| 2004-01-12 00:00:00 | BUILDING REVIEW CHECKLIST: |
| | 1-NEED RECORDED NOTICE OF COMMENCEMENT. |
| | 2-STORM SHUTTERS: REVISE KEY PLAN AND |
| | INSTALLATION SCHEUDLE TO MATCH PLANS. |
| | NEED EMERGENCY EGRESS THAT COMPLIES |
| | WITH SEC. 1005.4.5 FBC 2001. |
| | B)CLEARLY INDICATE ANCHOR TYPE & SPACING |
| | TO BE USED ACCORDING TO EDGE DISTANCE |
| | PANEL SPAN, CONNECTION TYPE, DESIGN |
| | PRESSURES & STRUCTURE TO BE ATTACHED |
| | TO (MASONRY OR CONCRETE). |
| | 3-PROVIDE FLORIDA PRODUCT APPROVAL FOR: |
| | A)HORIZONTAL SLIDER WINDOW. NEED THE |
| | APPROVED DRAWINGS. |
| | B)GLASS BLOCK. |
| | C)ROOF TILE (FBC APPROVAL IS PENDING). |
| | D)SINGLE HUNG WINDOWS. |
| | E)ENTRY DOOR WITH SIDELITE ASSEMBLY. |
| | F)SLIDING GLASS DOORS. |
| | G)WINDOW MULLIONS. |
| | H)TRUSS CONNECTORS. |
| | |
| | 4-ARCHITECT TO HAVE ALL HIS INFORMATION |
| | ON TITLE BLOCK AND SIGN AND DATE DWGS |
| | AS REQ'D BY CHAPTER 481 FL STATUTES. |
| | SEE 61G1-16004 F.A.C. |
| | 5- 1HR FIRE RATED GLASS BLOCK ASSEMBLY |
| | NEED SPECIFIC UL LISTED ASSEMBLY AND |
| | REVISE DETAIL TO SHOW ALL COMPONENTS |
| | SPECIFIED ON THE UL ASSEMBLY. SECTION |
| | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| | 6-CLARIFY GARAGE DOOR BUCK SPECS.DETAIL |
| | E/4 AND NOTES ON DWG #2 DON'T MATCH. |
| | CHECK SIZE OF FASTENER TO ALLOW 2" |
| | EMBEDMENT. SEC. 104.2.1.2 CITY |
| | AMENDMENTS TO FBC 2001. |
| | 7-REVISE/UPDATE TRUSS ANCHOR SCHEDULE & |
| | ALL DETAILS THAT ARE AFFECTED BY SEC. |
| | 1609.4.3 FBC 2001. |
| | B)PROVIDE SPECIFIC SIZE OF USP RT |
| | CONNECTOR TO BE USED. SEC. 104.2.1.2 |
| | CITY AMENDMENTS TO FBC 2001. |
| | 8-ENGINEER TO SPECIFY ROOF TILE FASTENER |
| | AS REQ'D BY SEC. 104.2.1.1 OF CITY |
| | AMENDMENTS TO FBC 2001 |
| | 9-REVISE WINDOW BUCK DETAIL. SEE SECTION |
| | 1707.4.4.2 FBC 2001 FOR PROPER BUCK |
| | INSTALLATION. |
| | 10-SHEET #7: A)CLARIFY WHERE IS USP |
| | EHUH 28-3 TAKEN FROM? UNABLE TO FIND |
| | IN 2003 CATALOGUE. SEC. 104.2.1.2 CITY |
| | AMENDMENTS TO FBC 2001. |
| | B)MISSING SPECS FOR CONNECTOR AT ONE END |
| | OF GIRDER TRUSS AT REAR PORCH. SECTION |
| | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| | C)REAR ELEVATION: CLARIFY CALCULATED |
| | PRESSURES FOR OPENINGS. WHY SAME |
| | PRESSURES FOR DIFFERENT OPENING SIZE |
| | AND LOCATION. SEC. 104.2.1.2 CITY |
| | AMENDMENTS TO FBC 2001. |
| | **CLEARLY INDICATE TYPE OF WINDOW. DWG |
| | SHOW FIXED WINDOWS WHICH DOESN'T MATCH |
| | WINDOW SCHEDULE. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| | JULIO GOMEZ AT 805-6712. |