Plan Review Details - Permit 04010006
Plan Review Stops For Permit 04010006
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2005-04-08 Cont ID  
Sent By rmcdouga Date 2005-04-08 Time 10:59 Rev Time 0.00
Received By rmcdouga Date 2005-04-08 Time 10:59 Sent To  
Notes
2005-04-08 00:00:00REVISED PAGES A6-A9 ARE OK.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-03-21 Cont ID  
Sent By rmcdouga Date 2005-03-21 Time 16:02 Rev Time 0.00
Received By rmcdouga Date 2005-03-21 Time 16:02 Sent To  
Notes
2005-03-21 00:00:00OWENS CORNING SHINGLES APPROVED FOR USE
 ABOVE 33 FEET BY NEIL MELICK, B.O.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-03-15 Cont ID  
Sent By rmcdouga Date 2005-03-15 Time 11:50 Rev Time 0.00
Received By rmcdouga Date 2005-03-15 Time 07:10 Sent To  
Notes
2005-03-21 00:00:00CONTRACTOR TO BRING IN NEW ENERGY CALCS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-02-11 Cont ID  
Sent By jwitmer Date 2004-02-11 Time 12:42 Rev Time 0.00
Received By mamini Date 2005-01-28 Time 13:34 Sent To  
Notes
2004-02-11 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04010006 (8 UNIT)
 ADD: 1100 N CONGRESS
 CONT: WCI N CONGRESS
 CONTACT PERSON: DOUG BERK
 TEL: (561)262-3684
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 ARCH: WCI ARCHITECTURE & LAND PLANNING
 CONTACT: PETER SYNOYANNIS
 (954) 575-4200
  
 1ST REVIEW
 ACTION: DENIED
  
 THE COMMENTS FROM 04010005 (4) UNIT
 BUILDING ARE APPLICIABLE ACCEPT FOR THE
 FAIR HOUSING.
  
 1)903.8.2 FLOR ST STATUTE 553.895(2)
 ALL RESIDENTIAL BUILD. 3 OR MORE STORIES
 TALL WHETHER DESIGNATED AS TOWNHOUSE,
 CONDOMINIUMS, "APARTMENT HOUSES,
 TENEMENTS, GARDEN APARTMENTS OR BY ANY
 OTHER NAME SHALL BE SUPPLIED BY FIRE
 SPRINKLERS MEETING NFPA 101.
 PROVIDE 3 COPIES OF FIRE SPRINKLER
 PLANS TO BE INCLUDED WITH THE BUILDING
 PLANS.
  
 2) PROVIDE THE MEAN ROOF HEIGHT OF THE
 BUILDING FROM "GRADE" TO INCLUDE 1/2 THE
 HEIGHT OF THE TRUSSES OFF OF THE HEIGH-
 EST BEAM. APPROX- 38'-4 1/2".
  
 3) SHEET S-4 TRUSS PLAN DOES NOT INDI-
 CATE THE TRUSS OR GIRDER LOADS, VERTICAL
 HORIZONTAL AND GRAVITY LOADS TO BE
 RESISTED. THE TRUSS ANCHOR LEGOND
 "E-H" DOES NOT GIVE ANY VALUE FOR THE
 FASTENER!!!!!!!!!!!!!!!!!!!!!!!!!!!!
  
 4) SHEET S-3 INDICATES PRECAST LINTELS
 ARETO BE USED, PROVIDE LINTEL SCHEDULE
 AND ALLOWABLE LOADS VS SPANS.
  
 5) SHEET S-5 WALL AND ROOF PRESSURE
 ZONES INDICATE LOW PRESSURES! SINCE THE
 MEAN ROOF HEIGHT IS > 35' A HEIGHT
 ADJUSTMENT FACTOR IS REQUIRED OF 1.09
 SEE TABLE 1606.2D.
  
 6) SHEET S-5 ROOF NAILING SCHEDULE
 ZONE# 3 NAILS ARE TO BE "RING SHANK".
 WEST PALM BEACH AMENDMENT TABLE 2306.1.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-02-09 Cont ID  
Sent By dpalmer Date 2005-02-09 Time 19:30 Rev Time 0.30
Received By dpalmer Date 2005-02-09 Time 19:30 Sent To  
Notes
2005-02-09 00:00:00ELEC OK, STAMPED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-01-12 Cont ID  
Sent By dpalmer Date 2004-01-12 Time 14:07 Rev Time 1.00
Received By dpalmer Date 2004-01-12 Time 14:07 Sent To  
Notes
2004-01-12 00:00:00************* UNSAT *****************
  
 1)NOTE: PLANS REFERENCE THE 1999 NEC,
 PLEASE SEE THAT WE ARE UNDER THE 2002
 NEC.
  
 2)NOTE: PLEASE NOTE, ALL PLANS DRAWN
 BY AN ARCHITECT/ENGINEER CONTAIN-
 -ING A TITLE BLOCK: MUST BE SIGNED,
 DATED AND SEALD BY THAT ARCH/ENG.
 PER FS 481.221 471.025
 FAC 61G15-23.002, 61G1-16.004
  
 3 )NOTE: PLEASE SEE MISSING REQ'D EGRESS
 LIGHTING AND/OR CLARIFY EGRESS LIGHTING
 PER 210.70 AND LS-101 5-8
  
 4) NOTE: PLEASE LIST ALL THE REQ'D
 DEDICATED BATH(S) CIRCUIT(S) ON PANEL
 SCHEDULE. PER 210.52D, 210.11C3
  
 5) NOTE: PLEASE SHOW GROUNDING ELETRODE
 SYSTEM PER 250.50. FOOTER STEEL/COLD
 WATER/ ETC. SIZE ALL PER 250.66
  
 6)NOTE: PLEASE INCLUDE ALL LICENSE #'S
 AS REQ'D UNDER FAC 61G15-23.002/FS 471
 PLEASE ALSO SEE FS 471.023
  
 7)NOTE: PLEASE SEE RISER, SHOWS EMT
 BEING INSTALLED FOR DIRECT BURIAL.
 PLEASE SEE THAT THIS IS NOT PERMITTED.
 SEE 348-5 LOCAL AMENDMENTS.
 PLEASE ALSO SEE NEC 358
  
 8)NOTE: PLEASE SEE FHAR CFR 100.205
 FOR ALL HEIGHT REQ'MENTS. PLEASE SHOW
 ON PLANS.
  
 9)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
 SHOWN FOR UNIT MAINS, BUT NOT FOR 1200A
 MAIN.
  
 10) NOTE: PLEASE SEE MISSING RECEPTS FOR
 FRONT AND/OR REAR OF DWELLING.
 210.52EREAR?
  
 11)NOTE:PLEASE SEE MISSING RECEPT REQ'D
 FOR A/C EQUIPMENT. 210.63
  
 PLEASE SEE COMMENTS FROM OTHER REVIEWERS
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2005-01-28 Cont ID  
Sent By mamini Date 2005-01-28 Time 13:34 Rev Time 0.00
Received By mamini Date 2005-01-28 Time 13:34 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2004-01-08 Cont ID  
Sent By mamini Date 2004-01-08 Time 14:48 Rev Time 1.00
Received By mamini Date 2004-01-08 Time 14:48 Sent To  
Notes
2004-01-08 00:00:00PASSED:
 1. SEE PERMIT # 03101412 FOR UNDERGROUND
 UTILITIES AND SITE WORK (PALN REVIEW).
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-03-02 Cont ID  
Sent By nmccray Date 2005-03-02 Time 14:22 Rev Time 0.00
Received By nmccray Date 2005-03-02 Time 14:22 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-01-09 Cont ID  
Sent By mcarsill Date 2004-01-09 Time 13:06 Rev Time 0.00
Received By mcarsill Date 2004-01-09 Time 13:06 Sent To  
Notes
2004-01-09 00:00:001) NO FIRE SPRINKLER PLANS PROVIDED
 WITH DRAWINGS.
  
 2) BUILDING ADDRESSES REQUIRED.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-04-06 Cont ID  
Sent By adarroug Date 2005-04-06 Time 11:44 Rev Time 0.00
Received By adarroug Date 2005-04-06 Time 11:44 Sent To B
Notes
2005-04-06 00:00:00TO "RMCDOUGAL" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-01-28 Cont ID  
Sent By pkrauss Date 2005-02-01 Time 11:37 Rev Time 0.00
Received By mjacobs Date 2005-01-28 Time 10:55 Sent To  
Notes
2005-03-02 00:00:003/2/05 MOVED TO BD#54-ADARROUGH
2005-01-28 00:00:00TO "COMM BD#37/RESUB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-01-02 Cont ID  
Sent By mmclean Date 2004-02-13 Time 11:44 Rev Time 0.00
Received By csiegber Date 2004-01-02 Time 13:15 Sent To  
Notes
2004-01-02 00:00:00TO COMM BD#34

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2005-02-07 Cont ID  
Sent By pkrauss Date 2005-02-07 Time 06:52 Rev Time 0.40
Received By pkrauss Date 2005-02-07 Time 06:52 Sent To  
Notes
2005-02-07 00:00:00SUBMITTAL - ENERGY & MANUAL J
 CALCULATIONS ALONG WITH A SIGNED,SEALED
 LETTER FROM THE ENGINEER INDICATING THE
 O.A. DUCT WILL BE CONSTRUCTED OF METAL
 PER THE MECHANICAL CODE.
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2005-02-01 Cont ID  
Sent By pkrauss Date 2005-02-01 Time 07:16 Rev Time 1.00
Received By pkrauss Date 2005-02-01 Time 06:51 Sent To  
Notes
2005-02-01 00:00:00DENIED:
 COMMENTS FROM REVIEW DATED 3-25-04

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2004-03-25 Cont ID  
Sent By pkrauss Date 2004-03-25 Time 11:14 Rev Time 1.40
Received By pkrauss Date 2004-03-25 Time 11:14 Sent To  
Notes
2004-03-25 00:00:00DENIED:
 1.PLEASE NOTE, DETAIL OF UL DESIGN
 L528 IN THE UL DIRECTORY DOES NOT
 INDICATE ANY PENETRATIONS THROUGH THIS
 ASSEMBLY.PLEASE PROVIDE UL LISTING
 FOR THE PENETRATIONS THROUGH THE RATED
 ASSEMBLY.
  
 2.PLEASE CLARIFY RATING ON PLAN SHEET
 A-10 DETAIL #4, THE 1HR RATING IS AT THE
 PARTITION WALL TO THE UNDERSIDE OF THE
 CEILING CORRECT?IF THIS IS CORRECT,
 THE FIRE DAMPER INDICATED ON PLAN SHEET
 M-1 IS NOT REQUIRED BECAUSE THE WALL
 DOES NOT CONTINUE ABOVE THE CEILING.
  
 3.CLARIFY O.A. DUCT, IS APPEARS TO BE
 ABOVE THE CEILING AND DOES NOT PENETRATE
 THE BOTTOM MEMBRANE OF THE ASSEMBLY OR
 AT THE POINT OF ENTRY, FIRE DAMPER NOT
 REQUIRED.
  
 4.PLANS SHALL BE SIGNED BY THE
 ENGINEER NOT STAMPED WITH THEIR S
 SIGNATURE PER FS 471.025.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-01-22 Cont ID  
Sent By pkrauss Date 2004-01-22 Time 11:11 Rev Time 1.20
Received By pkrauss Date 2004-01-22 Time 11:11 Sent To  
Notes
2004-01-22 00:00:00DENIED:
 1.PLANS ARE NOT SIGNED, SEALED, AND
 DATED BY THE ENGINEER AS REQUIRED BY FS
 471.025 & THE FAC 61G15-23.002.
  
 2.PLAN SHEET A-9 & A-13.1 DETAIL 1 &
 2, INDICATE 1 HOUR FIRE RATED
 FLOOR/CEILING & CEILING/ROOF
 ASSEMBLIES.PENETRATIONS THROUGH RATED
 ASSEMBLIES SHALL COMPY WITH 2001 FBC(M)
 607.2.
  
 3.DUCTS PENETRATING MORE THAN ONE
 STORY SHALL BE PROTECTED BY A SHAFT
 ENCLOSURE PER 2001 FBC(M) 607.4.
 PLEASE PROVIDE DETAIL OF SHAFT
 ENCLOSURE.
  
 4.PLEASE INDICATE PROTECTION OF
 EXHAUST DUCT WORK PENETRATING 1 HOUR
 CEILING/ROOF ASSEMBLY. (PLAN SHEET M-2)
  
 5.PLAN SHEET RETURN AIR JUMPERS ARE
 NOT SIZED PROPERLY.PLEASE NOTE,
 MASTER BEDROOM IS TO INCLUDE ALL AIR TO
 THE MASTER SUITE PER 2001 FBC(M) 601.4
 EXCEPTION 1 AND 4 (SEE THE ATTACHED
 SCHEDULE FOR PROPER SIZING).
  
 6.PLEASE PROVIDE OUTSIDE AIR
 CALCULATIONS PER 2001 FBC(M) 403.3.
  
 7.INDICATE OUTSIDE AIR INTAKE, DUCT
 SIZE, MATERIAL, AND LAYOUT.
  
 8.ENERGY AND MANUAL J CALCULATIONS
 REQUIRED FOR APPROVAL PER 2001 FBC
 CHAPTER 13.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-03-03 Cont ID  
Sent By kstevens Date 2005-03-03 Time 06:56 Rev Time 0.50
Received By kstevens Date 2005-03-03 Time 06:56 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-01-22 Cont ID  
Sent By kstevens Date 2004-01-22 Time 13:46 Rev Time 1.00
Received By kstevens Date 2004-01-22 Time 13:46 Sent To  
Notes
2004-01-22 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FLORIDA ADMIN. CODE
 FLORIDA STATUTES
  
 1) A SANITARY AND A WATER RISER DIAGRAM
 ARE REQUIRED PER SECTION 104.2.1.
 2) PROFESSIONAL ENGINEER SHALL SIGN HIS
 NAME AND AFFIX HIS SEAL TO ALL PLANS,
 SPECIFICATIONS, REPORTS AND FINAL BID
 DOCUMENTS PROVIDED TO THE OWNER OR THE
 OWNER'S REPRESENTATIVE, OR OTHER DOCU-
 MENTS PREPARED OR ISSUED BY SAID REGIS-
 TRANT AND BEING FILED FOR PUBLIC RECORD.
 THE DATE THAT THE SIGNATURE AND SEAL IS
 AFFIXED AS PROVIDED HEREIN SHALL BE EN-
 TERED ON SAID PLANS, SPECIFICATIONS, RE-
 PORTS, OR OTHER DOCUMENTS IMMEDIATELY
 UNDER THE SIGNATURE OF THE PROFESSIONAL
 ENGINEER, FAC 61G15-23.002(1)
 ***
 EACH SHEET OF PLANS AND PRINTS WHICH
 MUST BE SEALED UNDER THE PROVISIONS OF
 CHAPTER 471 SHALL BE SEALED, SIGNED AND
 DATED BY THE PROFESSIONAL ENGINEER IN
 RESPONSIBLE CHARGE. FAC 61G15-23.002(2)
 ***
 ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME, ADDRESS AND LICENSE NUMBER ON EACH
 SHEET. IF PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS, ENGIN-
 EERS, ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME AND LICENSE NUMBER, AS WELL
 AS, THE NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. A TITLE BLOCK
 WILL SATISFY THIS REQUIREMENT. FAC
 61G15-23.002(2)
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 3 Status P Date 2005-04-07 Cont ID  
Sent By eschneid Date 2005-04-07 Time 09:55 Rev Time 0.00
Received By eschneid Date 2005-04-07 Time 09:54 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2005-02-14 Cont ID  
Sent By eschneid Date 2005-02-14 Time 14:36 Rev Time 0.20
Received By eschneid Date 2005-02-14 Time 14:24 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2003-12-12 Cont ID  
Sent By mmclean Date 2004-02-13 Time 11:44 Rev Time 0.00
Received By mmclean Date 2003-12-12 Time 11:43 Sent To I
Notes
2004-02-13 00:00:002ND REQUEST - PER ERIC SCHNEIDER SENIOR
 PLANNER 1- NO LANDSCAPE PLANS WERE
 INCLUDED, NEED TO PROVIDE ONE FOR PERMIT
 2 - SITE PLAN SHEET 1 OR 5 IS NOT THE
 ONE THE CITY COMMISSION APPROVED.NEED
 TO SUBMIT THE 9/26/03 REVISED ONE ITEMS
 AFFECTED ARE PARKING DATA IS MISSING.
 3 - ENTRY SIGN LOCATION SHOWN ON SHEETS
 1,3 & 5 DO NOT MEET SETBACKS. RESIDENTAL
 DEVELOPMENT ENTRY SIGNS ARE REQUIRED TO
 HAVE A 20' SETBACK FROM THE ROW.