CHANGES IN OCCUPANCY OF ANY EXISTING | | | BUILDING SHALL NOT BE MADE UNTIL A REVIS | | | ED CERTIFICATE OF OCCUPANCY HAS BEEN | | | ISSUED BY THE BUILDING OFFICIAL | | | CERTIFYING THAT THE FLOORS ARE SUITABLE | | | FOR THE LOADS CHARACTERISTICS OF THE | | | PROPOSED OCCUPANCY. | | | 2) 3401.3 THE BUILDING IS TO CONFORM TO | | | THE PROVISIONS OF THE TECHNICAL CODE AND | | | OTHER APPLICABLE LAWS AND ORDINANCES | | | FOR SUCH OCCUPANCY. | | | 3) INDICATE COMPLIANCE WITH ACCESSIBIITY | | | CODE, RAMPS FOR ACCESSIBLE ENTRANCE. | | | 4)FL. BLD CODE 1606.1.7 THE FOLLOWING | | | INFORMATION RELATED TO WIND SHALL BE | | | SHOWN ON THE CONSTRUCTION DRAWINGS, | | | 1)- BASIC WIND SPEED, MPH | | | 2)- WIND IMPORTANCE FACTOR, & BUILDING | | | CATEGORY | | | 3)- WIND EXPOSURE | | | 4)- INTERNAL PRESSURE COEFFICIENT, | | | 5)- COMPONENTS & CLADDING, THE DESIGN | | | WIND PRESSURES IN TERMS OF PSF. | | | 5) FL BLD CODE 1606.1.5: COMPONENTS & | | | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- | | | OLD OR RESIDENT INSPECTOR) OF PRODUCT | | | TESTING REPORTS,MISSING REPORTS ARE AS | | | FOLLOWS: | | | A) NEW EXTERIOR WINDOWS | | | B) EXTERIOR DOORS IF REPLACED? | | | 6) PLANS INDICATE OCCUPANCY IS FOR R3, | | | CHANGE TO BUSINESS. | | | 7) TABLE 803.3 MINIMUM INTERIOR FINISH | | | CLASSIFICATION; PROVIDE INFORMATION | | | BASED ON INTERIOR FINISH REQUIREMENTS | | | BASED ON OCCUPANCY | | | 8)1204.2 SURROUNDING MATERIALS; | | | THE WALLS & FLOORS OF ALL PUBLIC REST- | | | ROOMS SHALL BE LINED WITH NONABSORBANT | | | MATERIALS TO A HEIGTH OF 4'-0" ABOVE THE | | | FLOOR. | | | 9)BEFORE A PERMIT TO CONSTRUCT, MAY | | | BE ISSUED, IMPACT FEES MUST BE PAID TO | | | PALM BEACH COUNTY. THE ACTUAL PERMIT | | | SET OF PLANS MUST BE STAMPED BY THAT | | | OFFICE, AND A COPY OF THE PAID RECEIPT | | | ATTACHED TO THE PERMIT APPLICATION. | | | PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | LOOK FOR COMMENTS BY THE OTHER PLAN | | | REVIEW DISCIPLINES THAT MAY BE WRITTEN | | | ON THE APPLICATION, PLANS, OR ATTACHED | | | SEPARATELY. WHEN RESUBMITTING PLANS | | | PLEASE CLEARLY INDICATE THE REVISION AND | | | REMOVE AND REPLACE ANY PAGES AS NECESS- | | | ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH | | | THE PLANS WHEN RESUBMITTING PLANS. A | | | TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW NUMBER, WITH A DESCRIPTION OF THE | | | REVISION MADE, IDENTIFYING THE SHEET OR | | | SPECIFICATION PAGE WHERE THE CHANGES CAN | | | BE FOUND, WILL HELP TO EXPEDITE YOUR | | | PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | JIM WITMER | | | BUILDING PLAN REVIEW | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
N |
Date |
2004-01-05 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2004-01-05 |
Time |
08:45 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2004-01-05 |
Time |
08:45 |
Sent To |
|
|
| Notes |
| 2004-01-05 00:00:00 | OK PER RYAN N |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2004-05-28 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2004-05-28 |
Time |
11:43 |
Rev Time |
0.45 |
| Received By |
jleahy |
Date |
2004-05-28 |
Time |
11:42 |
Sent To |
P |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2004-04-28 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-04-28 |
Time |
05:47 |
Rev Time |
0.50 |
| Received By |
dpalmer |
Date |
2004-04-28 |
Time |
05:47 |
Sent To |
|
|
| Notes |
| 2004-04-28 00:00:00 | ********** UNSAT ********* | | | | | | PLEASE SEE SOME NOTES FORM FIRST REVIEW | | | NOT DONE AND THERE ARE ALOS NEW NOTES. | | | | | | 1)NOTE: PLEASE SHOW ALL CIRCUITING ON | | | PLANS AND CORRELATE WITH A SUBMITTED | | | PANEL SCHEDULE. | | | PANEL SCHEDULE MUST SHOWS CIRCUIT #'S, | | | OCP, AWG ETC. | | | | | | 2)NOTE: PLEASE SEE NEC FOR DERATING | | | OF INDIVIDUAL BRANCH CIRCUITS IN 1" | | | SCH80 PVC CONDUIT. 240,TABLES ETC. | | | | | | 3)NOTE: PLEASE SHOW A/C EQUIPMENT ON | | | ELECTRICAL PLANS ALONG WITH DISC AS | | | REQ'D PER 440.11. | | | | | | 4)NOTE: PLEASE SHOW RECEPTS REQ'D UNDER | | | 210.63 FOR A/C EQUIPMENT. | | | | | | 5)NOTE: PLEASE SEE BLDG USE IS BEING | | | CHANGED FROM RESIDENCE TO COMM. | | | PLEASE SEE TWO METER SYSTEM MUST BE | | | REMOVED AND BE INSTALLED BACK TO SINLGE | | | METER INSTALLATION. | | | PLEASE ADJUST SERVICE ACCORD. | | | | | | 6)NOTE: PLEASE SEE 700.12E FOR CIRCUIT- | | | -ING OF EM/EXT LTS. | | | | | | 7)NOTE: PLEASE HAVE ENGINEER SIGN WITH | | | COMPLETE "SIGNATURE" AS SHOWN ON LICENSE | | | /RAISED SEAL AS REQ'D UNDER FS 471.025 | | | INITIALS ARE NOT ACCEPTABLE PER FBPE'S. | | | PLEASE ALSO CLARIFY BBC DESIGN ON | | | TITLE BLOCK?? 61G15-23.002/ 61G1-16.004? | | | | | | 8)NOTE: PLEASE SEE FBC 104.6.5, VALUE | | | FOR SCOPE OF WORK NEEDS TO BE INCREASED | | | DUE TO SCOPE PF WORK BEING PERFORMED. | | | VALUE IS INCLUDE ALL LABOR AND MATERIALS | | | PLEASE SEE BLDG REVIEW COMMENTS. | | | | | | 9)NOTE: PLEASE SEE COPY OF FS 553.80(2) | | | (B) FOR PLANS REVIEWED FOR SAME COMMENTS | | | IF PLANS COME BACK IN FOR 3RD REVIEW, | | | AND ANY OF THE SAME COMMENTS FROM | | | PREVIOUS TWO REVIEWS ARE NOT ADDRESSED | | | A 4X FEE SHALL BE ISSUED. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2004-03-30 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-04-27 |
Time |
14:14 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2004-03-30 |
Time |
08:05 |
Sent To |
|
|
| Notes |
| 2004-03-30 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} SHOW EXIT AND EMERGENCY LIGHTS PER | | | NFPA-101 AND ARTICLE 700 NEC.SEE FIRE | | | REVIEW COMMENTS. | | | | | | 2} PLEASE SHOW CIRCUIT NUMBERS AT ALL | | | LUMINAIRES AND DEVICES. | | | | | | 3} PROVIDE A PANEL SCHEDULE WITH | | | CORRESPONDIG CIRCUIT NUMBERS. | | | | | | 4} PLEASE INDICATE THE LOCATION OF THE | | | SERVICE EQUIPMENT, INCLUDING PANEL | | | LOCATION(S) | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2004-05-20 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2004-05-20 |
Time |
09:40 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2004-05-20 |
Time |
09:40 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2004-04-28 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2004-04-28 |
Time |
13:19 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2004-04-28 |
Time |
13:19 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2004-03-19 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2004-03-19 |
Time |
14:31 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2004-03-19 |
Time |
14:31 |
Sent To |
|
|
| Notes |
| 2004-03-19 00:00:00 | 1) ACCORDING TO PERMIT APPLICATION, THE | | | BUILDING WAS FORMERLY RESIDENTIAL AND | | | IS BEING CHANGED TO BUSINESS. THIS | | | CONVERSION WILL BE CLASSIFIED AS A | | | CHANGE OF USE. | | | | | | 2) BUILDING ADDRESS REQUIRED. A MINIMUM | | | OF 6" HIGH NUMBERS ARE REQUIRED. | | | | | | 3) HANDRAILS REQUIRED ON BOTH SIDES | | | OF ALL STAIRS AND RAMPS. | | | | | | 4) NO EXIT SIGNS OR EMERGENCY LIGHTS | | | SHOWN. | | | | | | 5) NO INFORMATION PROVIDED WITH REGARDS | | | TO PORTABLE FIRE EXTINGUISHERS. | | | | | | 6) NO INFORMATION PROVIDED WITH REGARDS | | | TO PORTABLE FIRE EXTINGUISERS. | | | | | | 7) PLEASE PROVIDE INFORMATION ABOUT | | | EXTERIOR DOOR LOCKS. | | | | | | 8) DOOR LEADING FROM OFFICE TO EXTERIOR | | | DOOR CANNOT BE SUBJECT TO LOCKING IF | | | AN EXIT DOOR IS PRESENT. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2004-06-02 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-06-02 |
Time |
07:45 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-06-02 |
Time |
07:45 |
Sent To |
|
|
| Notes |
| 2004-06-02 00:00:00 | TO COMM BD#22 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2004-05-18 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-05-18 |
Time |
15:16 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-05-18 |
Time |
15:16 |
Sent To |
|
|
| Notes |
| 2004-05-18 00:00:00 | TO COMM BD#21 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2004-04-27 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-04-27 |
Time |
14:14 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-04-27 |
Time |
14:14 |
Sent To |
|
|
| Notes |
| 2004-04-27 00:00:00 | TO COMM BD#7 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2004-03-19 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-03-19 |
Time |
12:36 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-03-19 |
Time |
12:36 |
Sent To |
|
|
| Notes |
| 2004-03-19 00:00:00 | TO COMM BD#49 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2004-05-28 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2004-05-28 |
Time |
13:07 |
Rev Time |
0.30 |
| Received By |
pkrauss |
Date |
2004-05-28 |
Time |
13:07 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2004-05-13 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2004-05-11 |
Time |
11:19 |
Rev Time |
0.30 |
| Received By |
pkrauss |
Date |
2004-05-11 |
Time |
11:19 |
Sent To |
|
|
| Notes |
| 2004-05-11 00:00:00 | PLANS NEED TO BE STAMPED | | | PER MEETING WITH GENERAL CONTRACTOR & | | | OWNERS; RESIDENTIAL BUILDING CONVERTED | | | TO OFFICE BUILDING.WINDOWS ARE | | | OPERABLE & INSTALLED PRIOR TO 1979. | | | OUTSIDE AIR PER NATURAL VENTILATION | | | 402.2. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2004-04-28 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2004-04-28 |
Time |
12:43 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2004-04-28 |
Time |
12:16 |
Sent To |
|
|
| Notes |
| 2004-04-28 00:00:00 | DENIED: | | | PLAN SHEET M-1 INDICATES FRESH AIR BY | | | NATURAL MEANS 402.2.PROVIDE | | | CALCULATION SHOWING 4% OF THE FLOOR | | | SPACE TO THE OPENABLE AREA OF THE | | | WINDOWS & DOORS.PROVIDE TEST RESULTS | | | FROM THE TESTING AGENCY INDICATING THE | | | ACTUAL FILTRATION RATE.PROVIDE THIS | | | INFORMATION FOR EACH WINDOW & DOOR. | | | INDICATE CALCUALTION ON THE PLAN SHOWING | | | COMPLAINCE WITH 402.2. | | | | | | PLAN ALSO INDICATES CIRCULATION RATE | | | PER F.P.C. (FBC?) 403.3.PLEASE | | | INDICATE WHICH MEANS WILL BE USED AND | | | SHOW CALCULATION ON THE PLAN. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2004-04-06 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2004-04-06 |
Time |
11:19 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
2004-04-06 |
Time |
11:19 |
Sent To |
|
|
| Notes |
| 2004-04-06 00:00:00 | DENIED: | | | 1.PLEASE PROVIDE OUTSIDE AIR | | | CALCULATIONS PER 2001 FBC(M) 403.3. | | | | | | 2.INDICATE OUTSIDE AIR INTAKE, DUCT | | | SIZE, MATERIAL AND LAYOUT. | | | | | | 3.PLAN SHEET M-1 INDICATES 3 TON | | | SYSTEM, INDICATE IF THE EQUIPMENT IS | | | NEW OR EXISTING. | | | | | | 4.AUXILIARY DRAIN PAN WITH OVERFLOW | | | PROTECTION REQUIRED PER 2001 FBC(M) | | | 307.2.3. | | | | | | 5.PLEASE NOTE THE LOCATION OF THE AHU | | | SHALL HAVE SUFFICIENT SPACE TO ALLOW FOR | | | INSPECTION, SERVICE, REPAIR OR REPLACE- | | | MENT.2001 FBC(M) 306.1. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2004-06-03 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2004-06-03 |
Time |
13:38 |
Rev Time |
2.00 |
| Received By |
kstevens |
Date |
2004-06-03 |
Time |
13:38 |
Sent To |
|
|
| Notes |
| 2004-06-03 00:00:00 | REVISION OK - SECOND BATH TO BE ADAPT- | | | ABLE. DOOR TO BE CHANGED TO HAVE ACCESS | | | FROM SINGLE OFFICE ONLY. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2004-05-28 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2004-05-28 |
Time |
13:27 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2004-05-28 |
Time |
13:27 |
Sent To |
|
|
| Notes |
| 2004-05-28 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | FBC-2001 CHAPTER 11 | | | FLORIDA STATUTES | | | | | | A) FROM PREVIOUS REVIEWS: | | | 2) IF TOILET ROOMS ARE PROVIDED, THEN | | | EACH PUBLIC AND COMMON USE TOILET ROOM | | | SHALL COMPLY WITH 11-4.22. SUBMIT A DE- | | | TAIL SHOWING COMPLIANCE WITH 11-4.16, | | | 11-4.19, AND 11-4.22 AND ALL SUBSECTIONS | | | 11-4.1.3(11). | | | - HEIGHT OF TOILET NOT SHOWN 11-4.16.3, | | | CLEAR FLOOR SPACE/TURNING AREA 11-4.16.2 | | | 11-4.22.3. GRAB BARS NOT SHOWN IN TOILET | | | ROOM BY KITCHEN 11-4.16.4, CLEAR FLOOR | | | SPACE FOR TOILETS 11-4.16.2, CLEAR FLOOR | | | SPACE FOR LAV IN TOILET BY KITCHEN AREA | | | 11-4.19.3, EXPOSED PIPES AND SURFACES | | | 11-4.19.4, DOORS SHALL NOT SWING INTO | | | THE CLEAR FLOOR SPACE OF ANY FIXTURE | | | 11-4.22.2(1). | | | 3) SHT E-1 SANITARY RISER DIAGRAM DOES | | | NOT MEET CODE, EXTRA VENT LINE OFF LAV | | | STACK IS A HORIZONTAL DRY VENT AND IS | | | NOT REQUIRED. DELETE FROM RISER DIAGRAM. | | | SECTION 905.3 - 704.5 | | | | | | INFORMATIONAL: SEE ATTACHED SHEET FOR | | | DESIGN PROFESSIONAL CONCERNING FLORIDA | | | STATUTE 553.80(2)(B). | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2004-05-11 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2004-05-28 |
Time |
11:43 |
Rev Time |
1.00 |
| Received By |
kstevens |
Date |
2004-05-11 |
Time |
14:00 |
Sent To |
|
|
| Notes |
| 2004-05-11 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | FBC-2001 CHAPTER 11 | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | A) FROM PREVIOUS REVIEW: COMMENTS NOT | | | ADDRESSED TO CODE SATISFACTION. NUMBER | | | OF COMMENT FROM FIRST REVIEW TO STAY THE | | | SAME TO AVOID CONFUSION. | | | 2) IF TOILET ROOMS ARE PROVIDED, THEN | | | EACH PUBLIC AND COMMON USE TOILET ROOM | | | SHALL COMPLY WITH 11-4.22. SUBMIT A DE- | | | TAIL SHOWING COMPLIANCE WITH 11-4.16, | | | 11-4.19, AND 11-4.22 AND ALL SUBSECTIONS | | | - SECTION 11-4.1.3(11). RESPONSE NOTED, | | | BUT HEIGHT OF TOILET NOT SHOWN 11-4.16.3 | | | CLEAR FLOOR SPACE/TURNING AREA 11-4.16.2 | | | GRAB BARS NOT SHOWN IN TOILET ROOM BY | | | KITCHEN 11-4.16.4, CLEAR FLOOR SPACE FOR | | | LAV 11-4.19.3, EXPOSED PIPES & SURFACES | | | 11-4.19.4, DOORS SHALL NOT SWING INTO | | | THE CLEAR FLOOR SPACE FOR ANY FIXTURE | | | 11-4.22.2(1). | | | 3) SHT E-1 SANITARY RISER DIAGRAM DOES | | | NOT REFLECT THE FLOOR PLAN. THE ACCESSI- | | | BLE TOILET ROOM SHOULD BE LOCATED ON THE | | | LEFT SIDE OF THE BLDG. DRAIN. IF THE | | | BUILDING HAS TWO BLDG. DRAINS THEN A C/O | | | IS REQUIRED AS EACH BLDG. DRAIN EXITS | | | THE BLDG. SECTION 708.3.5 - REMOVE THE | | | DRINKING FOUNTAIN FROM THE SANT. RISER | | | DIAGRAM, HAND DRAWN CHANGES TO A SIGNED | | | AND SEALED SET OF PLANS IS NOT APPROVED. | | | 4) KITCHEN SINK SHALL COMPLY WITH SECT- | | | ION 11-4.24 AND ALL SUBSECTIONS. CLEAR | | | FLOOR SPACE FOR SINK IS NOT SHOWN. SEE | | | SECTION 11-4.24.5 | | | NEW COMMENT...................... | | | 1B) ENGINEERS SHALL SIGN PLAN WITH A | | | SIGNATURE. PER FBPE'S RULING INITIALS | | | ARE NOT ACCEPTABLE. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2004-03-23 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2004-03-23 |
Time |
15:48 |
Rev Time |
1.00 |
| Received By |
kstevens |
Date |
2004-03-23 |
Time |
15:48 |
Sent To |
|
|
| Notes |
| 2004-03-23 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | FBC-2001 CHAPTER 11 | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | 1) A DRINKING FOUNTAIN IS REQUIRED PER | | | TABLE 403.1 | | | 2) IF TOILET ROOMS ARE PROVIDED, THEN | | | EACH PUBLIC AND COMMON USE TOILET ROOM | | | SHALL COMPLY WITH 11-4.22. SUBMIT A DE- | | | TAIL SHOWING COMPLIANCE WITH 11-4.16, | | | 11-4.19, AND 11-4.22 AND ALL SUBSECTIONS | | | - SECTION 11-4.1.3(11) | | | 3) SHT E-1 SANITARY RISER DIAGRAM DOES | | | NOT REFLECT THE FLOOR PLAN. THE ACCESS- | | | IBLE TOILET ROOM SHOULD BE LOCATED ON | | | THE LEFT SIDE OF THE BLDG. DRAIN AND | | | SHOWS TWO FIXTURES ON THE LAV STACK. | | | THE OTHER TOILET ROOM NEAR THE KITCHEN | | | SHOWS NO LAV. | | | 4) KITCHEN SINK SHALL COMPLY WITH SECT- | | | ION 11-4.24 AND ALL SUBSECTIONS. SUBMIT | | | A DETAIL SHOWING COMPLIANCE. | | | 5 ENGINEERS SHALL LEGIBLY INDICATE THEIR | | | NAME, ADDRESS AND LICENSE NUMBER ON EACH | | | SHEET. FAC 61G1-15.002(2) - FS 471.025 | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2004-03-18 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2004-03-18 |
Time |
16:09 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2004-03-18 |
Time |
16:09 |
Sent To |
I |
|
| Notes |
| 2004-03-18 00:00:00 | PROVISO: STREET HEDGE AT THREE FEET SIX | | | INCHES AROUND THE PARKING LOT IN REAR |
|
|