Plan Review Details - Permit 03121385
Plan Review Stops For Permit 03121385
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-04-12 Cont ID  
Sent By csiegber Date 2004-04-12 Time 12:05 Rev Time 0.00
Received By csiegber Date 2004-04-12 Time 12:05 Sent To M
Notes
2004-04-12 00:00:00TO PK BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-12-22 Cont ID  
Sent By csiegber Date 2003-12-22 Time 15:52 Rev Time 0.00
Received By csiegber Date 2003-12-22 Time 15:52 Sent To M
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-04-16 Cont ID  
Sent By pkrauss Date 2004-04-16 Time 14:10 Rev Time 0.30
Received By pkrauss Date 2004-04-16 Time 14:10 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-12-30 Cont ID  
Sent By csiegber Date 2004-04-12 Time 12:05 Rev Time 0.25
Received By pkrauss Date 2003-12-30 Time 07:18 Sent To  
Notes
2003-12-30 00:00:00DENIED:
 BUILDING PERMIT 03111303 INDICATES
 PLANSAND MECHANICAL INFORMATION TO BE
 SUBMITTED WITH MECHANICAL PERMIT
 APPLICATION.NO MECHANICAL INFORMATION
 SUBMITTED.PLEASE PROVIDE THE FOLLOWING
 INFORMATION FOR REVIEW:
  
 1.ENERGY & MANUAL J CALCULATIONS PER
 2001 FBC CHAPTER 13 SUB-CHAPTER 600.
  
 2.PROVIDE EQUIPMENT SCHEDULE.
  
 3.PROVIDE PLANS INDICATING DUCT/GRILLE
 SIZE, MATERIAL AND LAYOUT.
  
 4.PLEASE NOTE RETURN AIR REQUIRED FROM
 BEDROOM AREAS PER 2001 FBC(M) 601.4.
  
 5.NARRATIVE SUBMITTED FOR PROPOSED
 WORK INDICATES WORK TO BE DONE UNDER THE
 SFBC.SHOULD READ THE FLORIDA BUILDING
 CODE (FBC).
  
 6.AUXILIARY DRAIN PAN WITH OVERFLOW
 PROTECTION REQUIRED PER 2001 FBC(M)
 307.2.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.