Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2004-04-06 Cont ID  
Sent By jwitmer Date 2004-04-06 Time 16:09 Rev Time 0.75
Received By jwitmer Date 2004-04-06 Time 16:09 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-02-20 Cont ID  
Sent By csiegber Date 2004-03-22 Time 10:52 Rev Time 1.33
Received By jwitmer Date 2004-02-20 Time 10:05 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-01-27 Cont ID  
Sent By jwitmer Date 2004-01-27 Time 12:07 Rev Time 0.50
Received By jwitmer Date 2004-01-27 Time 12:07 Sent To  
Notes
2004-01-27 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03121021
 ADD: 1016 CLARE AVE # 5
 CONT: SPRADLEY
 TEL: (561)301-1004
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 SECOND REVIEW
 ACTION: DENIED
  
 COMMENTS NOT ADDRESSED FROM FIRST
 REVIEW.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-01-14 Cont ID  
Sent By jwitmer Date 2004-01-14 Time 15:39 Rev Time 1.11
Received By jwitmer Date 2004-01-14 Time 15:39 Sent To  
Notes
2004-01-14 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03121021
 ADD: 1016 CLARE AVE
 CONT: SPRADLEY CONST
 TEL: (561)301-1004
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST BUILDING REVIEW
 ACTION: DENIED
  
 1)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 4HR RATED WALL BETWEEN UNITS 4 & 5. THE
 PLANS INDICATE THE USE OF ROLL UP DOOR?
 EXPLAINOR PROVIDE RATING ON DOOR?
  
 2) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) GLASS BLOCK, WALL THICKNESS MAY
 REQUIRE STORM SHUTTERS.
 B) NEW ROLL UP DOOR.
 C) NEW STOREFRONT GLASS
 D) TELLAR STYLE STEEL DOOR
  
 3)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 4)11-4.8.2 SLOPE & RISE. THE LEAST
 POSSIBLE SLOPE SHALL BE USED FOR ANY
 RAMP. THE MAXIMUM SLOPE FOR A RAMP IN
 NEW CONSTRUCTION SHALL BE 1 TO 12. THE
 MAXIMUM RISE FOR RUN SHALL BE 30" (SEE
 FIGURE 16).
  
 5)11-4.8.4.(2) LANDINGS. ALL LANDINGS
 ON RAMPS SHALL NOT BE LESS THAN 60"
 CLEAR, & THE BOTTOM OF EACH RAMP SHALL
 HAVE NOT LESS THAN 72" OF STRAIGHT &
 LEVEL CLEARENCE.
  
 6)11.4.8.5. HANDRAILS: IF A RAMP HAS
 A RISE GREATER THAN 6" OR A HORIZONTAL
 PROJECTION GREATER THAN 72", THEN IT
 SHALL HAVE HANDRAILS ON BOTH SIDES.
  
 7)1204.2 SURROUNDING MATERIALS;
 THE WALLS & FLOORS OF ALL PUBLIC REST-
 ROOMS SHALL BE LINED WITH NONABSORBANT
 MATERIALS TO A HEIGTH OF 4'-0" ABOVE THE
 FLOOR.
  
 8) PLANS INDICATE A SECOND AND THIRD
 FLOOR, PLEASAE HOW EXITING.
  
 9) 1016.2.1 EMERGENCY LIGHTING , PROVIDE
 LAYOUT SHOWING STORAGE AREAS AND EGRESS
 ROUTES, PLANS INDICATE A THIRD FLOOR BUT
 NO INFORMATION PROVIDED.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2004-04-20 Cont ID  
Sent By dpalmer Date 2004-04-20 Time 06:34 Rev Time 0.25
Received By dpalmer Date 2004-04-20 Time 06:34 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2004-03-31 Cont ID  
Sent By csiegber Date 2004-04-14 Time 13:06 Rev Time 0.75
Received By btrobaug Date 2004-03-31 Time 12:58 Sent To  
Notes
2004-03-31 00:00:00 
 PLEASE NOTE THAT THE BUILDING PLAN HAS
 CHANGED. THERE CAN BE NO ELECTRICAL
 PLANS SUBMITTED FOR REVIEW PRIOR TO THE
 BUILDING PLAN BEING SUBMITTED FOR
 REVIEW.
 ALL PLANS MAY BE SUBMITTED TOGETHER TO
 EXPEDITE THE REVIEW PROCESS.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE NOTE THAT OFFICE AREAS ARE TO
 BE CALCULATED PER 220.3(A).
  
 2} PLEASE SHOW LOAD CALCULATIONS,
 PLEASE SHOW PER:
 220.3,220.10,220.11,220.13 ETC.
 PLEASE ALSO SHOW ALL CONTINOUS LOADS
 AT 125% PER 215.2(A)(1),210.19(A)(1) &
 210.20(A).
  
 3} PANEL "A" CALCULATION REMAINS THE
 SAME AS ON THE PERMITED SET OF PLANS,
 BUT ACCORDING TO THE REVISION SET THERE
 ARE IS LIGHTING AND RECEPTACLE LOADS
 ADDED, PLEASE CORRECT.
  
 4} PANEL "B" HAD A ROLLUP DOOR REMOVED
 FROM THE PANEL , PLEASE INDICATE WHERE
 IT IS BEING FED FROM, INCLUDE IT ON A
 SCHEDULE AND IN THE LOAD CALC'S.
  
 5} PANEL "C" IS BEING FED FROM THE MAIN
 PANEL ON THE RISER DIAGRAM, BUT IS NOT
 ON THAT PANEL.SCHEDULE, NO OCP OR WIRE
 SIZE LISTED. PLEASE SHOW HOW FED.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-01-26 Cont ID  
Sent By alange Date 2004-03-30 Time 11:11 Rev Time 0.50
Received By dpalmer Date 2004-01-26 Time 09:09 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-12-30 Cont ID  
Sent By dpalmer Date 2003-12-30 Time 08:51 Rev Time 1.00
Received By dpalmer Date 2003-12-30 Time 08:23 Sent To  
Notes
2003-12-30 00:00:00*************** UNSAT ************
  
 1)NOTE: PLEASE CORRELATECIRCUITS #'S
 ON PLANS AND PANEL SCHEDULES.
  
 2)NOTE: PLEASE SEE THAT MEANS OF EGRESS
 LIGHTING CONTROL MUST ALSO HAVE A MEANS
 CONTROL FOR STAIRWAYLIGHTING FROM
 SECOND FLR. LS101 5-8
  
 3)NOTE: PLEASE SEE FIRE REVIEW NOTES AS
 THEY WILL HAVE A DIRECT AFFECT ON
 ELECTRICAL PLANS.
  
 4)NOTE: PLEASE CLARIFYSERVICE, SHOWN
 AS NEW, BUT IF SERVICE EXSITING PLEASE
 NOTE AS EXISTING.
  
 5)NOTE: PLEASE CLARIFY WORK SHOP, WHAT
 WILL BE THIS ROOM BE USED FOR. PLEASE
 SHOW ANY CLASS LOCATIONS, IF ANY.
  
 6)NOTE; PLEASE SEE 600.5 , IF BLDG WILL
 HAVE ANY PUBLIC TRAFFIC.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2004-04-01 Cont ID  
Sent By nmccray Date 2004-04-01 Time 10:47 Rev Time 0.00
Received By nmccray Date 2004-04-01 Time 10:47 Sent To  
Notes
2004-04-01 00:00:00REVISIONS DATED 3-19-04 AND 3-29-04

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-01-22 Cont ID  
Sent By mcarsill Date 2004-01-22 Time 16:11 Rev Time 0.00
Received By mcarsill Date 2004-01-22 Time 16:11 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-12-29 Cont ID  
Sent By mcarsill Date 2003-12-29 Time 16:53 Rev Time 0.00
Received By mcarsill Date 2003-12-29 Time 16:53 Sent To  
Notes
2003-12-29 00:00:001) NO EXIT SIGNS DIRECTING PERSONS
 TO THE DOOR THAT LEADS TO THE EXISTING
 HC RAMP AND EXIT DOOR.
  
 2) PLEASE EXPLAIN PURPOSE AND FUNCTION
 FOR NEW ROLL UP DOORS.
  
 3) PLEASE PROVIDE DETAILS ON EXISTING
 EXTERIOR STAIR FROM SECOND FLOOR.
 PLEASE INDICATE STAIR RISE AND RUN,
 TREAD SIZE AND HANDRAIL INFORMATION.
  
 4) NO EMERGENCY LIGHTING SHOWN IN
 EXISTING HC RAMP AND EXIT AREA.
  
 5) PLEASE EXPLAIN SINGLE EXIT RATIONALE
 FROM SEVERAL OF THE ROOMS IN SPACE #5.
  
 6) FOR LARGE AREAS OF THE SPACE, THERE
 APPEARS TO BE TOO FEW EMERGENCY
 LIGHT FIXTURES.
  
 7) EXISTING ROLL-UP DOORS APPEAR TO
 REMAIN. PLEASE INDICATE RATING, AND
 WILL THEY BE UP OR DOWN.
  
 8) NO FIRE EQUIPMENT SHOWN ON PLANS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-04-14 Cont ID  
Sent By csiegber Date 2004-04-14 Time 13:06 Rev Time 0.00
Received By csiegber Date 2004-04-14 Time 13:06 Sent To E
Notes
2004-04-14 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-03-30 Cont ID  
Sent By alange Date 2004-03-30 Time 11:11 Rev Time 0.00
Received By alange Date 2004-03-30 Time 11:11 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-03-22 Cont ID  
Sent By csiegber Date 2004-03-22 Time 10:52 Rev Time 0.00
Received By csiegber Date 2004-03-22 Time 10:52 Sent To B
Notes
2004-03-22 00:00:00TO JW DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-01-21 Cont ID  
Sent By csiegber Date 2004-01-21 Time 12:04 Rev Time 0.00
Received By csiegber Date 2004-01-21 Time 12:04 Sent To  
Notes
2004-01-21 00:00:00TO COMM BD#31

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-01-14 Cont ID  
Sent By csiegber Date 2004-02-17 Time 16:31 Rev Time 0.00
Received By csiegber Date 2003-12-17 Time 16:27 Sent To  
Notes
2003-12-17 00:00:00TO COMM BD#64


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved