| 2004-02-02 00:00:00 | BUILDING PLAN REVIEW: FAILED!! |
| | |
| | |
| | 1. SURVEY SAYS STRUCTURE IS IN A "B" |
| | ZONE. MAPS SHOW "AO" REQUIRING A |
| | COMPLETED ELEVATION CERTIFICATE. |
| | |
| | 2. THE TYPE OF CONSTRUCTION SHOWN ON |
| | SHEET A0.01 HAS BEEN CHANGED TO TYPE |
| | V. ACCORDING TO TABLE 600 IT SHOULD BE |
| | A TYPE "VI" ZONE. CORRECT NOTES. |
| | |
| | 3. A SIGNED AND SEALED COPY OF THE SOIL |
| | REPORT MUST BE SUBMITTED. |
| | |
| | 4. CORRECT DETAIL FOR GLASS BLOCK TO |
| | COMPLY WITH 1 HOUR ASSEMBLY ON ZERO LOT |
| | LINE. |
| | |
| | 5. PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, |
| | 2003 ARE REQUIRED TO COMPLY WITH THE |
| | FLORIDA PRODUCT APPROVAL SYSTEM. FOR |
| | INFORMATIONPLEASE SEE THE STATE WEBSITE |
| | AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. |
| | |
| | 6. TERMITE PROTECTION: A SOIL BAIT |
| | TREATMENT IS THE METHOD DESCRIBED IN |
| | SEC. 1816.1.7.A SIGNED CONTRACT IS |
| | REQUIRED TO BE SUBMITTED ASSURING THE |
| | INSTALLATION, MAINTENANCE, & MONITORING |
| | OF THE BAITING SYSTEM FOR A MINIUM OF |
| | FIVE (5) YEARS. SEE FBC 1816 TERMITE |
| | PROTECTION. |
| | |
| | ANY QUESTIONS PLEASE CALL: |
| | LEA SMITH, BUILDING PLANS EXAMINER |
| | 805-6713 |