Plan Review Details - Permit 03121414
Plan Review Stops For Permit 03121414
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2004-03-05 Cont ID  
Sent By alange Date 2004-03-05 Time 08:36 Rev Time 1.00
Received By alange Date 2004-03-05 Time 08:36 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2004-02-19 Cont ID  
Sent By kstevens Date 2004-03-04 Time 16:56 Rev Time 1.50
Received By alange Date 2004-02-19 Time 10:15 Sent To Z
Notes
2004-02-19 00:00:00DENIED
 WEST PALM BEACH AMMENDMENT TO THE FBC
 104.6.5BUILDING PERMIT VALUATION
 TOTAL PERMIT FEES PAID ARE FOR $25,000
 NUMBERS 6,7,8,9 AND 10 ARE NOT INCLUDED
 IN THE PERMIT VALUE. ADDITIONAL VALUE
 OF $15,000 NEEDS TO BE APPLIED BEFORE A
 PERMIT WILL BE ISSUED.
  
 FBC 3401.7.2.6WHEN REPAIRS AND
 ALTERATIONS AMOUNTING TO MORE THAN 50%
 OF THE VALUE OF THE EXISTING STRUCTURE
 ARE MADE DURING ANY 12 MONTH PERIOD,
 THE STRUCTURE SHALL BE MADE TO CONFORM
 TO THE REQUIREMENTS FOR A NEW STRUCTURE.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-01-16 Cont ID  
Sent By kstevens Date 2004-02-13 Time 08:43 Rev Time 1.75
Received By alange Date 2004-01-16 Time 13:35 Sent To  
Notes
2004-01-16 00:00:001. DIFFERENT ENGINEERS USED FROM FIRST
 PLAN TO REVISED PLAN.HAVE FIRST
 ENGINNER SIGN OFF PROJECT TO NEW
 ENGINEER.
 2.SHOW NEW STAIR FRAMING DETAIL.
 3.SHOW INTERIOR BEARING WALL FRAMING
 DETAILS.
 4.SUBMIT PRODUCT APPROVALS FOR EXTERIOR
 DOORS,WINDOWS, AND IMPACT PROTECTION.
 5. SLEEPING ROOMS SHALL COMPLY WITH SEC.
 1005.0 FBC EMERGENCY EGRESS
 REQUIREMENTS.
 6.GLASS SHALL BE IN ACCORDANCE WITH
 SECTION FBC 2405.2.1 HAZARDOUS
 LOCATIONS.
 7.A E-1 CLEARANCE BETWEEN WOOD AND
 GROUND FBC 2304.2.5MIN. 6" CLEARANCE
 UNLESS PRESERVATIVE-TREATED WOOD IS
 USED.
 8.SHOW INSULATION DETAILS.
 9.FBC. 104.6.5 BUILDING PERMIT VALUATI
 ON TOO LOW. SEE ATTACHED CODE SECTION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-12-23 Cont ID  
Sent By alange Date 2003-12-23 Time 13:53 Rev Time 0.25
Received By alange Date 2003-12-23 Time 13:53 Sent To  
Notes
2003-12-23 00:00:00PROJECT VALUE TOO LOW.AFTER DISCUSSING
 PROJECT WITH ROBERT BROWN AND BILL
 TROBAUGH PROJECT VALUE WAS DECREASED TO
 $5000 AFTER OUR RECOMMENDATIONS TO
 INCREASE IT TO A FAIR VALUE.
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2005-03-18 Cont ID  
Sent By btrobaug Date 2005-03-18 Time 13:42 Rev Time 0.50
Received By btrobaug Date 2005-03-18 Time 13:25 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-03-04 Cont ID  
Sent By btrobaug Date 2004-03-04 Time 13:27 Rev Time 0.50
Received By btrobaug Date 2004-03-04 Time 12:39 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-02-19 Cont ID  
Sent By csiegber Date 2004-03-03 Time 09:37 Rev Time 0.50
Received By btrobaug Date 2004-02-09 Time 11:41 Sent To P
Notes
2004-02-09 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING
 INSTALL-ED. MAINS/BRKRS AND PANELS ARE
 ALL TO BERATED FOR THE AVAILABLE FAULT
 CURRENT.
 PER 110.9/215.5
  
 2} PLEASE SUBMIT PANEL SCHEDULES FOR ALL
 PANELS SO THAT CODE COMPLIANCE OF
 CIRCUITS CAN BE DETERMINED.
  
 3} PLEASE SHOW PANEL "A" LOCATION ON
 PLAN.
  
 4} PLEASE SEE RECEPTS SERVING
 KITCHEN COUNTERSPACE TO MEET 210.52C-
 SEC'S 1,2,3,4 AND 5.COUNTERTOP SPACING
 IS INCORRECT.
  
 5} THE BATHROOM OFF THE KITCHEN IS
 REQUIRED TO HAVE A GFI RECEPTACLE PER
 210.52(D) & COMLPY WITH 210.11(C)(3).
  
 6} PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CURCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  
  
  
  
 2)NOTE: PLEASE SEE BLDG PLAN REVIEW
 NOTES. PLEASE CORRELATE PLANS/PAPERWORK
 FOR COTTAGES.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-01-08 Cont ID  
Sent By csiegber Date 2004-02-06 Time 11:44 Rev Time 1.00
Received By btrobaug Date 2004-01-08 Time 12:13 Sent To P
Notes
2004-01-08 00:00:00 
 UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 ON THE PLAN FOR CODE COMPLIANCE AS
 NOTED.
  
 1} THE RISER DIAGRAM SHOWS THE 200 AMP
 PANEL AS NEW AND LISTS IT AS EXISTING
 ON THE NOTE.IT IS AGAIN LISTED AS "NEW"
 AT THE SITE LOCATION.PLEASE CORRELATE.
  
 2} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING
 INSTALL-ED. MAINS/BRKRS AND PANELS ARE
 ALL TO BERATED FOR THE AVAILABLE FAULT
 CURRENT.
 PER 110.9/215.5
  
 3} THE PANEL SCEDULE APPEARS TO HAVE THE
 BREAKER AND BREAKER AMPSINCORRECT FOR
 THEIR EQUIPMENT SERVED.
  
 4} THE #6 WIRE SHOWN ON A 100 AMP
 BREAKER (COND UNITS) DOES NOT COMPLY
 WITH 310.16.
  
 5} THE NEUTRAL FEEDING PANEL "B" IS
 SHOWN AS #3/0,PLEASE VERIFY.
  
 6} PLEASE SUBMIT PANEL SCHEDULES FOR ALL
 PANELS SO THAT CODE COMPLIANCE OF
 CIRCUITS AND OCP CAN BE DETERMINED.
  
 7} PLEASE NOTE KITCHEN COUNTER-
 -SPACE RECEPT SPACING SHALL MEET ART;
 210.52C 1,2,3,4,AND 5.
  
 8} PLEASE SEE MISSING RECEPTS FOR
 FRONT AND/OR REAR OF DWELLING.
 210.52E
  
 9} PLEASE SEE MISSING RECEPT REQ'D
 FOR A/C EQUIPMENT. 210.63
  
 10} PLEASE ADD THE SMOKE DETECTOR ON THE
 FIRST FLOOR AT THE STAIR TO COMPLY WITH
 905.2.2 FBC AND NFPA-72
  
 11} INCREASE THE BUILDING PERMIT
 VALUATION PER 104.6.5 CWPB AMMENDMENTS
 TO THE FBC, ATTACHED.
  
 12} ONLY ONE SET OF DRAWINGS ARE SEALED
 BY THE ENG. ON SHEET E-1.ALSO NOTE THAT
 SHEETS A-1 & A-2 ARE NOT SIGNED AND
 SEALED BY THE ENGINEER OF RECORD.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-03-03 Cont ID  
Sent By csiegber Date 2004-03-03 Time 09:37 Rev Time 0.00
Received By csiegber Date 2004-03-03 Time 09:37 Sent To E
Notes
2004-03-03 00:00:00TO BT DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-02-06 Cont ID  
Sent By mmclean Date 2004-02-20 Time 15:23 Rev Time 0.00
Received By csiegber Date 2004-02-06 Time 11:44 Sent To E
Notes
2004-02-06 00:00:00TO BT DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-02-20 Cont ID  
Sent By csiegber Date 2004-02-20 Time 16:10 Rev Time 0.00
Received By csiegber Date 2003-12-29 Time 11:16 Sent To E
Notes
2004-02-20 00:00:00TO BT DESK/RESUB
2003-12-29 00:00:00TO BT DESK

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2004-03-05 Cont ID  
Sent By kstevens Date 2004-01-10 Time 06:03 Rev Time 0.00
Received By alange Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2004-03-04 Cont ID  
Sent By kstevens Date 2004-03-04 Time 16:55 Rev Time 0.33
Received By kstevens Date 2004-03-04 Time 16:55 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2004-02-13 Cont ID  
Sent By btrobaug Date 2004-03-04 Time 13:27 Rev Time 0.50
Received By kstevens Date 2004-02-12 Time 14:30 Sent To B
Notes
2004-02-13 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FLORIDA ADMIN. CODE
 FLORIDA STATUTES
  
 1) SHT A-2 SANITARY RISER DIAGRAM DOES
 NOT MEET CODE REQUIREMENT. TUB IN MASTER
 BATH NOT VENTED. SEE RED LINE FOR
 CORRECT VENTING.
  
 EACH SHEET OF PLANS AND PRINTS WHICH
 MUST BE SEALED UNDER THE PROVISIONS OF
 CHAPTER 471 SHALL BE SEALED, SIGNED AND
 DATED BY THE PROFESSIONAL ENGINEER IN
 RESPONSIBLE CHARGE. FAC 61G15-23.002(2)
  
 ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME, ADDRESS AND LICENSE NUMBER ON EACH
 SHEET. IF PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS, ENGIN-
 EERS, ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME AND LICENSE NUMBER, AS WELL
 AS, THE NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. A TITLE BLOCK
 WILL SATISFY THIS REQUIREMENT. FAC
 61G15-23.002(2)
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-01-10 Cont ID  
Sent By btrobaug Date 2004-02-09 Time 12:09 Rev Time 0.50
Received By kstevens Date 2004-01-09 Time 18:50 Sent To M
Notes
2004-01-10 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SHT E-1 SANITARY RISER DIAGRAM DOES
 NOT MEET CODE REQUIREMENTS, NOR DOES IT
 REFLECT THE FLOOR PLAN.
 A) BATH #2 SHOWS A TUB ON FLOOR PLAN.
 BUT SHOWS SHOWER ON RISER.
 B) BATH #2 TUB AND LAV NOT VENTED.
 C) MASTER BATH LAVS NOT VENTED AND NOT
 IN M/BATHROOM.
 D) MASTER BATH TUB NOT VENTED.
 2) SEE RED LINE CORRECTIONS AND EXAMPLE
 FOR MASTER BATH RISER.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2004-02-20 Cont ID  
Sent By alange Date 2004-02-19 Time 10:37 Rev Time 0.00
Received By mmclean Date 2004-02-20 Time 15:22 Sent To I
Notes
***NONE***