Plan Review Details - Permit 03121012
Plan Review Stops For Permit 03121012
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-02-12 Cont ID  
Sent By nmccray Date 2004-02-12 Time 09:42 Rev Time 0.00
Received By nmccray Date 2004-02-12 Time 09:42 Sent To  
Notes
2004-02-12 00:00:00REVISION DATED FOR 02-12-04

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2003-12-29 Cont ID  
Sent By pkrauss Date 2003-12-22 Time 15:14 Rev Time 0.00
Received By nmccray Date 2003-12-29 Time 13:41 Sent To  
Notes
2003-12-29 00:00:00**********PROVISO***********************
 SEPARATE PERMIT AND SHOP DRAWING ARE
 REQUIRED FOR SUPPRESSION SYSTEM
  
 NATE MCCRAY, CAPTAIN
 805-6722 OR 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-02-25 Cont ID  
Sent By csiegber Date 2004-02-25 Time 11:24 Rev Time 0.00
Received By csiegber Date 2004-02-25 Time 11:24 Sent To M
Notes
2004-02-25 00:00:00TO PK BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-12-17 Cont ID  
Sent By csiegber Date 2003-12-17 Time 15:41 Rev Time 0.00
Received By csiegber Date 2003-12-17 Time 15:41 Sent To M
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2004-03-01 Cont ID  
Sent By pkrauss Date 2004-03-01 Time 07:45 Rev Time 0.40
Received By pkrauss Date 2004-03-01 Time 07:27 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-02-12 Cont ID  
Sent By csiegber Date 2004-02-25 Time 11:24 Rev Time 0.40
Received By pkrauss Date 2004-02-12 Time 09:22 Sent To  
Notes
2004-02-12 00:00:00SEE PROVISO FROM 1ST REVIEW.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-12-22 Cont ID  
Sent By csiegber Date 2003-12-22 Time 15:41 Rev Time 0.40
Received By pkrauss Date 2003-12-22 Time 15:05 Sent To FIRE
Notes
2003-12-22 00:00:00PROVISO:
 1. GREASE DUCT SHALL TERMINATE A MINIMUM
 OF 10 FT FROM PROPERTY LINE, ADJACENT OR
 CONTINGUOUS BUILDINGS, AND AIR INTAKES.
  
 2. PROVIDE MANUFACTURER SUBMITTAL &
 INSTALLATION INSTRUCTIONS FOR THE FIRE
 MASTER 15A ON THE JOBSITE AT THE TIME OF
 INSPECTION. PLEASE NOTE WELDS TO BE
 INSPECTED PRIOR TO COVERING WITH FIRE
 WRAP.
  
 3. SHOULD THE ELEVATION FOR THE FANS
 EXCEED 16 FT, A PERMANENT MEANS OF
 ACCESS IS REQUIRED.SLOPEOF THE ROOF
 GREATER THAN 33% SLOPE SHALL HAVE A
 LEVEL PLATFORM PER 2001 FBC(M) 306.5 &
 306.6.
  
 4.ADDITIONAL PERMIT AND PLANS REQUIRED
 FOR THE FIRE SUPPRESSION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.