| 2004-01-14 00:00:00 | BUILDING REVIEW CHECKLIST: |
| | 1-ARCHITECT TO COMPLY WITH ALL REQUIRE- |
| | MENTS OF CHAPTER 481 FLORIDA STATUTES |
| | WHEN SUBMITTING DRAWINGS FOR PUBLIC |
| | RECORDS. |
| | 2-NEED RECORDED NOTICE OF COMMENCEMENT. |
| | 3-PROVIDE COMPLETE FLORIDA/SITE SPECIFIC |
| | PRODUCT APPROVAL FOR: ALL DOORS AND |
| | WINDOWS, ROOF TILE & TRUSS CONNECTORS. |
| | 4-PROVIDE SPECIFIC UL LISTING FOR ONE HR |
| | FIRE RATED GLASS BLOCK ASSEMBLY AND |
| | REVISE DETAIL TO SHOW ALL COMPONENTS |
| | LISTED ON THE ASSEMBLY. SEC. 104.2.1.2 |
| | CITY AMENDMENTS TO FBC 2001. |
| | 5-GARAGE BUCK DETAIL AND NOTES ON DWG #2 |
| | DON'T MATCH. CHECK SIZE OF FASTENER. |
| | 6-TRUSS ANCHOR SCHEDULE: SPECIFY SIZE OF |
| | USP RT CONNECTORS. SEC. 104.2.1.2 CITY |
| | AMENDMENTS TO FBC 2001. |
| | 7-DESIGNER OF RECORD TO SPECIFY ROOF |
| | TILE FASTENERS. SEC. 104.2.1.1 CITY |
| | AMENDMENTS TO FBC 2001. |
| | 8-REVISE WINDOW BUCK DETAIL. SEE SEC. |
| | 1707.4.4.2 FBC 2001 FOR PROPER BUCK |
| | INSTALLATION. |
| | 9-A)REVISE DESIGN PRESSURES FOR EXTERIOR |
| | OPENINGS. SEE TABLES 1606.2B AND |
| | 1606.2E ACCORDING TO SIZE & LOCATION. |
| | PROVIDE CALCULATIONS FOR DESIGN |
| | PRESSURES OTHER THAN THOSE PUBLISHED |
| | ON ABOVE TABLES. SEC. 104.2.1.2 CITY |
| | AMENDMENTS TO FBC 2001. |
| | B)SIMPSON EG7 CONNECTOR HAS DIFFERENT |
| | FASTENERS THAN THOSE PUBLISHED.PROVIDE |
| | ENGINEERING CALCS SHOWING COMPLIANCE |
| | WITH SEC. 1609.4.3 FBC 2001 WHICH DOES |
| | NOT ALLOW THE STEEL STRESS TO BE |
| | INCREASED. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| | JULIO GOMEZ AT 805-6712. |