| Plan Review Stops For Permit 03121378 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2004-02-19 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2004-02-19 |
Time |
12:05 |
Rev Time |
1.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2004-02-19 00:00:00 | | | | PROVISO | | | ------- | | | | | | SUBMIT NEW PRODUCT TEST REPORT FOR | | | IMPACT RATED GLAZING. | | | | | | REVISE WALL SECTION DETAIL, 1/2' | | | PLYWOOD NOT PERMITED PER FIRE DISTRICT | | | REGULATIONS. | | | | | | | | | | | | | | | | | | | | | LUIS MARTINEZ | | | 8056710 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2004-01-14 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2004-01-14 |
Time |
14:38 |
Rev Time |
1.10 |
| Received By |
jwitmer |
Date |
2004-01-14 |
Time |
14:38 |
Sent To |
|
|
| Notes |
| 2004-01-14 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT: 03121378 | | | ADD: 2161 PALM BEACH LAKES BLVD | | | CONT: JANIS SERVICES | | | TEL: (561)540-8977 | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | | | | 1ST REVIEW | | | ACTION: DENIED | | | | | | 1) PROVIDE NOC RECORDED WITH THE CLERK | | | OF COURT BEFORE A PERMIT CAN BE ISSUED. | | | REFILE NOC, WHEN WORK HAS NOT STARTED | | | WITHIN 90 DAYS OF FILINGNOC HAS TO BE | | | RERECORDED. | | | | | | 2)FL BLD CODE 104.2.1.2 | | | ADDITIONAL INFORMATION REQUIRED, | | | DISCREPANCY, SQUARE FOOT AREA, PERMIT | | | APP 1565 VS 829 ON PLANS AREA AFFECTED. | | | USING THE 829 THE EXITING MEETS CODE, | | | IF THE 1565 IS USED 2 MEANS OF EGRESS | | | ARE REQUIRED. | | | | | | 3) THE PRODUCT TESTING REPORTS ARE MISS- | | | ING THE FLORIDA PRODUCT APPROVAL COVER | | | SHEET. | | | PRODUCT APPROVALS SUBMITTED WITH | | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 | | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | | PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A COVER SHEET THAT LISTS | | | THE PRODUCT IDENTITY NUMBER FROM THE | | | STATE. IF THE PRODUCT DOES NOT HAVE | | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | | SPECIFIC FORM PER RULE 9B-72. SEE | | | ATTACHMENT. WWW.FLORIDABUILDING.ORG | | | | | | FL BLD CODE 2001 SECTION 103.6, | | | 1606.1.4, 1707.4 & 3401.7.2.4. | | | PROCEDURES: 1(B) A COMPLETE INSTALLATION | | | SCHEDULE SUMMARIZING & IDENTIFYING | | | OPENING SIZES, STORY HEIGHTS, UNIT MARK | | | NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM | | | BAR REINFORCING REQUIREMENTS, WALL PRES- | | | SURE ZONES, SLAT TYPES, ETC., SHALL BE | | | SUBMITTED AT TIME OF PERMIT APPLICATION | | | TO FACILITATE PLAN REVIEW AND PERMIT | | | ISSUANCE. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2004-03-29 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2004-03-29 |
Time |
17:36 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2004-03-29 |
Time |
17:24 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2004-01-05 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-01-05 |
Time |
06:01 |
Rev Time |
0.33 |
| Received By |
dpalmer |
Date |
2004-01-05 |
Time |
05:59 |
Sent To |
|
|
| Notes |
| 2004-01-05 00:00:00 | PASSED PENDING FIRE REVIEW |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2004-02-05 |
|
|
Cont ID |
|
| Sent By |
nmccray |
Date |
2004-02-05 |
Time |
16:02 |
Rev Time |
0.00 |
| Received By |
nmccray |
Date |
2004-02-05 |
Time |
16:02 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2004-01-08 |
|
|
Cont ID |
|
| Sent By |
nmccray |
Date |
2004-01-08 |
Time |
10:20 |
Rev Time |
0.00 |
| Received By |
nmccray |
Date |
2004-01-08 |
Time |
10:20 |
Sent To |
|
|
| Notes |
| 2004-01-08 00:00:00 | ************DENIED********************** | | | WHAT WILL BE THE OCCUPANT LOAD IN THIS | | | OUTSIDE BAR WITH STANDING AND WAITING | | | AREA. A SECOND EXIT GATE MAYBE REQUIRED. | | | | | | NATE MCCRAY, CAPTAIN | | | 805-6722 OR 835-2910 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2004-03-16 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-03-16 |
Time |
16:34 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-03-16 |
Time |
16:34 |
Sent To |
P |
|
| Notes |
| 2004-03-16 00:00:00 | TO KS BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2004-02-04 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-02-04 |
Time |
10:43 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-02-04 |
Time |
10:43 |
Sent To |
|
|
| Notes |
| 2004-02-04 00:00:00 | TO COMM BD#29 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2004-02-19 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-02-19 |
Time |
12:14 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2003-12-22 |
Time |
15:38 |
Sent To |
|
|
| Notes |
| 2004-01-02 00:00:00 | 12/22/03 TO Z | | | TO COMM BD#42 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2004-01-07 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2004-01-07 |
Time |
12:24 |
Rev Time |
0.15 |
| Received By |
pkrauss |
Date |
2004-01-07 |
Time |
12:24 |
Sent To |
|
|
| Notes |
| 2004-01-07 00:00:00 | NO MECHANICAL PLANS SUBMITTED FOR REVIEW |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2004-03-20 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2004-03-20 |
Time |
07:21 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2004-03-20 |
Time |
07:21 |
Sent To |
|
|
| Notes |
| 2004-03-20 00:00:00 | REVISION OK - ADDED FLOOR DRAIN |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2004-02-06 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-03-16 |
Time |
16:35 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2004-02-06 |
Time |
17:06 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2004-01-14 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2004-01-14 |
Time |
07:37 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2004-01-14 |
Time |
07:37 |
Sent To |
|
|
| Notes |
| 2004-01-14 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | | | | 1) SPECIFICATION SHEETS FROM HOTEL & | | | RESTURANT DIVISION SHALL BE SUBMITTED ON | | | EACH SET OF PLANS. | | | 2) ADDITIONAL SQUARE FOOTAGE MAY REQUIRE | | | ADDITIONAL PLUMBING FACILITIES. INDICATE | | | EXISTING SQUARE FOOTAGE OF SPACE AND | | | SHOW EXISTING TOILET FACILITIES. | | | 3) DRAINAGE SHALL CONNECT TO BLDG. DRAIN | | | OR BRANCH LINE NOT FLOOR DRAIN AS STATED | | | ON SHT A2.0 | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2004-01-02 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2003-12-22 |
Time |
15:39 |
Rev Time |
0.00 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|