Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2004-06-23 Cont ID  
Sent By jgomez Date 2004-06-23 Time 10:01 Rev Time 0.50
Received By jgomez Date 2004-06-23 Time 10:01 Sent To PC
Notes
2004-06-23 00:00:00PRODUCT APPROVAL SUBMITTAL CHECKLIST:
 1-PROVIDE COPIES OF GARAGE DOOR DWGS
 THAT WERE SUBMITTED TO SBCCI FOR
 APPROVAL. NEED DRAWINGS THAT WERE
 SIGNED AND SEALED ON THE DATE NOTED
 ON THE SBCCI EVALUATION REPORT.
 2-PROVIDE FLORIDA PRODUCT APPROVAL COVER
 PAGE FOR ENTRY DOOR THAT MATCHES DADE
 COUNTY NOA SUBMITTED. BENCHMARK AND
 THERMA-TRU DOORS ARE DIFFERENT MODELS.
 3-SIMONTON WINDOWS/DOORS PACKAGE IS
 INCOMPLETE. NEED FLORIDA PRODUCT
 APPROVAL COVER PAGE FOR FIXED WINDOWS
 AND SLIDING GLASS DOORS USED.
 4-PROVIDE ALL INFORMATION REQUESTED ON
 PROVISO DATED 1-20-04. SEE ATTACHED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 805-6712.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-01-20 Cont ID  
Sent By csiegber Date 2004-02-27 Time 12:20 Rev Time 1.00
Received By jgomez Date 2004-01-20 Time 17:32 Sent To M
Notes
2004-01-20 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-PROVIDE COMPLETE FLORIDA/SITE SPECIFIC
 PRODUCT APPROVAL FOR ALL DOORS,WINDOWS
 GLASS BLOCK, MULLIONS, ROOF TILE AND
 STRUCTURAL CONNECTORS.
 2-REVISE DETAIL E/4. FASTENER SPECIFIED
 DON'T PROVIDE 2" MIN. EMBEDMENT. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 3-PROVIDE ENGINEERING CALCS FOR TRUSS
 CONNECTORS AND NUMBER OF FASTENERS
 SINCE VALUES ARE DIFFERENT THAN THOSE
 TESTED AND PUBLISHED BY USP TO COMPLY
 WITH SEC. 1609.4.3 FBC 2001 REGARDING
 STEEL STRESS LIMITATIONS.SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 4-REVISE DETAIL A/4. WHERE ARE TABLES
 6 AND 8 TAKEN FROM?. WE USE FBC 2001
 AND ASCE 7-98.SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 5-SHEET #7: A)REVISE DESIGN PRESSURES AT
 EXTERIOR OPENINGS. SEE TABLES 1606.2B
 AND 1606.2E FBC 2001.
 B)DESIGN PRESSURES SHOWN ON THIS DRAWING
 DON'T MATCH THOSE ON SHEET 3. REVISE
 C)REVISE NOTES ON FLOOR PLAN AND ROOF
 PLAN. MAKE SURE NOTES RELATE TO CONCRE
 TE BEAM AND NOT WOOD BEAM. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 D)WINDOWS SHOWN ON ELEVATION DON'T MATCH
 WINDOW SCHEDULE. REVISE AS REQUIRED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-01-09 Cont ID  
Sent By pkrauss Date 2004-01-06 Time 12:32 Rev Time 2.00
Received By jgomez Date 2004-01-09 Time 17:59 Sent To PC
Notes
2004-01-09 00:00:00BUILDING REVIEW CHECKLIST:
 1-NEED RECORDED NOTICE OF COMMENCEMENT.
 2-STORM SHUTTERS: A)REVISE KEY PLAN AND
 INSTALLATION SCHEDULE. NEED EMERGENCY
 EGRESS THAT COMPLIES WITH SECTION
 1005.4.5 FBC 2001.
 B)CLEARLY INDICATE ANCHOR TYPE & SPACING
 TO BE USED ACCORDING TO THE DESIGN
 PRESSURES, EDGE DISTANCE, CONNECTION
 TYPE, PANEL SPAN AND STRUCTURE TO BE
 ATTACHED TO (MASONRY OR CONCRETE). SEC
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 3-PROVIDE FLORIDA PRODUCT APPROVAL FOR:
 A)HORIZONTAL SLIDER WINDOW: NEED THE
 APPROVED DRAWINGS.
 B)GLASS BLOCK.
 C)ROOF TILE (FBC APPROVAL IS PENDING).
 D)SINGLE HUNG WINDOWS.
 E)ENTRY DOOR WITH SIDELITE ASSEMBLY.
 F)SLIDING GLASS DOORS.
 G)WINDOW MULLIONS.
 H)TRUSS CONNECTORS.
  
 4-ARCHITECT TO HAVE ALL HIS INFORMATION
 ON TITLE BLOCK AS REQUIRED BY CHAPTER
 481 FLORIDA STATUTES. SEE FAC SECTION
 61G1-16004.
 5-1 HR FIRE RATED GLASS BLOCK ASSEMBLY
 NEED SPECIFIC UL LISTED ASSEMBLY AND
 REVISE DETAIL TO MATCH SUCH ASSEMBLY.
 SPECIFY ALL COMPONENTS REQUIRED TO
 OBTAIN THE REQUIRED FIRE RATING. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 6-CLARIFY GARAGE DOOR BUCK SPECS. DETAIL
 E/4 AND NOTES ON DWG #2 DON'T MATCH.
 CHECK SIZE OF FASTENER AND EMBEDMENT
 REQUIRED. SEC. 104.2.1.2 CITY AMENDM.
 7-REVISE/UPDATE TRUSS ANCHOR SCHEDULE &
 ALL DETAILS THAT ARE AFFECTED BY SEC.
 1609.4.3 FBC 2001 REGARDING THE STEEL
 STRESS.
 B)SPECIFY USP RT SIZES TO VERIFY VALUE
 SPECIFIED ON CATALOGUE.
 C)KEEP IN MIND THAT ALL CONNECTORS NEED
 TO HAVE PRODUCT APPROVAL.
 8-ENGINEER OF RECORD TO SPECIFY ROOF
 TILE FASTENERS AS REQUIRED BY SECTION
 104.2.1.1 CITY AMENDMENTS TO FBC 2001.
 9-REVISE WINDOW BUCK DETAIL. SEE SECTION
 1707.4.4.2 FBC 2001 FOR PROPER BUCK
 INSTALLATION.
 10-SHEET #7: A)CLARIFY WHERE IS USP
 EHUH 28-3 TAKEN FROM?. UNABLE TO FIND
 THIS CONNECTOR IN 2003 USP CATALOGUE.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 B)MISSING SPECIFICATIONS FOR ONE END OF
 GIRDER TRUSS AT REAR PORCH. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 C)REAR ELEVATION: CLARIFY CALCULATIONS
 FOR DESIGN PRESSURES WITH DIFFERENT
 SIZES.
 **ALSO, SHOW TYPE OF WINDOWS. THEY ARE
 SHOWN AS FIXED WINDOWS.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 805-6712.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2004-01-06 Cont ID  
Sent By jleech Date 2004-01-03 Time 11:24 Rev Time 0.33
Received By dpalmer Date 2004-01-06 Time 06:35 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-02-27 Cont ID  
Sent By csiegber Date 2004-02-27 Time 12:20 Rev Time 0.00
Received By csiegber Date 2004-02-27 Time 12:20 Sent To B
Notes
2004-02-27 00:00:00TO JG DESK/SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-01-09 Cont ID  
Sent By mmclean Date 2004-01-09 Time 18:25 Rev Time 0.00
Received By jgomez Date 2003-12-24 Time 13:22 Sent To PC
Notes
2003-12-29 00:00:0012/24/03 TO Z
 12/29/03 TO E

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-01-22 Cont ID  
Sent By pkrauss Date 2004-01-22 Time 13:36 Rev Time 0.25
Received By pkrauss Date 2004-01-22 Time 13:36 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-01-06 Cont ID  
Sent By jgomez Date 2004-01-20 Time 17:33 Rev Time 0.33
Received By pkrauss Date 2004-01-06 Time 12:31 Sent To B
Notes
2004-01-06 00:00:00DENIED:
 RETURN AIR JUMPER FROM THE MASTER
 BEDROOM IS NOT SIZED PROPERLY.ALL AIR
 TO THE MASTER SUITE IS TO BE INCLUDED
 IN THE CALCULATION FOR TOTAL SUPPLY
 AIR.RETURN AIR SHALL BE SIZED
 ACCORDING TO THE TOTAL OF SUPPLY AIR.
 SEE THE ATTACHED SCHEDULE & REVISE
 ACCORDINGLY.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 1 Status P Date 2004-01-03 Cont ID  
Sent By jleech Date 2004-01-03 Time 11:24 Rev Time 0.25
Received By jleech Date 2004-01-03 Time 11:24 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2003-12-24 Cont ID  
Sent By dpalmer Date 2004-01-06 Time 06:36 Rev Time 0.00
Received By mmclean Date 2003-12-24 Time 15:16 Sent To I
Notes
***NONE***