Plan Review Details - Permit 03121400
Plan Review Stops For Permit 03121400
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-01-05 Cont ID  
Sent By jwitmer Date 2004-01-05 Time 12:16 Rev Time 2.00
Received By jwitmer Date 2004-01-05 Time 11:51 Sent To  
Notes
2004-01-05 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03121400
 ADD: 721 VILLAGE BLVD
 CONT: DAVIS CONSTRUCTION
 TEL: (561)718-8161
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST REVIEW
 ACTION: DENIED
  
 1)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 DISCREPANCY: SHEET A0.1 EXISTING FLOOR
 PLAN INDICATES AN EXISTING MANAGERS
 OFFICE, CREW MEMBERS TOILET ROOM AND
 SODA ROOM, SHEET A1.0 INDICATES A PAIR
 OF NEW 3'-0" DOORS AND A RECONFIGURATION
 OF THIS SPACE. PLANS NOTE " NO WORK" IN
 THIS AREA? COMMENT PLEASE.
  
 2)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 2A.) DEPENDING ON WHICH SHEET YOU
 LOOK AT AN EXTERIOR DOOR BY THE REGIONAL
 MANAGERS OFFICE?
 2B.) ALSO ON SHEET A1.0 BY THE REGION
 AL MANAGERS OFFICE EITHER A NEW WALL OR
 A HEADER APPEARS?
  
 3) THE NEW EXTERIOR INDICATES EITHER
 NEW DOORS OR GATES SEPERATING THIS AREA
 FROM THE COMMON AREAS, WHICH IS IT?
 ALSO THE OCCUPANT COUNT IN THIS AREA
 IS OVER 50 WITH STAFF, 2 MEANS OF EGRESS
 ARE PROVIDED, BUT THE MEANS OF EGRESS
 TO THE EAST SIDE DOESN'T HAVE A 44"
 MEANS OF EGRESS.
 PLANS ALSO DO NOT INDICATE THE
 EGRESS FOR THE STAFF TO THE WORKING AREA
 OF THE OUTSIDE BAR?
  
 4) PLANS DO NOT HAVE A SECTION THROUGH
 INDICATING WHERE THE NEW SLAB WILL BE,
 NOR THE HEIGHT? WILL THERE BE A FOUNDA-
 TION FOR FUTURE EXSPANSION?
  
 5) THERE APPEARS TO BE ROOF DRAINS AND
 LITTERS THAT EMPTIED INTO THE EXISTING
 FLOWER BEDS? WHERE DO THEY NOW EMPTY AT?
  
 6) WHAT WILL THE TOTAL OCCUPANT LOAD BE
 FOR THIS ESTABLISHMENT?
  
 7)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-01-02 Cont ID  
Sent By dpalmer Date 2004-01-02 Time 05:35 Rev Time 0.50
Received By dpalmer Date 2004-01-02 Time 05:35 Sent To  
Notes
2004-01-02 00:00:00**************** UNSAT ***********
  
 1)NOTE: PLEASE SEE RISER DIAGRAM, NOTE
 AT BOTTOM OF RISER MENTIONS,"EXISTING"
 ELECTRICAL , YET NOTE ABOVE WHAT APPEARS
 TO BE A MAIN, MENTIONS TO "PROVIDE" A
 42K RATED MAIN BREAKER???? PLEASE SEE
 THAT THIS SOUNDS LIKE A NEW MAIN IS
 BEING INSTALLED??
 IF THIS IS THE CASE, PLEASE PROVIDE
 MORE INFORMATION ON MAIN.
 215.5
  
 2)NOTE: PLEASE ALSO PROVIDE METHOD OF
 EQUIPMENT GROUNDING FROM MAIN TO 1200A
 MLO DIST PANEL.250.110,250.24,SIZE PER
 250.122.
  
 3)NOTE: PLEASE SEE LOAD CALCULATIONS,
 PLEASE SEE TOTAL LOAD SHOWN.
 PLEASE SEE THAT ALL LOADS CAN NOT BE
 DERATED AS SHOWN AT 65%. PLEASE SEE
 220.36
  
 4)NOTE; PLEASE NOTE, PANEL 'C' ON RISER
 IS SHOWN FEEDING PANEL 'KP' PLEASE SEE
 PANEL 'C' SCHEDULE, KP IS NO WHERE TO BE
 FOUND. PLEASE CLARIFY.215.5
  
 5)NOTE: PLEASE SHOW /CLARIFY ANY NEW
 OR EXISTING LIGHTING FOR AREA SHOWN.
 LS 101 5-8
  
 PLEASE SEE COMMENT FROM OTHER REVIEWERS
 THAT MAY AFFECT ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-01-02 Cont ID  
Sent By mcarsill Date 2004-01-02 Time 07:15 Rev Time 0.00
Received By mcarsill Date 2004-01-02 Time 07:15 Sent To  
Notes
2004-01-02 00:00:001) PLEASE PROVIDE DETAILS THAT THE
 NEW GREEN CANVAS AWNINGS WILL BE
 FIRE RETARDANT.
  
 2) WHAT EMERGENCY LIGHTING OR EXIT
 SIGNAGE WILL BE PROVIDED FOR THE
 OUTSIDE BAR AREA.
  
 3) PLEASE INDICATE IF ANY EXISTING
 FIRE LANE SIGNS REMAIN ON THE COLUMNS
 FOR THE PORTE CACHERE. AT ONE TIME THIS
 AREA WAS A FIRE LANE.
  
 4) PLEASE INDICATE SIZES AND HARDWARE
 FOR THE TWO EXIT DOORS FROM THE OUTSIDE
 BAR.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-12-23 Cont ID  
Sent By csiegber Date 2003-12-23 Time 11:45 Rev Time 0.00
Received By csiegber Date 2003-12-23 Time 11:45 Sent To  
Notes
2003-12-23 00:00:00TO COMM BD#19

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-01-07 Cont ID  
Sent By pkrauss Date 2004-01-07 Time 06:39 Rev Time 0.40
Received By pkrauss Date 2004-01-06 Time 16:53 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-01-07 Cont ID  
Sent By kstevens Date 2004-01-07 Time 14:11 Rev Time 1.00
Received By kstevens Date 2004-01-07 Time 14:11 Sent To  
Notes
2004-01-07 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) SANITARY AND WATER RISER DIAGRAMS ARE
 REQUIRED PER SECTION 104.3.1.1
 2) DRAINAGE REQUIRED FOR ICE MACHINE,
 HAND SINK, AND S/S DRAIN BOARD. INDIRECT
 WASTE REQUIRED FOR DRAIN BOARD AND ICE
 MACHINE. PLEASE SUBMIT INFORMATION FOR
 REVIEW.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2004-01-14 Cont ID  
Sent By gjoyce Date 2004-01-14 Time 10:43 Rev Time 0.50
Received By gjoyce Date 2004-01-14 Time 10:43 Sent To  
Notes
2004-01-14 00:00:00REQUIRES A MINOR AMENDMENT/MUST GET APPR
 OVAL FROM VILLAGE COMMENS FOR AWNINGS CA
 LLED DAVIS CONST, GMJ