Plan Review Details - Permit 03121694
Plan Review Stops For Permit 03121694
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-03-26 Cont ID  
Sent By rbrown Date 2004-03-26 Time 14:46 Rev Time 0.00
Received By rbrown Date 2004-03-26 Time 14:46 Sent To  
Notes
2004-03-26 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE BUILDING PLAN
 REVIEW OF 1/28/04:
  
 3) FBC* 104.2.4SITE SURVEY.CONTRARY
 TO THE COMMENT RESPONSE LETTER DATED
 FEBRUARY 18, 2004, THIS COMMENT HAS NOT
 BEEN ADDRESSED.NO SIGNED AND SEALED
 SURVEY WAS SUBMITTED.A SIGNED AND
 SEALED SURVEY DRAWING PREPARED BY A
 LICENSED SURVEYOR/MAPPER IS REQUIRED.
 (REF: 472.025(1) FL. STATUTES)
  
 4) MINOR SUBDIVISION.IT IS NOTED, FROM
 THE RESPONSE, THAT THE PLAT IS BEING
 RECORDED.A COPY OF THE RECORDED PLAT
 WILL BE REQUIRED FOR ADDRESSING PURPOSES
 NOTE THAT THIS IS NOT WITHIN THE REMIT
 OF THE PLANNING DEPARTMENT.
  
 11) FL. ADMIN CODE RULE 9B-72.PRODUCT
 APPROVAL.CONTRARY TO THE COMMENT
 RESPONSE LETTER DATED FEBRUARY 18, 2004,
 ALL OF THE DOOR AND WINDOW PRODUCTS DO
 NOT HAVE STATEWIDE PRODUCT APPROVAL AT
 THIS TIME.BEFORE A PERMIT IS ISSUED
 THE SPECIFIED PRODUCTS MUST HAVE
 STATEWIDE, LOCAL OR SITE-SPECIFIC
 PRODUCT APPROVAL.NO PRODUCT APPROVAL
 DOCUMENTATION HAS BEEN SUBMITTED FOR THE
 ROOF TILES.NONE OF THE ARCH ALUMINUM
 OR REPUBLIC BUILDERS PRODUCTS COMPONENTS
 CURRENTLY HAVE STATEWIDE PRODUCT
 APPROVAL.TO EXPEDITE THE REVIEW, THE
 STATEWIDE PRODUCT APPROVAL COVER SHEET
 HAS BEEN PRINTED AND ATTACHED TO THE
 KAWNEER STOREFRONT NOTICE OF ACCEPTANCE.
 FOR PRODUCTS WHICH DO NOT HAVE STATEWIDE
 PRODUCT APPROVAL, LOCAL PRODUCT APPROVAL
 CAN BE ACHIEVED IF THERE IS A QUALITY
 ASSURANCE PROGRAM IN PLACE WITH A STATE
 APPROVED QUALITY ASSURANCE ENTITY.IF
 NEITHER IS APPLICABLE, THEN SITE
 SPECIFIC APPROVAL IS REQUIRED.LOCAL
 PRODUCT APPROVAL WILL ALLOW A PRODUCT TO
 BE USED, IN ACCORDANCE WITH THE TEST
 CRITERIA, THROUGHT THE JURISDICTION OF
 WEST PALM BEACH.SITE SPECIFIC PRODUCT
 APPROVAL WILL ALLOW A PRODUCT TO BE
 USED ONLY ON THE PROJECT FOR WHICH THAT
 SITE SPECIFIC APPROVAL IS GRANTED.
 LOCAL AND SITE SPECIFIC PRODUCT APPROVAL
 APPLICATION FORMS ARE AVAILABLE FROM
 THIS OFFICE.APPROVED QUALITY ASSURANCE
 ENTITIES ARE LISTED ON THE DCA WEBSITE:
 WWW.FLORIDABUILDING.ORG/COMMON/C_ORG_
 REGI_SRCH.ASP
  
 13) FBC 607 AND 608SHEET A00.0 STATES
 THAT THE CONSTRUCTION IS TYPE V
 UNPROTECTED WITH AN ALLOWABLE AREA OF
 14000 S.F.THE ELEVATIONS AND SECTIONS
 HAVE BEEN REVISED TO SHOW CONSTRUCTION
 WHICH WOULD BE CLASSIFIED AS TYPE VI
 UNPROTECTED.AMEND SHEET A00.O TO
 REFLECT THIS AND SHOW AN ALLOWABLE AREA
 OF 9000 S.F.
  
 14) TO EXPEDITE REVIEW OF A RESUBMITTAL
 WHICH REQUIRES NEW PLANS IN ORDER TO
 ADDRESS THE ABOVE COMMENTS, THE OLD
 SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHOULD BE STAPLED/CLIPPED TO THE
 REMAINING OLD SHEETS FOR COMPARISON OF
 REVISIONS WHEN REVIEWING THE RESUBMITTED
 PLANS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-01-28 Cont ID  
Sent By rbrown Date 2004-01-28 Time 18:22 Rev Time 0.00
Received By rbrown Date 2004-01-22 Time 15:25 Sent To  
Notes
2004-01-22 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) WORKING DRAWING REVIEW ONLY.NO
 PERMIT CAN BE ISSUED UNTIL THE PERMIT
 APPLICATION AND FEES ARE SUBMITTED.
  
 2) 61G1-16.004FL. ADMIN. CODE.PLANS
 PREPARED BY A REGISTERED ARCHITECT SHALL
 INCLUDE A TITLE BLOCK WHICH MUST STATE
 THE FIRM'S LICENSE NUMBER, THE PRINTED
 LICENSE NUMBER OF THE ARCHITECT AND
 INCLUDE THE SIGNATURE OF THE ARCHITECT
 SEALING THE PLANS.IT IS NOTED THAT
 THE PLANS/SEALS HAVE BEEN INITIALED BUT
 THEY MUST INCLUDE THE FULL SIGNATURE AS
 ON FILE WITH THE BOARD OF ARCHITECTURE
 AND INTERIOR DESIGN.
  
 3) FBC* 104.2.4SITE SURVEY.A SIGNED
 AND SEALED SURVEY DRAWING PREPARED BY A
 LICENSED SURVEYOR/MAPPER IS REQUIRED.
 (REF: 472.025(1) FL. STATUTES)
 THE SUBMITTED 'DESCRIPTION SKETCH' BY
 WALLACE SURVEYING CORP STATES "THIS IS
 NOT A SURVEY!".SEE ALSO COMMENT (4)
 BELOW.
  
 4) MINOR SUBDIVISION PLAT. FROM SHEET C2
 IT APPEARS THAT THE PROPOSAL INVOLVES
 SUBDIVISION OF PARCEL
 74-43-43-17-25-003-0020 INTO FOUR
 SEPARATE PARCELS AND A PRIVATE STREET.
 SUBMIT A RECORDED MINOR SUBDIVISION PLAT
 (TO BE RECORDED AT THE COUTY COURTHOUSE)
 PREPARED BY A PROFESSIONAL SURVEYOR AND
 MAPPER AND APPROVED BY THE CITY OF WEST
 PALM BEACH PLANNING DIRECTOR, IN ACCORD.
 WITH THE PROVISIONS OF ARTICLE XI,
 SECTIONS 33-130 THROUGH 33-133 OF THE
 OFFICIAL ZONING CODE OF THE CITY OF WEST
 PALM BEACH, FLORIDA.
  
 5) FBC 13-103.1.2BEFORE A BUILDING
 PERMIT CAN BE ISSUED, SHEET 2 OF THE
 ENERGY CODE COMPLIANCE FORMS SHALL BE
 SIGNED BY THE BUILDING OWNER, THE
 OWNER'S ARCHITECT OR OTHER AUTHORIZED
 AGENT LEGALLY DESIGNATED BY THE OWNER.
  
 6) FBC 1606.2.2SHEET S5.1, WALL
 COMPONENT AND CLADDING WIND LOADS.THE
 27.4PSF NEGATIVE PRESSURE STATED FOR
 ZONE 4 LOCATIONS HAVING A TRIBUTARY AREA
 OF 50 SQFT IS TOO LOW.AMEND THE TABLE.
  
 7) FBC* TABLE 2306.1SHEET S2.1, ROOF
 FRAMING NOTE 5.THE PLAN SPECIFIES 10D
 NAILS AT 8" O.C. INTERMEDIATE.THIS IS
 NOT EQUIVALENT TO THE REQUIRED 8D NAILS
 AT 6" O.C. INTERMEDIATE. AMEND THE NOTE.
  
 8) FBC 1606.1.3SHEET S2.1, SIMPSON H10
 TRUSS ANCHORS.THE PLAN SHALL BE
 AMENDED TO STATE THE TYPE AND NUMBER OF
 FASTENERS TO BE USED AT THE TRUSS AND
 THE TOP PLATE.
  
 9) FBC 1606.1.3SHEET S2.1, SIMPSON
 MSTC28 STRAP TIES.THE SIMPSON CATALOG
 GIVES LOAD CAPACITIES FOR THE MSTC28
 WHEN USED WITH 36-16D SINKER NAILS.THE
 PLAN STATES "(10) NO. 12-14 SCREWS".
 AMEND THE PLAN TO SHOW A TIE/FASTENER
 COMBINATION THAT CAN BE JUSTIFIED FOR
 THE UPLIFTS.
  
 10) FBC 1606.1.3SHEET S2.1, SIMPSON
 MSTC52 STRAP TIES.THE SIMPSON CATALOG
 GIVES LOAD CAPACITIES FOR THE MSTC52
 WHEN USED WITH 62-16D SINKER NAILS.THE
 GIRDER TRUSS HURRICANE TIE FASTENERS
 SPECIFIED AT R-1, R-2, R-3 AND R-4 DO
 CORRELATE WITH THE CATALOGUE.AMEND THE
 PLAN TO SHOW A TIE/FASTENER COMBINATION
 THAT CAN BE JUSTIFIED FOR THE UPLIFTS.
  
 11) FL. ADMIN CODE RULE 9B-72.
 A SEARCH AT THE DEPT OF COMMUNITY
 AFFAIRS PRODUCT APPROVAL WEBSITE
 WWW.FLORIDABUILDING.ORG/PR/PR_SRCH.ASP
 SHOWS NO MATCHING STATEWIDE PRODUCT
 APPROVAL FOR ANY OF THE SUBMITTED ARCH
 ALUMINUM & GLASS CO. OR REPUBLIC
 BUILDERS PRODUCT MIAMI-DADE PRODUCT
 APPROVAL NOTICES OF ACCEPTANCE.
 SPECIFY ALTERNATIVES THAT HAVE
 STATEWIDE OR LOCAL PRODUCT APPROVAL.
 NOTE: FL. ADMIN CODE RULE 9B-72 (IN
 EFFECT SINCE OCTOBER 1, 2003) REQUIRES
 THAT PRODUCTS HAVE STATEWIDE, LOCAL OR
 SITE-SPECIFIC PRODUCT APPROVAL.THE
 SUBMITTAL SHOULD INCLUDE THE STATEWIDE
 PRODUCT APPROVAL NUMBER (FL###),
 AVAILABLE FROM THE DEPT OF COMMUNITY
 AFFAIRS PRODUCT APPROVAL WEBSITE
 WWW.FLORIDABUILDING.ORG/PR/PR_SRCH.ASP
 OR SITE SPECIFIC PRODUCT APPROVAL FORMS
 (AVAILABLE FROM THIS OFFICE) COMPLETED
 BY THE PRODUCT MANUFACTURER.
  
 12) IF NEW PLAN SHEETS ARE REQUIRED, IN
 ORDER TO ADDRESS THE ABOVE COMMENTS, THE
 OLD SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHALL BE INCLUDED WITH THE
 RESUBMITTAL FOR COMPARISON OF REVISIONS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-03-08 Cont ID  
Sent By dpalmer Date 2004-03-08 Time 06:33 Rev Time 0.50
Received By dpalmer Date 2004-03-08 Time 06:14 Sent To  
Notes
2004-03-08 00:00:00*** REDLINED**
 NO EQUIPMENT GROUNDING CONDUCTOR FROM
 METER TO FIRST MEANS OF DISCONNECT.
 250.24.
 EG, IS ONLY INSTALLED AFTER THE FIRST
 MEANS OF DISC.
  
  
 ELECTRICAL PLANS STAMPED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-01-13 Cont ID  
Sent By dpalmer Date 2004-01-12 Time 16:42 Rev Time 2.00
Received By dpalmer Date 2004-01-12 Time 16:37 Sent To  
Notes
2004-01-12 00:00:00********** UNSAT *****************
  
 1)NOTE: PLANS/ CODES REFERENCED ON PLANS
 REFER TO THE 99 NEC. PLEASE SEE THAT WE
 ARE THE 2002 NEC. PLEASE ADJUST.
  
 2)NOTE; PLEASE SEE MULTIPLE PAGES FOR
 WIND LOADING OF POLES.
 ONE SHOWS 140 MPH (REQ'D) ANOTHER,120MPH
 PLEASE SEE 2001 FBC. WE ARE UNDER 140MPH
 PLEASE ALSO SEE NOTE MENTIONS, CONTRACT-
 -OR TO PROVIDE SPECIFIC SIGNED AND SEAL-
 -ED WIND LOAD CALCS/SPECS ETC AT LATER
 DATE. PLEASE SEE THAT THIS INFORMATION
 IS REQ'D AT THIS TIME AND SHOULD BE
 SUBMITTED WHEN SUBMITTING FOR PERMIT.
  
 2)NOTE: PLANS ARE ONLY IN FOR PLAN
 REVIEW AND NOT FOR PERMIT.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
 3)NOTE: PLEASE

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2004-01-06 Cont ID  
Sent By mamini Date 2004-01-06 Time 10:38 Rev Time 1.00
Received By mamini Date 2004-01-06 Time 10:38 Sent To  
Notes
2004-01-06 00:00:00PASSED WITH PROVISOS:
 1. PLEASE SUBMIT CIVIL PLANS TO THE
 PUBLIC UTILITIES AND ENGINEERING FOR THE
 THEIR REVIEW AND APPROVAL.CIVIL PLANS
 MUST BE APPROVED AND STAMPED BY THE
 PUBLIC UTILITIES AND ENGINEERING PRIOR
 TO SUBMITTING TO THE CONSTRUCTION
 SERVICES FOR ACTUAL PERMITTING,659-8040
 MANNY GONZALEZ.
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-02-27 Cont ID  
Sent By mcarsill Date 2004-02-27 Time 14:30 Rev Time 0.00
Received By mcarsill Date 2004-02-27 Time 14:29 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-01-02 Cont ID  
Sent By mcarsill Date 2004-01-02 Time 14:51 Rev Time 0.00
Received By mcarsill Date 2004-01-02 Time 14:51 Sent To  
Notes
2004-01-02 00:00:001) SITE PLAN DOES NOT GIVE VICINITY
 OR STREET NAME LOCATIONS.
  
 2) SITE PLAN DOES NOT DISPLAY FIRE
 HYDRANT LOCATIONS.
  
 3) PLEASE EXPLAIN WHAT EFFECT THE SQUARE
 COLUMN WILL HAVE ON EXITING FROM
 VESTIBULE 100.
  
 4) THE PROPOSED LOCATION MAY BE LOCATED
 IN THE CITY FIRE LIMITS, CERTAIN
 RESTRICTIONS MAY APPLY. PLEASE SEE
 APPENDIX F, LOCAL AMENDMENTS TO THE
 FLORIDA BUILDING CODE.
  
 5) BUILDING ADDRESS NOT SHOWN ON
 ELEVATION DRAWINGS. A MINIMUM OF 6"
 HIGH NUMBERS ARE REQUIRED.
  
 6) HANDRAILS REQUIRED ON BOTH SIDES
 OF SERVICE STAIR.
  
 7) ELECTRICAL ROOM SHALL BE ONE HOUR
 FIRE RATED WITH 45 MINUTE OPENING
 PROTECTED IF THE BUILDING IS NOT FIRE
 SPRINKLER PROTECTED.
  
 8) TITLE PAGE MAKES REFERENCE TO
 BASEMENT. PLEASE ADVISE.
  
 9) WET FIRE HYDRANTS ARE REQUIRED PRIOR
 TO, DURING AND AFTER CONSTRUCTION.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-02-25 Cont ID  
Sent By mmclean Date 2004-02-27 Time 16:18 Rev Time 0.00
Received By csiegber Date 2004-02-25 Time 13:31 Sent To  
Notes
2004-02-25 00:00:00TO COMM BD#11

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-12-31 Cont ID  
Sent By mmclean Date 2004-01-15 Time 09:26 Rev Time 0.00
Received By csiegber Date 2003-12-31 Time 14:44 Sent To  
Notes
2003-12-31 00:00:00TO COMM BD#21/BOX OF PLANS ON RACK

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-03-24 Cont ID  
Sent By pkrauss Date 2004-03-24 Time 15:32 Rev Time 0.45
Received By pkrauss Date 2004-03-24 Time 13:02 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-01-26 Cont ID  
Sent By pkrauss Date 2004-01-26 Time 12:32 Rev Time 0.45
Received By pkrauss Date 2004-01-26 Time 12:32 Sent To  
Notes
2004-01-26 00:00:00PROVISO:
 PLAN SHEET M-2 A/C EQUIPMENT SCHEDULE
 NOTE #3 "SMOKE DETECTOR MOUNTED ON
 RETURN", PER 2001 FBC(M) 606.2.1 DUCT
 SMOKE DETECTORS TO INSTALLED ON THE
 SUPPLY AIR NOT THE RETURN.
  
 PLEASE CLARIFY THE FIRE RATING TO THE
 WALL AROUND THE VAULT AND THE EXPANSION
 VAULT.
  
 PLANS ARE OTHERWISE CODE COMPLIANT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 2 Status F Date 2004-02-28 Cont ID  
Sent By kstevens Date 2004-02-28 Time 11:12 Rev Time 1.00
Received By kstevens Date 2004-02-28 Time 11:12 Sent To  
Notes
2004-02-28 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FLORIDA ADMIN. CODE
 FLORIDA STATUTES
  
 COMMENTS FROM PREVIOUS REVIEW WILL NEED
 TO BE ADDRESSED PROPERLY. THE COMMENT
 NUMBER FROM PREVIOUS WILL REMAIN THE
 SAME FOR CLAIRITY.
 2) SHT A01.1 SHOW CLEAR FLOOR SPACE FOR
 LAV'S AND W/C'S IN TOILET ROOMS PER SEC
 11-4.22.3. DOOR SHALL NOT SWING INTO THE
 CLEAR FLOOR SPACE REQUIRED FOR ANY FIX-
 TURE. SEC 11-4.22.2
 5) SHT P-2 PROVIDE STRUCTURAL INFORMAT-
 ION FOR BACKING, FASTENERS, ECT FOR THE
 WATER HEATER SHELF. - RESPONSE INDICATES
 THE SHELF WILL BE FASTENED TO THE WALL
 WITH 4 - 1/4" DIA STEEL FASTENERS. -
 INDICATE IF THIS WILL BE A SOLID WALL OR
 IF BACKING WILL BE USED. IF BACKING
 SPECIFY TYPE AND WIDTH BEING USED. ALSO
 SPECIFY TYPE AND LENGTH OF FASTENERS.
 7) PROFESSIONAL ENGINEER SHALL SIGN HIS
 NAME AND AFFIX HIS SEAL TO ALL PLANS,
 SPECIFICATIONS, REPORTS AND FINAL BID
 DOCUMENTS PROVIDED TO THE OWNER OR THE
 OWNER'S REPRESENTATIVE, OR OTHER DOCU-
 MENTS PREPARED OR ISSUED BY SAID REGIS-
 TRANT AND BEING FILED FOR PUBLIC RECORD.
 THE DATE THAT THE SIGNATURE AND SEAL IS
 AFFIXED AS PROVIDED HEREIN SHALL BE EN-
 TERED ON SAID PLANS, SPECIFICATIONS, RE-
 PORTS, OR OTHER DOCUMENTS IMMEDIATELY
 UNDER THE SIGNATURE OF THE PROFESSIONAL
 ENGINEER, FAC 61G15-23.002(1) - PER FBPE
 RULING, INITIALS ARE NOT ACCEPTABLE, AND
 A SIGNATURE IS REQUIRED ON SEAL. - RES-
 PONSE NOTED, BUT INITIALS ARE STILL BE-
 ING USED ON SEAL. A MINIMUM OF FIRST AND
 LAST NAME AS SHOWN ON LICENSE IS REQUIR-
 ED.
 *****************NEW COMMENT************
 1B) SHT P-2 WATER RISER DIAGRAM, THE
 WATER HAMMER ARRESTORS SHALL BE LOCATED
 NEAR THE FIXTURE IN AN "EFFECTIVE RANGE"
 NOT IN THE CEILING AS SHOWN. PDI-WH 201
 AND MANUF. INSTALLATION INSTRUCTIONS.
 NOTE: WATER HAMMER ARRESTORS ARE ONLY
 REQUIRED AT QUICK CLOSING VALVES SUCH AS
 DISHWASHERS, WASH MACHINES, AND ICE
 MAKERS PER SECTION 604.9.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-01-17 Cont ID  
Sent By kstevens Date 2004-01-17 Time 16:30 Rev Time 1.50
Received By kstevens Date 2004-01-17 Time 16:29 Sent To  
Notes
2004-01-17 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMIN. CODE
 FLORIDA STATUTES
 CITY CODE
  
 1) SUBMIT A DETAIL FOR THE BREAKROOM
 SINK SHOWING COMPLIANCE WITH SECTION
 11-4.24 AND ALL SUBSECTIONS.
 2) SHT A01.1 SHOW CLEAR FLOOR SPACE FOR
 LAV'S AND W/C'S IN TOILET ROOMS PER
 SECTION 11-4.22.3. DOOR SHALL NOT SWING
 INTO THE CLEAR FLOOR SPACE REQUIRED FOR
 ANY FIXTURE. 11-4.22.2
 3) SHT P-1 CONDENSATE SHALL NOT DRAIN
 INTO THE SANITARY SYSTEM. CONDENSATE
 SHALL DRAIN TO THE OUTSIDE OF THE BLDG.
 AND TIE INTO A STORM LINE, CATCH BASIN,
 OR DRYWELL. CITY CODE SECTION 90-203.
 4) SHTS P-1 & P-2 ELECTRIC WATER HEATER
 AND DETAIL, THERMAL EXPANSION CONTROL IS
 REQUIRED PER SECTION 607.3.2.
 5) SHT P-2 PROVIDE STRUCTURAL INFORMAT-
 ION FOR BACKING, FASTENERS, ECT FOR THE
 WATER HEATER SHELF.
 6) SHT P-2 SUBMIT THE WATER RISER DIA-
 GRAM IN AN ISOMETRIC FORM. SECTION
 103.1.1.
 7) PROFESSIONAL ENGINEER SHALL SIGN HIS
 NAME AND AFFIX HIS SEAL TO ALL PLANS,
 SPECIFICATIONS, REPORTS AND FINAL BID
 DOCUMENTS PROVIDED TO THE OWNER OR THE
 OWNER'S REPRESENTATIVE, OR OTHER DOCU-
 MENTS PREPARED OR ISSUED BY SAID REGIS-
 TRANT AND BEING FILED FOR PUBLIC RECORD.
 THE DATE THAT THE SIGNATURE AND SEAL IS
 AFFIXED AS PROVIDED HEREIN SHALL BE EN-
 TERED ON SAID PLANS, SPECIFICATIONS, RE-
 PORTS, OR OTHER DOCUMENTS IMMEDIATELY
 UNDER THE SIGNATURE OF THE PROFESSIONAL
 ENGINEER, FAC 61G15-23.002(1) - PER FBPE
 RULING, INITIALS ARE NOT ACCEPTABLE, AND
 A SIGNATURE IS REQUIRED ON SEAL.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 2 Status F Date 2004-02-27 Cont ID  
Sent By mmclean Date 2004-02-27 Time 16:18 Rev Time 0.00
Received By mmclean Date 2004-02-27 Time 16:18 Sent To I
Notes
2004-02-27 00:00:00DENIED, BY PLANNER JOHN ROACH 659-8031
 AWAITING SIGNED & RECORDED TERMINATION
 AGREEMENT.FOR PARALLEL LOADING ZONE,
 ANGEL FRONT & REAR OF SPACE AT 45 DEGREE
 TO ALLOW INGRESS/EGRESS INTO LOADING
 ZONE AND ADJUST LANDSCAPE PLAN
 ACCORDINGLY.

Review Stop Z ZONING
Rev No 1 Status F Date 2004-01-15 Cont ID  
Sent By mmclean Date 2004-01-15 Time 09:26 Rev Time 0.00
Received By mmclean Date 2004-01-15 Time 09:26 Sent To I
Notes
2004-01-15 00:00:00DENIED, BY PLANNER JOHN ROACH 659-8031
 GENERAL UTILITY EASEMENT WILL NEED TO BE
 ABONDENED (IN PROGRESS)
 MAJOR AMENDENT TO THE HOME DEPOT CPD
 WILL NEED TO BE APPROVED (IN PROGRESS)
 FOR PARALLEL LOADING ZONE, ANGLE FRONT
 & REAR OF SPACE AT 45 DEGREE TO ALLOW
 INGRESS/EGRESS INTO LOADING ZONE.
 ADJUST LANDSCAPE PLAN ACCORDINGLY
 CALLED CONTR MM