| Plan Review Stops For Permit 04010007 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2005-02-02 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2005-02-02 |
Time |
07:44 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2005-02-02 |
Time |
07:43 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2005-01-31 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2005-01-31 |
Time |
16:34 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2005-01-31 |
Time |
16:04 |
Sent To |
|
|
| Notes |
| 2005-01-31 00:00:00 | DENIED | | | | | | 1) THE TRUSS DRAWINGS THAT WERE | | | SUBMITTED ARE FOR THE "B" ELEVATION AND | | | THIS IS THE "A" ELEVATION. | | | | | | 2) FBC 18O4.1.3 REQUIRES TO BOTTOM OF | | | FOOTERS TO BR A MINIMUM OF 12" BELOW | | | GRADE. CORRECT SHEET A16. | | | | | | 3) THE SOFFIT NOTE ON A20 CALLS FOR | | | STUCCO OVER 5/8" PLYWOOD. THIS IS THE | | | NOTE FOR THE FRAME WALLS. PLYWOOD IS NOT | | | INSTALLED BEHIND THE LATH ON THE | | | SOFFITS. | | | | | | 4) THE PRODUCT APPROVAL FOR THE SINGLE | | | HUNG WINDOWS IS MISSING THE INSTALLATION | | | DRAWINGS FOR CONCRETE OR MASONRY | | | OPENINGS. | | | | | | 5) THE PRODUCT APPROVALS FOR THE FIXED | | | GLASS WINDOWS ARE NOT CORRECT. THE | | | DRAWING NUMBERS ON PAGE ONE AND PAGE TWO | | | DO NOT MATCH AND THE WINDOWS ARE NOT | | | CURVED AT THE TOP. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2004-12-13 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2004-12-13 |
Time |
15:45 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2004-12-13 |
Time |
15:45 |
Sent To |
|
|
| Notes |
| 2004-12-13 00:00:00 | DENIED | | | | | | 1) THE ENERGY CALCULATIONS LIST THE | | | CEILING INSULATION AS R-19 AND THE PLANS | | | SPECIFY R-30. THE ENERGY CALCS. LIST | | | EXTERIOR WOOD FRAME WALLS WITH R-11 | | | INSULATION AND THE PLANS SPECIFY 2X6 | | | WALL WITH R-19. PLEASE CORRECT. | | | | | | 2) FAC 61G15-23.002 REQUIRES THE | | | ORIGINAL WET SIGNATURE OF THE TRUSS | | | ENGINEER TO BE ON THE TRUSS LAYOUT PLANS | | | AND DRAWINGS. | | | | | | 3) THE CEMENTITIOUS FINISH ON THE SOFFIT | | | IS REQUIRED TO BE 5/8" THICK PER FBC | | | 25O4.2.1 AND ASTM C 926. | | | | | | 4) SUBMIT PRODUCT APPROVALS AND SPECS. | | | FOR THE ONE HOUR FIRE RATED GLASS | | | BLOCK. | | | | | | 5) SUBMIT THE EVALUATION REPORT FOR THE | | | STRUCTURAL MULLIONS LISTING THE DESIGN | | | PRESSURES. | | | | | | 6) SUBMIT THE INSTALLATION DRAWINGS AND | | | DESIGN PRESSURES FOR THE SINGLE HUNG | | | WINDOWS. | | | | | | 7) SUBMIT THE PRODUCT APPROVALS FOR THE | | | FIXED GLASS WINDOWS. | | | | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2004-10-14 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2004-10-14 |
Time |
11:30 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2004-10-14 |
Time |
14:32 |
Sent To |
|
|
| Notes |
| 2004-10-14 00:00:00 | "MASTER" 6 UNIT/2 STORY | | | | | | DENIED | | | | | | 1)REDLINE CHANGES INITIALED AND DATED BY | | | THE DESIGNER OF RECORD ARE NOT ALLOWED | | | ON A "MASTER" PLAN. REVISE SHEET A-15 | | | WHICH HAS BEEN REDLINED BY D.O.R. | | | | | | 2) REVISE THE PLYWOOD SHEATHING NAILING | | | SCHEDULE ON S-4 TO CLARIFY THAT THE 8D | | | RING SHANK NAILS ARE REQUIRED FOR THE | | | ROOF SHEATHING IN ZONE 3 ONLY. | | | | | | 3) REVISE NOTE #7 ON S2 TO 8F8-1B, NOT | | | 8FB-1B. | | | | | | 4) REVISE THE NOTE FOR THE DOORS IN THE | | | GARAGE DEMISING WALLS TO SAY 3/4 HOUR | | | FIRE RATED DOORS, ON SHEETS A-1, A-3, | | | A-4 AND A7. | | | | | | 5) SPECIFY THE EMBED DEPTH OF THE 3/4" | | | DIA. ANCHOR BOLTS FOR THE STEEL COLUMN | | | BASES IN NOTE 6 ON S-1. | | | | | | 6) SECTION 8 ON S-6 IS INCORRECTLY | | | SPECIFIED ON SHEET S-3 FOR THE WALL | | | BETWEEN UNITS #3L AND 3R. THE TRUSSES | | | ARE PARALLEL TO THE WALL AT THIS | | | LOCATION. PLEASE CORRECT. | | | | | | 7) THE TRUSS LAYOUT AND DRAWINGS SHOW A | | | 2 MEMBER GRO3 ROOF TRUSS PARALLEL TO THE | | | THE WALL BETWEEN UNITS #3L AND 3R. THIS | | | TRUSS HAS A TOP CORD THAT IS FLAT. THIS | | | IS NOT INDICATED ON THE PLANS AND NO | | | CONNECTORS ARE SPECIFIED. SEE SECTION 1 | | | ON S-6. PLEASE REVIEW AND MAKE THE | | | NECESSARY CORRECTIONS. | | | | | | 8)REVISE THE UPLIFT VALUE OF THE SIMPSON | | | HETAL 20 CONNECTOR IN THE SCHEDULE ON | | | S-3 TO 1810#, WHICH IS THE VALUE IN THE | | | 2004 SIMPSON CATALOG TABLE ON PAGE 127, | | | WHICH INCLUDES THE LOAD DURATION | | | INCREASE ATTRIBUTED TO THE PROPETIES OF | | | WOOD BUT NOT THE STRESS INCREASE ON THE | | | STEEL CAPACITY, WHICH IS NOT ALLOWED BY | | | THE FLORIDA BUILDING CODE. SEE ATTACHED. | | | | | | 9) PLEASE GATHER ALL PRODUCT APPROVALS | | | FROM PREVIOUS SUBMITTALS AND COMBINE | | | WITH THE NEW SUBMITTALS TO MAKE 3 | | | COMPLETE SETS OF PLANS AND PRODUCT | | | APPROVALS. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CALL: | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2004-02-11 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2004-02-10 |
Time |
10:26 |
Rev Time |
3.75 |
| Received By |
jwitmer |
Date |
2004-02-10 |
Time |
10:26 |
Sent To |
PC |
|
| Notes |
| 2004-02-10 00:00:00 | | | | BUILDING PLAN REVIEW | | | PERMIT: 04010007 | | | ADD: 1100 N CONGRESS | | | CONT: WCI COMMUNITIES | | | CONTACT PERSON: DOUG BERK | | | TEL: (561)262-3684 | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | | | | ARCH: WCI ARCHITECTURE & LAND PLANNING | | | CONTACT: PETER SNYOYANNIS | | | (954) 575-4200 | | | | | | 1ST REVIEW | | | | | | THE COMMENTS FROM 0410005 (4) UNIT | | | BUILDING ARE APPLICIABLE ACCEPT FOR THE | | | FAIR HOUSING. | | | ADDITIONAL COMMENTS: | | | 1)FL BLD CODE 104.2.1.2 | | | ADDITIONAL INFORMATION REQUIRED, | | | DISCREPANCY IN UNIT# 2. A-1, A-18 DETAIL | | | #3 AND S-2, DEPENDING ON WHICH PAGE OR | | | SECTION, VIEWED.A RATED METAL STUD WALL | | | WITH BEAM ABOVE, NO INFO ON BEAM OR | | | S-1 INDICATING THE USE OF A WOOD POST? | | | 2101.3.2 MASONRY SHALL NOT BE SUPPORTED | | | BY WOOD GIRDERS OR OTHER FORMS OF WOOD. | | | | | | 2) S-3 TRUSS PLAN DOES NOT INDICATE THE | | | TRUSS OR GIRDER LOADS, VERTICAL, HORI- | | | ZONTAL AND GRAVITY LOADS TO BE RESISTED. | | | | | | 3) S-2 MASONARY WALLS ARE DESIGNATED AS | | | MW-1, S-4 MASONARY WALLS SCHEDULE IS | | | #5@48" O.C. NO INFO AS TO FILLED CELLS | | | AT WINDOWS, CORNERS ETC? | | | | | | 4) GARAGE BEAMS DO NOT GIVE IF LINTELS | | | ARE TO BE USED? WHAT THE ALLOWABLE SAFE | | | LOADS ARE? | | | | | | LOOK FOR COMMENTS BY THE OTHER PLAN | | | REVIEW DISCIPLINES THAT MAY BE WRITTEN | | | ON THE APPLICATION, PLANS, OR ATTACHED | | | SEPARATELY. WHEN RESUBMITTING PLANS | | | PLEASE CLEARLY INDICATE THE REVISION AND | | | REMOVE AND REPLACE ANY PAGES AS NECESS- | | | ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH | | | THE PLANS WHEN RESUBMITTING PLANS. A | | | TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW NUMBER, WITH A DESCRIPTION OF THE | | | REVISION MADE, IDENTIFYING THE SHEET OR | | | SPECIFICATION PAGE WHERE THE CHANGES CAN | | | BE FOUND, WILL HELP TO EXPEDITE YOUR | | | PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | JIM WITMER | | | BUILDING PLAN REVIEW | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2005-01-13 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-01-13 |
Time |
16:03 |
Rev Time |
0.33 |
| Received By |
dpalmer |
Date |
2005-01-13 |
Time |
16:00 |
Sent To |
|
|
| Notes |
| 2005-01-13 00:00:00 | RE-STAMPED E-2 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2004-10-08 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-10-08 |
Time |
16:43 |
Rev Time |
1.00 |
| Received By |
dpalmer |
Date |
2004-10-08 |
Time |
16:43 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2004-01-12 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-01-12 |
Time |
15:00 |
Rev Time |
1.00 |
| Received By |
dpalmer |
Date |
2004-01-12 |
Time |
15:00 |
Sent To |
|
|
| Notes |
| 2004-01-12 00:00:00 | *********** UNSAT ****************** | | | | | | 1)NOTE: PLANS REFERENCE 1999 NEC. | | | WE ARE UNDER THE 2002 NEC | | | 7/1/2003 | | | | | | 2)NOTE: PLEASE NOTE, ALL PLANS DRAWN | | | BY AN ARCHITECT/ENGINEER CONTAIN- | | | -ING A TITLE BLOCK: MUST BE SIGNED, | | | DATED AND SEALD BY THAT ARCH/ENG. | | | PER FS 481.221 471.025 | | | FAC 61G15-23.002, 61G1-16.004 | | | | | | 3)NOTE: PLEASE PROVIDE ALL LICENSE #`'S | | | ON TITLE BLOCK(S) AS REQ'D UNDER FAC | | | 61G15-23.002 / FS 471.023 | | | | | | 4) NOTE: PLEASE LIST ALL THE REQ'D | | | DEDICATED BATH(S) CIRCUIT(S) ON PANEL | | | SCHEDULE. PER 210.52D, 210.11C3 | | | | | | 5))NOTE: PLEASE SEE MISSING REQ'D EGRESS | | | LIGHTING AND/OR CLARIFY EGRESS LIGHTING | | | PER 210.70 AND LS-101 5-8 | | | | | | 6) NOTE: PLEASE SHOW GROUNDING ELETRODE | | | SYSTEM PER 250.50. FOOTER STEEL/COLD | | | WATER/ ETC. SIZE ALL PER 250.66 | | | | | | 7)) NOTE: PLEASE SEE MISSING RECEPTS FOR | | | FRONT AND/OR REAR OF DWELLING. | | | 210.52EREAR | | | | | | 8)NOTE: PLEASE SEE RISER DIAGRAM, SHOWS | | | EMT AS BEING DIRECT BURIAL FOR FEEDERS. | | | PLEASE SEE THIS IS NOT PERMITTED UNDER | | | LOCAL AMENDMENTS 348-5. | | | ALSO SEE 358 NEC | | | | | | PLEASE SEE COMMENTS FROM OTHER REVIEWERS | | | AS THEY MAY AFFECT ELECTRICAL PLANS. | | | PLEASE ALSO NOTE: INFORMATION REQ'D ON | | | TITLE BLOCKS FOR ARCHS/ENGS ARE REQ'D | | | OF ALL TRADES AND ALL SHEETS, WEATHER | | | OR NOT COMMENT IS MADE BY OTHER REVIEW- | | | -ERS. | | | | | | 9)NOTE: PLEASE LIST/SHOW ALL HEIGHTS | | | UNDER FHAR CFR 100.205. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
P |
Date |
2004-01-09 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2004-01-09 |
Time |
10:01 |
Rev Time |
1.00 |
| Received By |
mamini |
Date |
2004-01-09 |
Time |
10:01 |
Sent To |
|
|
| Notes |
| 2004-01-09 00:00:00 | PASSED: | | | 1. SEE PERMIT # 03101412 FOR UNDERGROUND | | | UTILITIES AND SITE WORK (PLAN REVIEW). | | | IF ANY QUESTION PLEASE CONTACT 805-6723 | | | MOHAMMAD R. AMINI |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2004-11-05 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-10-27 |
Time |
12:10 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-10-27 |
Time |
12:10 |
Sent To |
|
|
| Notes |
| 2004-11-02 00:00:00 | PASSED PER MIKE CARSILLO |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2004-01-08 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2004-01-08 |
Time |
17:50 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2004-01-08 |
Time |
17:50 |
Sent To |
|
|
| Notes |
| 2004-01-08 00:00:00 | 1) WET FIRE HYDRANTS ARE REQUIRED PRIOR | | | TO, DURING AND AFTER CONSTRUCTION. | | | | | | 2) BUILDING ADDRESSES ARE REQUIRED. | | | COULD NOT LOCATE THEM ON ELEVATION | | | DRAWINGS. | | | | | | 3) ENTRY DOORS SHOULD BE AT LEAST | | | 20 MINUTE FIRE RATED. | | | | | | 4) PLEASE VERIFY IF ONE HOUR TENANT | | | DEMISING WALLS WILL BE ACCEPTED BY | | | THE CONSTRUCTION SERVICES DEPARTMENT. | | | ONE HOUR WALLS ARE ALLOWED IN APARTMENTS | | | BUT TOWNHOMES USUALLY REQUIRE TWO | | | HOUR DEMISING WALLS. ARE THESE UNITS | | | RENTALS OR ARE THEY GOING TO BE SOLD | | | AND BE FEE SIMPLE. PLEASE ADVISE. | | | | | | 5) ANY AND ALL THREE STORY BUILDINGS | | | IN THE DEVOLPMENT WILL REQUIRE FIRE | | | SPRINKLER PROTECTION. | | | | | | 6) IF SECURITY GATES ARE PROVIDED, | | | TWENTY FEET IN CLEAR WIDTH WILL BE | | | REQUIRED FOR FIRE RESCUE ACCESS. A | | | KNOX-BOX KEY SWITCH WILL BE REQUIRED. | | | | | | 7) COULD NOT LOCATE FIRE EXTINGUISHERS. | | | PLEASE ADVISE LOCATIONS. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2005-01-11 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2005-01-11 |
Time |
12:50 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2005-01-11 |
Time |
12:49 |
Sent To |
|
|
| Notes |
| 2005-01-11 00:00:00 | TO "COMM BD#37/RESUB. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2004-11-15 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-11-15 |
Time |
10:27 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-11-15 |
Time |
10:27 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2004-11-02 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-11-02 |
Time |
12:05 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-11-02 |
Time |
12:05 |
Sent To |
M |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2004-10-07 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-10-07 |
Time |
16:19 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-10-07 |
Time |
16:19 |
Sent To |
|
|
| Notes |
| 2004-10-07 00:00:00 | TO COMM BD#43 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2004-01-02 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-01-02 |
Time |
13:12 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-01-02 |
Time |
13:12 |
Sent To |
|
|
| Notes |
| 2004-01-02 00:00:00 | TO COMM BD#33 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2005-01-20 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2005-01-20 |
Time |
15:46 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2005-01-20 |
Time |
15:46 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2004-11-04 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2004-11-04 |
Time |
10:17 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2004-11-04 |
Time |
10:16 |
Sent To |
|
|
| Notes |
| 2004-11-04 00:00:00 | PLAN CHECK ONLY |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2004-01-22 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2004-01-22 |
Time |
06:41 |
Rev Time |
1.50 |
| Received By |
pkrauss |
Date |
2004-01-22 |
Time |
06:41 |
Sent To |
|
|
| Notes |
| 2004-01-22 00:00:00 | DENIED: | | | 1.PLANS ARE NOT SIGNED SEALED AND | | | DATED BY THE ENGINEER AS REQUIRED BY FS | | | 471.025 & THE FAC 61G15-23.002. | | | | | | 2.PLAN SHEET A-17 & DETAIL 2 ON PLAN | | | SHEET A-21 INDICATE A 1 HOUR FIRE RATED | | | FLOOR/CEILING ASSEMBLY.UNITS 2R, 3R, | | | 3L, 2L GRILLES TERMINATING AT THE | | | CEILING SHALL HAVE PROTECTION. | | | DUCTWORK PENTRATING RATED ASSEMBLY TO | | | THE SECOND FLOOR SHALL BE PROTECTED BY | | | MEANS OF A FIRE DAMPER OR "RATED SHAFT" | | | ASSEMBLY.PLEASE REIVSE PLANS TO | | | INCLUDE DETAILS FOR THESE TYPE OF | | | PENTRATIONS. | | | | | | 3.PLEASE PROVIDE OUTSIDE AIR | | | CALCULATIONS PER 2001 FBC(M) 403.3. | | | | | | 4.INDICATE OUTSIDE AIR INTAKE, DUCT | | | SIZE, MATERIAL AND LAYOUT. | | | | | | 5.RETURN AIR JUMPER ARE NOT SIZED | | | PROPERLY.MASTER BEDROOMS ARE TO | | | INCLUDE ALL SUPPLY AIR TO THE MASTER | | | SUITE (CLOSETS, BATHROOM, ETC).PLEASE | | | SEE THE ATTACHED SCHEDULE FOR PROPER | | | SIZING OF RETURN AIR. | | | | | | 6.ENERGY AND MANUAL J CALCULATIONS | | | REQUIRED FOR APPROVAL PER 2001 FBC | | | CHAPTER 13. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2004-12-13 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2004-12-13 |
Time |
08:03 |
Rev Time |
0.60 |
| Received By |
kstevens |
Date |
2004-12-11 |
Time |
18:03 |
Sent To |
B1 |
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2004-10-15 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2004-10-15 |
Time |
21:10 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2004-10-15 |
Time |
21:10 |
Sent To |
|
|
| Notes |
| 2004-10-15 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | 1) SHT P-3 SANITARY RISER DIAGRAM DOES | | | NOT MEET CODE REQUIREMENTS. - ALSO SEE | | | SHT P-1 FLOOR PLAN, (B UNIT LEFT)AND | | | SHT P-2 FLOOR PLAN, (A UNIT LEFT) SANT. | | | LAYOUT. | | | A) WATER CLOSET IS NOT VENTED PER SECT- | | | ION 908.3 (B UNIT) | | | B) TWO SANITARY LINES ARE SHOWN FOR THE | | | LAVS. (A UNIT) | | | 2) SHTS P-2, & P-3 REQUIRE A CERTIFICATE | | | OF AUTHORIZATION AS "ENGINEERS" IMPLIES | | | A PARTNERSHIP. FS 481.219 & FAC 61G1-16. | | | 003. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2004-01-22 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2004-01-22 |
Time |
12:02 |
Rev Time |
1.00 |
| Received By |
kstevens |
Date |
2004-01-22 |
Time |
11:53 |
Sent To |
|
|
| Notes |
| 2004-01-22 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | FLORIDA ADMIN. CODE | | | FLORIDA STATUTES | | | | | | 1) A SANITARY AND A WATER RISER DIAGRAM | | | ARE REQUIRED PER SECTION 104.3.1.1 | | | 2)PROFESSIONAL ENGINEER SHALL SIGN HIS | | | NAME AND AFFIX HIS SEAL TO ALL PLANS, | | | SPECIFICATIONS, REPORTS AND FINAL BID | | | DOCUMENTS PROVIDED TO THE OWNER OR THE | | | OWNER'S REPRESENTATIVE, OR OTHER DOCU- | | | MENTS PREPARED OR ISSUED BY SAID REGIS- | | | TRANT AND BEING FILED FOR PUBLIC RECORD. | | | THE DATE THAT THE SIGNATURE AND SEAL IS | | | AFFIXED AS PROVIDED HEREIN SHALL BE EN- | | | TERED ON SAID PLANS, SPECIFICATIONS, RE- | | | PORTS, OR OTHER DOCUMENTS IMMEDIATELY | | | UNDER THE SIGNATURE OF THE PROFESSIONAL | | | ENGINEER, FAC 61G15-23.002(1) | | | | | | EACH SHEET OF PLANS AND PRINTS WHICH | | | MUST BE SEALED UNDER THE PROVISIONS OF | | | CHAPTER 471 SHALL BE SEALED, SIGNED AND | | | DATED BY THE PROFESSIONAL ENGINEER IN | | | RESPONSIBLE CHARGE. FAC 61G15-23.002(2) | | | | | | ENGINEERS SHALL LEGIBLY INDICATE THEIR | | | NAME, ADDRESS AND LICENSE NUMBER ON EACH | | | SHEET. IF PRACTICING THROUGH A DULY | | | AUTHORIZED ENGINEERING BUSINESS, ENGIN- | | | EERS, ENGINEERS SHALL LEGIBLY INDICATE | | | THEIR NAME AND LICENSE NUMBER, AS WELL | | | AS, THE NAME, ADDRESS AND CERTIFICATE OF | | | AUTHORIZATION NUMBER OF THE ENGINEERING | | | BUSINESS ON EACH SHEET. A TITLE BLOCK | | | WILL SATISFY THIS REQUIREMENT. FAC | | | 61G15-23.002(2) | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
2004-10-13 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2004-10-13 |
Time |
16:03 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2004-10-13 |
Time |
16:03 |
Sent To |
|
|
| Notes |
| 2004-10-13 00:00:00 | MASTER-ZONING REVIEW NOT REQUIRED. |
|
|