| 2004-02-20 00:00:00 | DENIED |
| | |
| | 1) SURVEY HAS WRONG FLOOD ZONE AND MAP |
| | NUMBER LISTED. SUBMIT CORRECTED SURVEY. |
| | |
| | 2) 1001.1.3/ 1005.4 ZERO LOT LINE |
| | EGRESS:WHEN ACCESS TO OR FROM A RE- |
| | QUIRED EMERGENCY ESCAPE AND RESCUE OPEN- |
| | ING OF A STRUCTURE TO THE PUBLIC WAY, |
| | REQUIRES TRANSVERSING A PROPERTY |
| | (ADJOINING LOT) THAT IS NOT PART OF THE |
| | ONE WHICH THE STRUCTURE IS LOCATED, AN |
| | EGRESS EASEMENT THROUGH THE ADJOINING |
| | PROPERTY IS REQUIRED AND SHALL BE RECORD |
| | ED IN THE COUNTY RECORDS. THIS EASEMENT |
| | SHALL BE A MINIMUM OF 3' WIDE AND NOTH- |
| | ING SHALL BE PLACED WITHIN THE EASEMENT |
| | AREA WHICH WOULD BLOCK ACCESS TO THE |
| | EASEMENT AND OR IMPEDE EMERGENCY EGRESS |
| | FROM THE RESCUE OPENING TO THE PUBLIC |
| | WAY. NO LANDSCAPING, FENCES OR OTHER |
| | IMPEDIMENTS SHALL BE INSTALLED IN THIS |
| | EASEMENT. SUBMIT RECORDED COPY OF |
| | SUBDIVISION COVENANTS WHICH SPECIFY AN |
| | EMERGENCY EGRESS EASEMENT AS SPECIFIED |
| | ABOVE. |
| | |
| | 3) THE FLOOR PLANS DO NOT SPECIFY A MARK |
| | FOR THE TRANSOM ABOVE THE FRONT DOORS. |
| | PLEASE CLARIFY IF THIS IS A WINDOW OR |
| | NOT. THE STORM PANEL KEY PLAN AND |
| | SCHEDULE INDICATE A WINDOW AT THIS |
| | LOCATION. |
| | |
| | 4) ON THE ROOF FRAMING PLANS ON S-1 THE |
| | LINES TYING THE TRUSS ANCHORS TO THE |
| | TRUSSES ARE TOO FAINT TO SEE. PLEASE |
| | SUBMIT LEGIBLE SHEETS. |
| | |
| | 5) REVISE DETAIL 4 ON S4. THE WEDGE |
| | ANCHOR SHOWN IN THE TRUSS SHOULD BE A |
| | THROUGH BOLT. |
| | |
| | 6) SUBMIT STATE OR LOCAL PRODUCT |
| | APPROVALS FOR THE DOUBLE OUTSWING ENTRY |
| | DOORS. |
| | |
| | 7) SUBMIT THE EVALUATION REPORT FOR THE |
| | STORM PANELS. |
| | |
| | 8) SUBMIT LOCAL PRODUCT APPROVAL FORMS |
| | FOR THE SUSHINE WINDOWS MANUFACTURING |
| | PRODUCTS WITH THE REQUIRED QUALITY |
| | ASSURANCE ENTITY LISTED. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |