Plan Review Details - Permit 04010007
Plan Review Stops For Permit 04010007
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2005-02-02 Cont ID  
Sent By rmcdouga Date 2005-02-02 Time 07:44 Rev Time 0.00
Received By rmcdouga Date 2005-02-02 Time 07:43 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2005-01-31 Cont ID  
Sent By rmcdouga Date 2005-01-31 Time 16:34 Rev Time 0.00
Received By rmcdouga Date 2005-01-31 Time 16:04 Sent To  
Notes
2005-01-31 00:00:00DENIED
  
 1) THE TRUSS DRAWINGS THAT WERE
 SUBMITTED ARE FOR THE "B" ELEVATION AND
 THIS IS THE "A" ELEVATION.
  
 2) FBC 18O4.1.3 REQUIRES TO BOTTOM OF
 FOOTERS TO BR A MINIMUM OF 12" BELOW
 GRADE. CORRECT SHEET A16.
  
 3) THE SOFFIT NOTE ON A20 CALLS FOR
 STUCCO OVER 5/8" PLYWOOD. THIS IS THE
 NOTE FOR THE FRAME WALLS. PLYWOOD IS NOT
 INSTALLED BEHIND THE LATH ON THE
 SOFFITS.
  
 4) THE PRODUCT APPROVAL FOR THE SINGLE
 HUNG WINDOWS IS MISSING THE INSTALLATION
 DRAWINGS FOR CONCRETE OR MASONRY
 OPENINGS.
  
 5) THE PRODUCT APPROVALS FOR THE FIXED
 GLASS WINDOWS ARE NOT CORRECT. THE
 DRAWING NUMBERS ON PAGE ONE AND PAGE TWO
 DO NOT MATCH AND THE WINDOWS ARE NOT
 CURVED AT THE TOP.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2004-12-13 Cont ID  
Sent By rmcdouga Date 2004-12-13 Time 15:45 Rev Time 0.00
Received By rmcdouga Date 2004-12-13 Time 15:45 Sent To  
Notes
2004-12-13 00:00:00DENIED
  
 1) THE ENERGY CALCULATIONS LIST THE
 CEILING INSULATION AS R-19 AND THE PLANS
 SPECIFY R-30. THE ENERGY CALCS. LIST
 EXTERIOR WOOD FRAME WALLS WITH R-11
 INSULATION AND THE PLANS SPECIFY 2X6
 WALL WITH R-19. PLEASE CORRECT.
  
 2) FAC 61G15-23.002 REQUIRES THE
 ORIGINAL WET SIGNATURE OF THE TRUSS
 ENGINEER TO BE ON THE TRUSS LAYOUT PLANS
 AND DRAWINGS.
  
 3) THE CEMENTITIOUS FINISH ON THE SOFFIT
 IS REQUIRED TO BE 5/8" THICK PER FBC
 25O4.2.1 AND ASTM C 926.
  
 4) SUBMIT PRODUCT APPROVALS AND SPECS.
 FOR THE ONE HOUR FIRE RATED GLASS
 BLOCK.
  
 5) SUBMIT THE EVALUATION REPORT FOR THE
 STRUCTURAL MULLIONS LISTING THE DESIGN
 PRESSURES.
  
 6) SUBMIT THE INSTALLATION DRAWINGS AND
 DESIGN PRESSURES FOR THE SINGLE HUNG
 WINDOWS.
  
 7) SUBMIT THE PRODUCT APPROVALS FOR THE
 FIXED GLASS WINDOWS.
  
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-10-14 Cont ID  
Sent By rmcdouga Date 2004-10-14 Time 11:30 Rev Time 0.00
Received By rmcdouga Date 2004-10-14 Time 14:32 Sent To  
Notes
2004-10-14 00:00:00"MASTER" 6 UNIT/2 STORY
  
 DENIED
  
 1)REDLINE CHANGES INITIALED AND DATED BY
 THE DESIGNER OF RECORD ARE NOT ALLOWED
 ON A "MASTER" PLAN. REVISE SHEET A-15
 WHICH HAS BEEN REDLINED BY D.O.R.
  
 2) REVISE THE PLYWOOD SHEATHING NAILING
 SCHEDULE ON S-4 TO CLARIFY THAT THE 8D
 RING SHANK NAILS ARE REQUIRED FOR THE
 ROOF SHEATHING IN ZONE 3 ONLY.
  
 3) REVISE NOTE #7 ON S2 TO 8F8-1B, NOT
 8FB-1B.
  
 4) REVISE THE NOTE FOR THE DOORS IN THE
 GARAGE DEMISING WALLS TO SAY 3/4 HOUR
 FIRE RATED DOORS, ON SHEETS A-1, A-3,
 A-4 AND A7.
  
 5) SPECIFY THE EMBED DEPTH OF THE 3/4"
 DIA. ANCHOR BOLTS FOR THE STEEL COLUMN
 BASES IN NOTE 6 ON S-1.
  
 6) SECTION 8 ON S-6 IS INCORRECTLY
 SPECIFIED ON SHEET S-3 FOR THE WALL
 BETWEEN UNITS #3L AND 3R. THE TRUSSES
 ARE PARALLEL TO THE WALL AT THIS
 LOCATION. PLEASE CORRECT.
  
 7) THE TRUSS LAYOUT AND DRAWINGS SHOW A
 2 MEMBER GRO3 ROOF TRUSS PARALLEL TO THE
 THE WALL BETWEEN UNITS #3L AND 3R. THIS
 TRUSS HAS A TOP CORD THAT IS FLAT. THIS
 IS NOT INDICATED ON THE PLANS AND NO
 CONNECTORS ARE SPECIFIED. SEE SECTION 1
 ON S-6. PLEASE REVIEW AND MAKE THE
 NECESSARY CORRECTIONS.
  
 8)REVISE THE UPLIFT VALUE OF THE SIMPSON
 HETAL 20 CONNECTOR IN THE SCHEDULE ON
 S-3 TO 1810#, WHICH IS THE VALUE IN THE
 2004 SIMPSON CATALOG TABLE ON PAGE 127,
 WHICH INCLUDES THE LOAD DURATION
 INCREASE ATTRIBUTED TO THE PROPETIES OF
 WOOD BUT NOT THE STRESS INCREASE ON THE
 STEEL CAPACITY, WHICH IS NOT ALLOWED BY
 THE FLORIDA BUILDING CODE. SEE ATTACHED.
  
 9) PLEASE GATHER ALL PRODUCT APPROVALS
 FROM PREVIOUS SUBMITTALS AND COMBINE
 WITH THE NEW SUBMITTALS TO MAKE 3
 COMPLETE SETS OF PLANS AND PRODUCT
 APPROVALS.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-02-11 Cont ID  
Sent By jwitmer Date 2004-02-10 Time 10:26 Rev Time 3.75
Received By jwitmer Date 2004-02-10 Time 10:26 Sent To PC
Notes
2004-02-10 00:00:00 
 BUILDING PLAN REVIEW
 PERMIT: 04010007
 ADD: 1100 N CONGRESS
 CONT: WCI COMMUNITIES
 CONTACT PERSON: DOUG BERK
 TEL: (561)262-3684
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 ARCH: WCI ARCHITECTURE & LAND PLANNING
 CONTACT: PETER SNYOYANNIS
 (954) 575-4200
  
 1ST REVIEW
  
 THE COMMENTS FROM 0410005 (4) UNIT
 BUILDING ARE APPLICIABLE ACCEPT FOR THE
 FAIR HOUSING.
 ADDITIONAL COMMENTS:
 1)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 DISCREPANCY IN UNIT# 2. A-1, A-18 DETAIL
 #3 AND S-2, DEPENDING ON WHICH PAGE OR
 SECTION, VIEWED.A RATED METAL STUD WALL
 WITH BEAM ABOVE, NO INFO ON BEAM OR
 S-1 INDICATING THE USE OF A WOOD POST?
 2101.3.2 MASONRY SHALL NOT BE SUPPORTED
 BY WOOD GIRDERS OR OTHER FORMS OF WOOD.
  
 2) S-3 TRUSS PLAN DOES NOT INDICATE THE
 TRUSS OR GIRDER LOADS, VERTICAL, HORI-
 ZONTAL AND GRAVITY LOADS TO BE RESISTED.
  
 3) S-2 MASONARY WALLS ARE DESIGNATED AS
 MW-1, S-4 MASONARY WALLS SCHEDULE IS
 #5@48" O.C. NO INFO AS TO FILLED CELLS
 AT WINDOWS, CORNERS ETC?
  
 4) GARAGE BEAMS DO NOT GIVE IF LINTELS
 ARE TO BE USED? WHAT THE ALLOWABLE SAFE
 LOADS ARE?
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-01-13 Cont ID  
Sent By dpalmer Date 2005-01-13 Time 16:03 Rev Time 0.33
Received By dpalmer Date 2005-01-13 Time 16:00 Sent To  
Notes
2005-01-13 00:00:00RE-STAMPED E-2

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-10-08 Cont ID  
Sent By dpalmer Date 2004-10-08 Time 16:43 Rev Time 1.00
Received By dpalmer Date 2004-10-08 Time 16:43 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-01-12 Cont ID  
Sent By dpalmer Date 2004-01-12 Time 15:00 Rev Time 1.00
Received By dpalmer Date 2004-01-12 Time 15:00 Sent To  
Notes
2004-01-12 00:00:00*********** UNSAT ******************
  
 1)NOTE: PLANS REFERENCE 1999 NEC.
 WE ARE UNDER THE 2002 NEC
 7/1/2003
  
 2)NOTE: PLEASE NOTE, ALL PLANS DRAWN
 BY AN ARCHITECT/ENGINEER CONTAIN-
 -ING A TITLE BLOCK: MUST BE SIGNED,
 DATED AND SEALD BY THAT ARCH/ENG.
 PER FS 481.221 471.025
 FAC 61G15-23.002, 61G1-16.004
  
 3)NOTE: PLEASE PROVIDE ALL LICENSE #`'S
 ON TITLE BLOCK(S) AS REQ'D UNDER FAC
 61G15-23.002 / FS 471.023
  
 4) NOTE: PLEASE LIST ALL THE REQ'D
 DEDICATED BATH(S) CIRCUIT(S) ON PANEL
 SCHEDULE. PER 210.52D, 210.11C3
  
 5))NOTE: PLEASE SEE MISSING REQ'D EGRESS
 LIGHTING AND/OR CLARIFY EGRESS LIGHTING
 PER 210.70 AND LS-101 5-8
  
 6) NOTE: PLEASE SHOW GROUNDING ELETRODE
 SYSTEM PER 250.50. FOOTER STEEL/COLD
 WATER/ ETC. SIZE ALL PER 250.66
  
 7)) NOTE: PLEASE SEE MISSING RECEPTS FOR
 FRONT AND/OR REAR OF DWELLING.
 210.52EREAR
  
 8)NOTE: PLEASE SEE RISER DIAGRAM, SHOWS
 EMT AS BEING DIRECT BURIAL FOR FEEDERS.
 PLEASE SEE THIS IS NOT PERMITTED UNDER
 LOCAL AMENDMENTS 348-5.
 ALSO SEE 358 NEC
  
 PLEASE SEE COMMENTS FROM OTHER REVIEWERS
 AS THEY MAY AFFECT ELECTRICAL PLANS.
 PLEASE ALSO NOTE: INFORMATION REQ'D ON
 TITLE BLOCKS FOR ARCHS/ENGS ARE REQ'D
 OF ALL TRADES AND ALL SHEETS, WEATHER
 OR NOT COMMENT IS MADE BY OTHER REVIEW-
 -ERS.
  
 9)NOTE: PLEASE LIST/SHOW ALL HEIGHTS
 UNDER FHAR CFR 100.205.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2004-01-09 Cont ID  
Sent By mamini Date 2004-01-09 Time 10:01 Rev Time 1.00
Received By mamini Date 2004-01-09 Time 10:01 Sent To  
Notes
2004-01-09 00:00:00PASSED:
 1. SEE PERMIT # 03101412 FOR UNDERGROUND
 UTILITIES AND SITE WORK (PLAN REVIEW).
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-11-05 Cont ID  
Sent By csiegber Date 2004-10-27 Time 12:10 Rev Time 0.00
Received By csiegber Date 2004-10-27 Time 12:10 Sent To  
Notes
2004-11-02 00:00:00PASSED PER MIKE CARSILLO

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-01-08 Cont ID  
Sent By mcarsill Date 2004-01-08 Time 17:50 Rev Time 0.00
Received By mcarsill Date 2004-01-08 Time 17:50 Sent To  
Notes
2004-01-08 00:00:001) WET FIRE HYDRANTS ARE REQUIRED PRIOR
 TO, DURING AND AFTER CONSTRUCTION.
  
 2) BUILDING ADDRESSES ARE REQUIRED.
 COULD NOT LOCATE THEM ON ELEVATION
 DRAWINGS.
  
 3) ENTRY DOORS SHOULD BE AT LEAST
 20 MINUTE FIRE RATED.
  
 4) PLEASE VERIFY IF ONE HOUR TENANT
 DEMISING WALLS WILL BE ACCEPTED BY
 THE CONSTRUCTION SERVICES DEPARTMENT.
 ONE HOUR WALLS ARE ALLOWED IN APARTMENTS
 BUT TOWNHOMES USUALLY REQUIRE TWO
 HOUR DEMISING WALLS. ARE THESE UNITS
 RENTALS OR ARE THEY GOING TO BE SOLD
 AND BE FEE SIMPLE. PLEASE ADVISE.
  
 5) ANY AND ALL THREE STORY BUILDINGS
 IN THE DEVOLPMENT WILL REQUIRE FIRE
 SPRINKLER PROTECTION.
  
 6) IF SECURITY GATES ARE PROVIDED,
 TWENTY FEET IN CLEAR WIDTH WILL BE
 REQUIRED FOR FIRE RESCUE ACCESS. A
 KNOX-BOX KEY SWITCH WILL BE REQUIRED.
  
 7) COULD NOT LOCATE FIRE EXTINGUISHERS.
 PLEASE ADVISE LOCATIONS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-01-11 Cont ID  
Sent By mjacobs Date 2005-01-11 Time 12:50 Rev Time 0.00
Received By mjacobs Date 2005-01-11 Time 12:49 Sent To  
Notes
2005-01-11 00:00:00TO "COMM BD#37/RESUB.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-11-15 Cont ID  
Sent By csiegber Date 2004-11-15 Time 10:27 Rev Time 0.00
Received By csiegber Date 2004-11-15 Time 10:27 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-11-02 Cont ID  
Sent By csiegber Date 2004-11-02 Time 12:05 Rev Time 0.00
Received By csiegber Date 2004-11-02 Time 12:05 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-10-07 Cont ID  
Sent By csiegber Date 2004-10-07 Time 16:19 Rev Time 0.00
Received By csiegber Date 2004-10-07 Time 16:19 Sent To  
Notes
2004-10-07 00:00:00TO COMM BD#43

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-01-02 Cont ID  
Sent By csiegber Date 2004-01-02 Time 13:12 Rev Time 0.00
Received By csiegber Date 2004-01-02 Time 13:12 Sent To  
Notes
2004-01-02 00:00:00TO COMM BD#33

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2005-01-20 Cont ID  
Sent By pkrauss Date 2005-01-20 Time 15:46 Rev Time 0.45
Received By pkrauss Date 2005-01-20 Time 15:46 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-11-04 Cont ID  
Sent By pkrauss Date 2004-11-04 Time 10:17 Rev Time 0.45
Received By pkrauss Date 2004-11-04 Time 10:16 Sent To  
Notes
2004-11-04 00:00:00PLAN CHECK ONLY

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-01-22 Cont ID  
Sent By pkrauss Date 2004-01-22 Time 06:41 Rev Time 1.50
Received By pkrauss Date 2004-01-22 Time 06:41 Sent To  
Notes
2004-01-22 00:00:00DENIED:
 1.PLANS ARE NOT SIGNED SEALED AND
 DATED BY THE ENGINEER AS REQUIRED BY FS
 471.025 & THE FAC 61G15-23.002.
  
 2.PLAN SHEET A-17 & DETAIL 2 ON PLAN
 SHEET A-21 INDICATE A 1 HOUR FIRE RATED
 FLOOR/CEILING ASSEMBLY.UNITS 2R, 3R,
 3L, 2L GRILLES TERMINATING AT THE
 CEILING SHALL HAVE PROTECTION.
 DUCTWORK PENTRATING RATED ASSEMBLY TO
 THE SECOND FLOOR SHALL BE PROTECTED BY
 MEANS OF A FIRE DAMPER OR "RATED SHAFT"
 ASSEMBLY.PLEASE REIVSE PLANS TO
 INCLUDE DETAILS FOR THESE TYPE OF
 PENTRATIONS.
  
 3.PLEASE PROVIDE OUTSIDE AIR
 CALCULATIONS PER 2001 FBC(M) 403.3.
  
 4.INDICATE OUTSIDE AIR INTAKE, DUCT
 SIZE, MATERIAL AND LAYOUT.
  
 5.RETURN AIR JUMPER ARE NOT SIZED
 PROPERLY.MASTER BEDROOMS ARE TO
 INCLUDE ALL SUPPLY AIR TO THE MASTER
 SUITE (CLOSETS, BATHROOM, ETC).PLEASE
 SEE THE ATTACHED SCHEDULE FOR PROPER
 SIZING OF RETURN AIR.
  
 6.ENERGY AND MANUAL J CALCULATIONS
 REQUIRED FOR APPROVAL PER 2001 FBC
 CHAPTER 13.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 3 Status P Date 2004-12-13 Cont ID  
Sent By kstevens Date 2004-12-13 Time 08:03 Rev Time 0.60
Received By kstevens Date 2004-12-11 Time 18:03 Sent To B1
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2004-10-15 Cont ID  
Sent By kstevens Date 2004-10-15 Time 21:10 Rev Time 0.50
Received By kstevens Date 2004-10-15 Time 21:10 Sent To  
Notes
2004-10-15 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) SHT P-3 SANITARY RISER DIAGRAM DOES
 NOT MEET CODE REQUIREMENTS. - ALSO SEE
 SHT P-1 FLOOR PLAN, (B UNIT LEFT)AND
 SHT P-2 FLOOR PLAN, (A UNIT LEFT) SANT.
 LAYOUT.
 A) WATER CLOSET IS NOT VENTED PER SECT-
 ION 908.3 (B UNIT)
 B) TWO SANITARY LINES ARE SHOWN FOR THE
 LAVS. (A UNIT)
 2) SHTS P-2, & P-3 REQUIRE A CERTIFICATE
 OF AUTHORIZATION AS "ENGINEERS" IMPLIES
 A PARTNERSHIP. FS 481.219 & FAC 61G1-16.
 003.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-01-22 Cont ID  
Sent By kstevens Date 2004-01-22 Time 12:02 Rev Time 1.00
Received By kstevens Date 2004-01-22 Time 11:53 Sent To  
Notes
2004-01-22 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FLORIDA ADMIN. CODE
 FLORIDA STATUTES
  
 1) A SANITARY AND A WATER RISER DIAGRAM
 ARE REQUIRED PER SECTION 104.3.1.1
 2)PROFESSIONAL ENGINEER SHALL SIGN HIS
 NAME AND AFFIX HIS SEAL TO ALL PLANS,
 SPECIFICATIONS, REPORTS AND FINAL BID
 DOCUMENTS PROVIDED TO THE OWNER OR THE
 OWNER'S REPRESENTATIVE, OR OTHER DOCU-
 MENTS PREPARED OR ISSUED BY SAID REGIS-
 TRANT AND BEING FILED FOR PUBLIC RECORD.
 THE DATE THAT THE SIGNATURE AND SEAL IS
 AFFIXED AS PROVIDED HEREIN SHALL BE EN-
 TERED ON SAID PLANS, SPECIFICATIONS, RE-
 PORTS, OR OTHER DOCUMENTS IMMEDIATELY
 UNDER THE SIGNATURE OF THE PROFESSIONAL
 ENGINEER, FAC 61G15-23.002(1)
  
 EACH SHEET OF PLANS AND PRINTS WHICH
 MUST BE SEALED UNDER THE PROVISIONS OF
 CHAPTER 471 SHALL BE SEALED, SIGNED AND
 DATED BY THE PROFESSIONAL ENGINEER IN
 RESPONSIBLE CHARGE. FAC 61G15-23.002(2)
  
 ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME, ADDRESS AND LICENSE NUMBER ON EACH
 SHEET. IF PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS, ENGIN-
 EERS, ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME AND LICENSE NUMBER, AS WELL
 AS, THE NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. A TITLE BLOCK
 WILL SATISFY THIS REQUIREMENT. FAC
 61G15-23.002(2)
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status N Date 2004-10-13 Cont ID  
Sent By rmcdouga Date 2004-10-13 Time 16:03 Rev Time 0.00
Received By rmcdouga Date 2004-10-13 Time 16:03 Sent To  
Notes
2004-10-13 00:00:00MASTER-ZONING REVIEW NOT REQUIRED.