Plan Review Details - Permit 03120955
Plan Review Stops For Permit 03120955
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2005-02-07 Cont ID  
Sent By rmcdouga Date 2005-02-07 Time 13:59 Rev Time 0.00
Received By rmcdouga Date 2005-02-07 Time 13:59 Sent To  
Notes
2005-02-07 00:00:00PROVISO
  
 1) REVISIONS TO SHEETS A2, A4 AND A5 ARE
 OK. HOWEVER STRUCTURAL SHEET S1 WILL
 HAVE TO BE REVISED TO SHOW REVISED
 POURED CELL LOCATIONS AND SHEET S4 TO
 SHOW REVISED LINTEL SCHEDULE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2004-06-16 Cont ID  
Sent By rmcdouga Date 2004-06-16 Time 08:43 Rev Time 0.00
Received By rmcdouga Date 2004-06-16 Time 08:43 Sent To  
Notes
2004-06-16 00:00:00REVISION TO CHANGE TO R-4.2 FOIL
 INSULATION IS OK.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2004-04-28 Cont ID  
Sent By csiegber Date 2004-06-11 Time 10:49 Rev Time 0.00
Received By rmcdouga Date 2004-04-28 Time 15:31 Sent To  
Notes
2004-04-28 00:00:00BUILDING PROVISO
  
 1) SUBMIT (2)SIGNED AND SEALED COPIES OF
 THE SOIL REPORT PER FAC 61G15-35 AND
 CITY AMENDMENTS TO FBC 1804.2.2.
  
 2) SUBMIT (2) SIGNED AND SEALED COPIES
 OF THE SURVEY.
  
 3) SUBMIT STATE PRODUCT APPROVALS FOR
 THE FOLLOWING:
 - ARCHED FIXED GLASS WINDOWS
 - DOUBLE INSWING ENTRY DOORS
 - SINGLE OUTSWING STEEL PANEL DOOR

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2004-04-09 Cont ID  
Sent By mmclean Date 2004-04-28 Time 15:15 Rev Time 2.00
Received By rmcdouga Date 2004-04-09 Time 10:53 Sent To  
Notes
2004-04-09 00:00:00DENIED
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) SUBMIT A SIGNED AND SEALED COPY OF
 THE SOIL REPORT. SEE 61G15-35 FAC AND
 CITY AMENDMENTS TO FBC 1804.2.2.
  
 3) PROVIDE AT LEAST ONE FULL BATH ROOM
 WITH A DOOR THAT HAS A 29" CLEAR OPENING
 AS REQUIRED BY FBC 11-4.22.2. A 32" WIDE
 DOOR IS NEEDED.
  
 4) THE FOOTPRINT OF THE STRUCTURE ON THE
 SURVEY DOES NOT MATCH THE PLANS. SUBMIT
 A NEW SURVEY.
  
 5) THE HEIGHT ADJUSTMENT COEFFICIENTS
 LISTED IN THE TABLE ON S4 ARE INCORRECT
 FOR EXPOSURE B AT 20',30'AND 50'. PLEASE
 CORRECT.
  
 6) SHEET A5 HAS NOTES THAT REFERENCE
 CODE SECTIONS OF THE FBD. THIS SHOULD BE
 FBC (FLORIDA BUILDING CODE). PLEASE
 CORRECT.
  
 7)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SUBMIT
 PRODUCT APPROVALS FOR THE FOLLOWING:
 - SINGLE HUNG WINDOWS
 - ONE HOUR FIRE RATED GLASS BLOCK
 - FIXED GLASS WINDOWS
 - ARCHED TOP WINDOWS
 - MULLIONS
 - OVERHEAD GARAGE DOORS
 - DOUBLE INSWING ENTRY DOORS
 - EXTERIOR PANEL DOOR
 - SLIDING GLASS DOORS
 - TRUSS CONNECTORS
 - HURRICANE PANELS
  
 8) IN ADDITION TO THE PRODUCT APPROVALS
 FOR THE HURRICANE PANELS, SUBMIT KEY
 PLANS AND INSTALLATION SCHEDULES.
 SPECIFY THE MOUNT TYPE, FASTENER TYPE
 AND FASTENER SPACING.
  
 9) A SEPARATE PERMIT WILL BE REQUIRED
 FOR ROOFING.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-02-25 Cont ID  
Sent By btrobaug Date 2004-04-08 Time 12:54 Rev Time 2.00
Received By rmcdouga Date 2004-02-25 Time 10:06 Sent To  
Notes
2004-02-25 00:00:00DENIED
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) SUBMIT A SIGNED AND SEALED COPY OF
 THE SOIL REPORT. 61G15-35 FAC AND CITY
 AMENDMENTS TO FBC 1804.2.2.
  
 3) THE FLOOR PLAN ON SHEET A2 SPECIFIES
 GLASS BLOCK IN BATH #3 AND THE LEFT SIDE
 ELEVATION ON A5 SHOWS A 2650 SH WINDOW.
 PLEASE CORRECT.
  
 4) THE MINIMUM SIZE FOR ATTIC ACCESS IS
 20"X 36" PER FBC 2309.6. PLEASE REVISE
 DIMENSIONS ON THE PLAN.
  
 5) PROVIDE AT LEAST ONE FULL BATHROOM
 WITH A DOOR THAT HAS A 29" CLEAR OPENING
 AS REQUIRED BY FBC CHAPTER 11. A 32"
 WIDE DOOR IS NEEDED.
  
 6) THE INFORMATION SUBMITTED FOR THE
 GAS BBQ IS NOT ADEQUATE. THE PRODUCT
 LISTING AND SPECS ARE REQUIRED.
  
 7) THE FOOTPRINT OF THE STRUCTURE ON THE
 SURVEY DOES NOT MATCH THE PLANS. SUBMIT
 A REVISED SURVEY.
  
 8) PROVIDE DETAILS (DRAWINGS) OF THE
 CUSTOM WALL BRACKETS (ID# 4,4A & 4B)
 SPECIFIED IN THE CONNECTOR SCHEDULE ON
 S3.
  
 9) SPECIFY THE MAXIMUM UPLIFT CAPACITY
 OF THE STEEL COLUMN ON SHEET S4.
  
 10) SOME OF THE ADJUSTMENT COEFFICIENTS
 FOR EXPOSURE B HAVE INCORRECT VALUES IN
 THE TABLE ON SHEET S4.
  
 11) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SUBMIT
 PRODUCT APPROVALS FOR THE FOLLOWING:
 - ONE HOUR FIRE RATED GLASS BLOCK
 - SINGLE HUNG WINDOWS
 - FIXED GLASS WINDOWS
 - ARCHED TOP WINDOWS
 - MULLIONS
 - OVERHEAD GARAGE DOORS
 - DOUBLE INSWING ENTRY DOORS
 - EXTERIOR PANEL DOOR
 - SLIDING GLASS DOORS
 - TRUSS CONNECTORS
 - HURRICANE PANELS
  
 22) IN ADDITION TO THE PRODUCT APPROVALS
 FOR THE HURRICANE PANELS, SUBMIT KEY
 PLANS AND INSTALLATION SCHEDULES.
 SPECIFY THE MOUNT TYPE, FASTENER TYPE
 AND FASTENER SPACING.
  
 23) A SEPARATE PERMIT WILL BE REQUIRED
 FOR ROOFING.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-01-20 Cont ID  
Sent By pkrauss Date 2004-02-23 Time 11:31 Rev Time 3.00
Received By rmcdouga Date 2004-01-20 Time 11:30 Sent To  
Notes
2004-01-20 00:00:00DENIED
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) SUBMIT A SIGNED AND SEALED COPY OF
 THE SOIL REPORT. CITY AMENDMENTS TO FBC
 1804.2.2.
  
 4) ONE HOUR FIRE RATED GLASS BLOCK IS
 REQUIRED WITHIN 3 FEET OF THE PROPERTY
 LINE PER FBC TABLE 600. SPECIFY THIS ON
 THE PLANS.
  
 5) GLASS BLOCK WITHIN THREE FEET OF A
 TUB OR SHOWER ARE REQUIRED TO HAVE A
 MINIMUM UNIFORM FACE THICKNESS OF 0.25"
 PER FBC 2405.2. SPECIFY ON THE PLANS.
  
 6) WINDOWS WITHIN THREE FEET OF A TUB OR
 SHOWER ARE REQUIRED TO HAVE SAFETY
 GLAZING PER FBC 2405.2. SPECIFY ON PLANS
 THAT THE WINDOWS IN MASTER BATH ARE
 TEMPERED.
  
 7) SPECIFY THE SIZE OF THE GLASS BLOCK
 OPENINGS.
  
 8) SPECIFY THE TYPE AND SIZES OF THE
 EGRESS WINDOWS IN THE GUEST BEDROOM.
  
 9) INDICATE THE SIZES OF ALL OF THE
 TRANSOM AND FIXED GLASS WINDOWS.
  
 10) SPECIFY THE SIZE OF THE ATTIC ACCESS
 ON THE PLANS. SEE FBC 2309.6.
  
 11) PROVIDE AT LEAST ONE FULL BATH WITH
 A DOOR THAT HAS A 29" CLEAR OPENING AS
 REQUIRED BY FBC CHAPTER 11.
  
 12) SUBMIT MANUFACTURER'S SPECS. AND
 UL LISTING INFORMATION FOR THE GAS BBQ.
  
 13) THE FOOT PRINT OF THE STRUCTURE ON
 THE SURVEY DOES NOT MATCH THE PLANS.
 SUBMIT CORRECTED SURVEY.
  
 14) THE ROOF SHEATHING IS REQUIRED TO BE
 NAILED AT 4"OC AT THE EDGES AND 6"OC
 INTERMEDIATE IN ZONE 3 PER CITY AMEND.
 TO FBC TABLE 2306.1. THE CORNERS OF HIP
 ROOFS ARE ZONE 3. PLEASE REVISE THE NOTE
 ON A6.
  
 15) SPECIFY THE FOUNDATION FOR THE 5'
 WALL AT THE GARDEN COURT ON S1.
  
 16) PROVIDE DETAILS OF THE CUSTOM WALL
 BRACKETS SPECIFIED IN THE CONNECTOR
 SCHEDULE ON S3.
  
 17)1609.4.3 LOAD REDUCTION.
 WHEN STRUCTURAL EFFECTS DUE TO TWO OR
 MORE LOADS IN COMBINATION WITH DEAD LOAD
 ARE INVESTIGATED IN LOAD COMBINATIONS OF
 1609.4.1 OR 1609.4.2, THE COMBINED
 EFFECTS DUE TO THE TWO OR LOADS MULTI-
 PLIED BY 0.75 PLUS EFFECTS DUE TO DEAD
 LOADS SHALL NOT BE LESS THAN THE EFFECTS
 FROM THE LOAD COMBINATION OF THE DEAD
 LOAD PLUS THE LOAD PRODUCING THE LARGEST
 EFFECTS. INCREASEIN ALLOWABLE STRESS SPE
 CIFIED IN THE MATERIALS SECTIONS OF THIS
 CODE OR A REFRENCED STANDARD SHALL NOT
 BE USED WITH THESE LOAD COMBINATIONS
 EXCEPT THAT A DURATION OF LOAD INCREASE
 SHALL BE PERMITTED IN ACCORDANCE WITH
 CHAPTER 23. REVISE THE CONNECTOR
 SCHEDULE ON S3 ACCORDINGLY. SEE NOTES ON
 THE PLAN.
  
 18) UPDATE THE USP HC 10/10-2 WHICH ARE
 NO LONGER LISTED IN THE USP CATALOG.
  
 19) SPECIFY THE WELD TYPES AND UPLIFT
 CAPACITIES FOR THE STEEL COLUMNS ON S4.
  
 20) CORRECT THE HEIGHT AND EXPOSURE
 COEFFICIENT VALUES IN TABLE 1606.2D ON
 S4. SEE MARKS ON THE PLAN.
  
 21) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SUBMIT
 PRODUCT APPROVALS FOR THE FOLLOWING:
 - ONE HOUR FIRE RATED GLASS BLOCK
 - SINGLE HUNG WINDOWS
 - FIXED GLASS WINDOWS
 - ARCHED TOP WINDOWS
 - MULLIONS
 - OVERHEAD GARAGE DOORS
 - DOUBLE INSWING ENTRY DOORS
 - PANEL DOORS
 - SLIDING GLASS DOORS
 - TRUSS CONNECTORS
 - STORM PANELS
  
 22) IN ADDITION TO THE PRODUCT APPROVALS
 FOR THE STORM PANELS, SUBMIT KEY PLANS
 AND AN INSTALLATION SCHEDULE. SPECIFY
 THE MOUNT TYPE AND FASTNER TYPE &
 SPACINGS THAT WILL BE USED. THIS INFO
 IS REQUIRED PRIOR TO ISSUANCE OF THIS
 PERMIT OR A SEPARATE PERMIT AND FEES
 WILL BE REQUIRED.
  
 NOTE: NO BUTT GLASS OR STOREFRONTS ARE
 INDICATED ON THE PLANS. PLEASE REMOVE
 THESE PRODUCT APPROVALS FORM SUBMITTAL.
  
 23) THERE WAS NO ROOFING CONTRACTOR
 SIGNED ON THE PERMIT APPLICATION WHEN IT
 WAS SUBMITTED. THEREFORE, A SEPARATE
 PERMIT AND FEES WILL BE REQUIRED.
 PRODUCT APPROVALS WILL BE REQUIRED AT
 THAT TIME. PLEASE REMOVE THE PRODUCT
 APPROVALS FOR THE ROOF TILES FROM THIS
 SUBMITTAL.
  
 IN ORDER TO AID PLAN REVIEW TIME, PLEASE
 SUBMIT OLD PLAN SHEETS THAT HAVE BEEN
 REMOVED AND REPLACED BY REVISED SHEETS.
 IF YOU HAVE QUESTIONS PLEASE CALL:
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop E ELECTRICAL
Rev No 9 Status P Date 2005-06-21 Cont ID  
Sent By btrobaug Date 2005-06-21 Time 10:17 Rev Time 0.50
Received By btrobaug Date 2005-06-21 Time 10:10 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 8 Status P Date 2005-06-08 Cont ID  
Sent By btrobaug Date 2005-06-08 Time 17:36 Rev Time 0.50
Received By btrobaug Date 2005-06-08 Time 17:19 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 7 Status F Date 2005-06-07 Cont ID  
Sent By btrobaug Date 2005-06-07 Time 14:23 Rev Time 0.50
Received By btrobaug Date 2005-06-07 Time 14:16 Sent To PC
Notes
2005-06-07 00:00:00PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} SMOKE DETECTORS ARE REQUIRED PER
 905.2.2 FBC, 8-1.4.1.6.2 NFPA-72.
  
 2} FRONT AND REAR GFI RECEPTACLES ARE
 REQUIRED PER 210.8(A)(3, 210.52(E).
  
 3} THE DISCONNECTS FOFR THE CONDENSING
 UNITS MOVED FROM THE REVIEWED PLAN AND
 ARE NOW IN VIOLATION OF 110.26.
  
 4} MICROWAVE IN LOAD CALCS NOT ON PANEL
 SCHEDULE. PLEASE CORRELATE.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2005-05-11 Cont ID  
Sent By dpalmer Date 2005-05-11 Time 12:03 Rev Time 0.50
Received By dpalmer Date 2005-05-11 Time 12:03 Sent To  
Notes
2005-05-11 00:00:00**** REVISIONUNSAT *****
  
 1)NOTE: PLEASE SEE 210.52C1 AND 210.52C3
 FOR MISSING GFI RECEPTS ALONG KITCHEN
 COUNTERSPACE AND PENINSULAR.
 PLEASE ALSO SEE 210.8A6
  
 2)NOTE: PLEASE SEE RECEPTS SHOWN W/IN
 6'IF WET BAR SINK REQUIRED TO BE GFI.
 210.8A3
  
 3)NOTE: PLEASE SEE 210.52 FOR MISSING
 RECEPT ALONG WALL SPACE. PLEASE SEE IF
 THIS AREA IS CONSIDERED A "HALLWAY" THEN
 RECEPT WILL NOT BE REQUIRED.
  
 4)NOTE: PLEASE CORRELATE LOAD
 CALCULATIONS AND PANEL SCHEDULES.
 PLEASE SEE MICROWAVE SHOWN ON LOAD
 CALCS, BUT NOT ON PANEL SCHEDULE.
 PLEASE SEE LOAD/AMPS FOR FRIG AND
 DISHWASHER BOTH SHOWN AT 19A'S??PLEASE
 SEE MAX LOAD ON A 20A BRANCH CIRCUIT IS
 16A'SHOWEVER THESE DO NOT CORRELATE WITH
 LOAD CALCULATIONS WHICH SHOWS A MUCH
 LESSER LOAD.
 240.24,310.16,210.11 ETC.
  
 5)NOTE: PLEASE SEE CONNECTED AMPS FOR
 DRYER IS SHOWN AT 40A'S, HOWEVER CIRCUIT
 SHOWN IS 30A'S AND KW LOAD ON LOAD
 CALCS, ONLY INDICATE 5KW??
 PLEASE CORRLEATE.
 240,215.5,310.16 ETC.
  
 6 )NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
  
 7)NOTE: PLEASE VERIFY POOL PUMP MOTOR
 SIZE. PANEL SCHEDULE SHOWS #8AWG, 40A
 OCP FOR 1HP MOTOR??
 PLEASE ALSO CORRELATE WITH LOAD CALCS.
  
 8)NOTE: PLEASE INCLUDE LOAD ON SUB PANEL
 "B". 215.5 220
  
 PLEASE SEE ONE SET OF PLANS HAS ABOVE
 ITEMS REDLINED AT AREAS OF NOTES.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2004-04-28 Cont ID  
Sent By dpalmer Date 2004-04-28 Time 16:25 Rev Time 2.00
Received By dpalmer Date 2004-04-28 Time 16:24 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2004-04-21 Cont ID  
Sent By dpalmer Date 2004-04-21 Time 18:19 Rev Time 1.50
Received By dpalmer Date 2004-04-21 Time 17:59 Sent To P
Notes
2004-04-21 00:00:00*************UNSAT 4TH REVIEW ******
  
 1)NOTE: PLEASE SEE 4X FEE WAS DUE ON
 LAST PLAN REVIEW DUE TO THREE REVIEWS
 WITH SAME COMMENTS. NOTICE WAS GIVEN IN
 NOTES ON 2ND AND 3RD REVIEW FOR THIS
 UNDER FS 553.80(2)(B). A COPY OF THE FS
 WAS ALSO ATTACHED TO NOTES.
 PLEASE SEE BZ #240163 IN THE AMOUNT OF
 $4032.00 WAS DUE BEFORE RESUBMITTING
 ON 4/20. BZ IS NOW ATTACHED.
 PLEASE ALSO SEE NOTES BELOW THAT HAVE
 STILL HAVE NOT BEEN ADDRESSED FROM
 FIRST 3 REVIEWS AND NOW THE 4TH REVIEW.
 PER FS 553.80(2)(B), A 4X FEE IS ACCESS-
 ED FOR EACH ONE REVIEW IF ANY OF THE
 SAME COMMENTS ARE NOT ADDRESSED FOR CODE
 COMPLIANCE.
 PLEASE SEE ADDITIONAL BZ ATTACHED FOR
 THIS 4XFEE REVIEW.BZ#240164 WHICH MUST
 BE PAID BEFORE SUBMITTING PLANS.
 PLANS WILL NOT BE PERMITTED TO BE RE-
 -SUBBED UNTIL FEES ARE PAID. PER FS.
 PLEASE NOTE: IF PLANS COME BACK FOR 5TH
 REVIEW AND ANY OF THE SAME COMMENTS FROM
 FIRST FOUR REVIEWS ARE NOT ADDRESSED.
 WE WILL BE REQ'D TO TURN PLANS INTO
 DBPR/ BOARD OF ARCH'S FOR REVIEW PER
 BLDG OFFICIAL.
 ONE SET OF EACH PLAN IS NOW BEING
 RETAINED FOR FILE.
 PLEASE SEE COMMENTS BELOW FROM PREVIOUS
 REVIEW THAT STILL NEED TO BE ADDRESSED.
  
 1)NOTE: PLEASE SEE RISER, STILL SHOWS
 AN EQUIPMENT GROUNDING CONDUCTOR BEING
 INSTALLED BETWEEN METER AND FIRST MEANS
 OF DISCONNECT. PLEASE REMOVE PER 250.6
 250.24.
  
 2)NOTE: PLEASE SEE RECEPT SPACING ON
 KITCHEN COUNTERSPACE PER 210.52C1
  
 3)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 4)NOTE: PLEASE SEE OCP SHOWN FOR OVENS/
 COOKTOP ETC. STILL BEING SHOWN AS 1-POLE
 BRKRS. PLEASE SEE OTHER 220V UNITS.
  
 5)NOTE:PLEASE SHOW LOAD CALCULATIONS
 FOR A RESIDENTIAL DWELLING AS SETFORTH
 IN 2002 NEC. 220. 215.5
  
 6)NOTE: PLEASE INCLUDE REQ'D LICENSE #
 ON TITLE BLOCK. REQ'D PER FAC 61G1-16.-
 004. PLEASE SEE FS 481.219 FOR REQ'D
 CERTIFICATE OF AUTHIRIZATION #.
 THIS IS REQ'D
  
 7)NOTE: PLEASE SHOW GROUNDING ELECTRODE
 SYSTEM PER 250.50, SIZE PER 250.66
  
 NEW COMMENT:
 PLANS HAVE HAD CHANGES TO THEM TO MEET
 NEC 210.12.HOWEVER, ALL THESE ARTS
 ARE REFERENCING THE FBC? PLEASE CORRECT.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL. MY # AND E-MAIL ADDRESS
 WAS PRINTED AND GIVEN ON PREVIOUS
 REVIEWS AS WELL AS BILL TROBAUGH.
 AS OF TODAY I HAVE NOT RECEIVED ANY
 CALLS FOR ANY QUESTIONS ON THE ABOVE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2004-04-08 Cont ID  
Sent By csiegber Date 2004-04-20 Time 12:34 Rev Time 0.75
Received By btrobaug Date 2004-04-08 Time 12:18 Sent To B
Notes
2004-04-08 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.ALSO NOTE THAT THESE COMMENTS
 ARE FROM THE FIRST TWO REVIEWS AND WERE
 NOT ADDRESSED. THE DESIGN PROFESSIONAL
 IS THEREFORE RESPONSIBLE FOR THE FEES
 IMPOSSED UNDER FS. 553.80(2)(B),
 ATTACHED.
  
 1} THE EQUIPMENT GROUNDING CONDUCTOR IN
 THE FEEDER TO THE FIRST MEANS OF
 DISCONNECT IS IN VIOLATION OF 250.24 &
 250.6.
  
 2} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING
 INSTALL-ED. MAINS/BRKRS AND PANELS ARE
 ALL TO BERATED FOR THE AVAILABLE FAULT
 CURRENT PER110.9,110.10 & 215.5.
  
 3} THERE ARE STILL RECEPTACLES MISSING
 FROM THE KITCHEN COUNTERTOPS PER
 210.52(C)(1).
  
 4} NOTE #9 INDICATES MINIMUM WIRE SIZE
 @ #12 AWG, THE PANEL SCHEDULES LISTS #14
 BEING USED ON SEVERAL CIRCUITS. PLEASE
 CORRELATE.
  
 5} THERE IS NO RECEPTACLE AT THE FRONT
 OF THE RESIDENCE, VIOLATION OF
 210.52(E).
  
 6} THE GROUNDING ELECTRODE SYSTEM MUST
 COMPLY WITH 250.50 ALL THAT APPLY,
 INCLUDE BUILDING STEEL.
  
 7} SHOW THE LOCATION OF THE SERVICE
 EQUIPMENT ON THE PLAN, INCLUDING METER
 AND MAIN DISCONNECT.
  
 8} VERIFY THE OCP FOR THE COOKTOP AND
 WALL OVEN. SEE NOTE #9, COMMENTS.
  
 9} SHOW LOADS IN CALCLATION PER ARTICLE
 220 NEC. INDICATE METHOD (ARTICLE) USED.
  
 10} RECEPTACLES ARE STILL MISSING IN THE
 BREAKFAST ROOM AND BEDROOM #3 IN
 VIOLATION OF 210.52(A)(2).
  
 11} THERE ARE 2 ROOMS DESIGNATED BEDROOM
 #3. PLEASE CORRELATE WITH ARCHITECTURAL
 PLANS.
  
 12} THE RECEPTALE IN THE BAR MUST BE GFI
 PROTECTED PER 210.8(A)(7).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-02-13 Cont ID  
Sent By alange Date 2004-03-30 Time 14:42 Rev Time 1.00
Received By dpalmer Date 2004-02-13 Time 15:30 Sent To P
Notes
2004-02-13 00:00:00************* UNSAT *****************
  
 1)NOTE: PLEASE SEE ALL NOTES FROM FIRST
 REVIEW. PLEASEE SEE THAT NO NOTES WERE
 ADDRESSED FOR NOTES???
 PLEASE SEE COPY OF FS 553.80(2)(B) WITH
 RESPECT TO DESIGN PROFESSIONAL.
 PLEASE ADDRESS ALL COMMENTS.
  
 2)NOTE: PLEASE SEE FAC 61G1-16.004,
 TITLE BLOCK IS REQ'D TO INCLUDE ALL
 INFORMATION SET FORTH.
 PER FS 481
 PLEASE SEE THAT PLANS ARE REQ'D TO BE
 SIGNED WITH A COMPLETE SIGNATURE AS
 REQ'D UNDER FS 481.221. PER FS, INITIALS
 ARE NOT PERMITTED. PLEASE SEE SOME
 SHEETS ARE SIGNED WITH COMPLETE SIGNAT-
 -URE AS REQ'D AND SOME ARETHE INITIALS
 T.E.D. PLEASE KNOW, WE HAVE BEEN
 NOTIFIED BY THE STATE THIS IS REQ'D.
 PLEASE SEE THE ABOVE IS REQ'D FOR ALL
 SHEETS WEATHER OR NOT COMMENT IS MADE
 BY OTHER REVIEWERS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-12-30 Cont ID  
Sent By csiegber Date 2004-02-11 Time 14:43 Rev Time 1.00
Received By dpalmer Date 2003-12-30 Time 14:00 Sent To M
Notes
2003-12-30 00:00:00************ UNSAT *****************
  
 1)NOTE: PLEASE SEE THAT AN EQUIPMENT
 GROUNDING CONDUCTOR IS NOT INSTALLED
 BETWEEN METER AND FIRST MEANS OF DISC.
 250.24. PLEASE REMOVE.
  
 2)NOTE: PLEASE SUBMIT AIC RATING FOR ALL
 SERVICE EQUIPMENT BEING INSTALLED.
 MAINS/PANELS AND BRKRS ARE ALL TO BE
 RATED FOR THE AVAILABLE FUALT CURRENT.
 PER 110.9/ 215.5
 IT IS NOTED THAT AIC RATING IS NOTED
 FOR BRANCH BRKRS IN PANELS.
  
 3)NOTE: PLEASE SEE MISSING RECEPTS FOR
 KITCHEN COUNTERSPACE PER 210.52C1
  
 4)NOTE: PLEASE SHOW LOAD CALCULATIONS
 WITH MIN LOADS REQ'D AS SETFORTH IN ART
 220 OF THE NEC.
  
 5)NOTE: PLEASE SEE NOTE #9, MENTIONS
 MIN AWG TO BE #12, PANEL SCHEDULE DOES
 NOT CORRELATE WITH THIS. PLEASE
 CORRELATE.
  
 6)NOTE: PLEASE LIST ALL THE REQ'D ARC
 FAULT PROTECTED CIRCUITS PER 210.12
 2002 NEC.
  
 7)NOTE: PLEASE CORRELATE FEEDERS FOR
 SUB PANEL 'B'. RISER SHOWS #3/0'S AND
 PANEL "A" SHOWS #3.
  
 8)NOTE: PLEASE SEE 210.52E FOR FRONT
 AND REAR RECEPTS. MISSING FRONT.
  
 9)NOTE: PLEASE INCLUDE FOOTER STEEL,
 COLD WATER PER 250.50 ON RISER DIAGRAM
 FOR GROUNDING ELECTRODE SYSTEM.
  
 10)NOTE: PLEASE SEE MISSING RECEPT ON
 2' OF WALL MASTER BR. 210.52
  
 11)NOTE: PLEASE SHOW SERVICE ON PLANS/
 LOCATION OF METER AND MAIN.
  
 12)NOTE: PLEASE VERIFY OCP FOR BOTH
 COOKTOP AND WALL OVEN. SHOWN AS 60A??
 PLEASE SEE THAT THIS IS NOT A COMMON
 SIZE, PLEASE VERIFY.
  
 13)NOTE: PLEASE SEE 220.16B FOR MIN KVA
 OF WASHER/LAUNDRY CIRCUIT. SHOWN WITH
 LOAD @ 10A'S??. PLEASE SEE NOTE #4
  
 14)NOTE: PLEASE SEE MISSING RECEPTS
 IN BR#3 AND BRKFST AREA PER 210.52
 PLEASE ALSO SEE RECEPT SPACING IN DINING
 RM AND ANY OTHER AREAS. DINING RM HAS
 RECEPT IN CENTER OF DOORWAY (MISPRINT).
  
 15)NOTE: PLEASE SEE THAT THERE ARE TWO
 ROOMS SHOWN AS BEDROOM #3. PLEASE ADJUST
  
 16)NOTE: PLEASE SEE 210.8 FOR GFI
 PROETCTION REQ'D IN BAR AREA. LOCAL
 AMENDMENTS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2005-06-16 Cont ID  
Sent By shill Date 2005-06-16 Time 14:04 Rev Time 0.00
Received By shill Date 2005-06-16 Time 14:04 Sent To E
Notes
2005-06-16 00:00:00TO BT DESK

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2005-06-08 Cont ID  
Sent By mjacobs Date 2005-06-08 Time 16:49 Rev Time 0.00
Received By mjacobs Date 2005-06-08 Time 16:49 Sent To E
Notes
2005-06-08 00:00:00TO 'BT' DESK./REV.

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2005-05-25 Cont ID  
Sent By adarroug Date 2005-05-25 Time 14:03 Rev Time 0.00
Received By adarroug Date 2005-05-25 Time 14:03 Sent To E
Notes
2005-05-25 00:00:00TO "BTROBAUG" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-05-09 Cont ID  
Sent By adarroug Date 2005-05-09 Time 15:36 Rev Time 0.00
Received By adarroug Date 2005-05-09 Time 15:36 Sent To E
Notes
2005-05-09 00:00:00TO "DPALMER" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-02-07 Cont ID  
Sent By adarroug Date 2005-02-07 Time 09:07 Rev Time 0.00
Received By adarroug Date 2005-02-07 Time 09:07 Sent To B
Notes
2005-02-07 00:00:00TO R.MCDOUGA DESK

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-06-11 Cont ID  
Sent By csiegber Date 2004-06-11 Time 10:49 Rev Time 0.00
Received By csiegber Date 2004-06-11 Time 10:48 Sent To B
Notes
2004-06-11 00:00:00TO RM DESK/REV/INSULATION

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-04-20 Cont ID  
Sent By csiegber Date 2004-04-20 Time 12:34 Rev Time 0.00
Received By csiegber Date 2004-04-20 Time 12:34 Sent To E
Notes
2004-04-20 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-03-30 Cont ID  
Sent By alange Date 2004-03-30 Time 14:42 Rev Time 0.00
Received By alange Date 2004-03-30 Time 14:42 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-02-11 Cont ID  
Sent By csiegber Date 2004-02-11 Time 14:43 Rev Time 0.00
Received By csiegber Date 2004-02-11 Time 14:43 Sent To E
Notes
2004-02-11 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-01-20 Cont ID  
Sent By mmclean Date 2003-12-19 Time 15:06 Rev Time 0.00
Received By rmcdouga Date 2003-12-17 Time 15:49 Sent To  
Notes
2003-12-22 00:00:00TO SFD RACK/E
2003-12-17 00:00:00TO Z

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-02-23 Cont ID  
Sent By jleech Date 2004-02-18 Time 09:23 Rev Time 0.33
Received By pkrauss Date 2004-02-23 Time 11:02 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-12-30 Cont ID  
Sent By dpalmer Date 2003-12-30 Time 14:38 Rev Time 0.75
Received By hmoser Date 2003-12-30 Time 17:35 Sent To P
Notes
2003-12-30 00:00:00PASS PRIVISO
 NEED RETURNAIR IN DEN/STUDY
 PLAN REVIEW BY HAROLD MOSER
 (561)805-6732

Review Stop P PLUMBING
Rev No 4 Status P Date 2005-06-25 Cont ID  
Sent By pschmitz Date 2005-06-25 Time 10:46 Rev Time 0.00
Received By pschmitz Date 2005-06-25 Time 10:45 Sent To PC
Notes
2005-06-25 00:00:00REVISION:
 ADDED BIDET TO ISOMETRIC.PES

Review Stop P PLUMBING
Rev No 3 Status P Date 2004-04-28 Cont ID  
Sent By btrobaug Date 2005-06-08 Time 10:38 Rev Time 0.00
Received By rmcdouga Date 2004-04-28 Time 15:31 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-02-18 Cont ID  
Sent By dpalmer Date 2004-04-21 Time 18:32 Rev Time 0.50
Received By jleech Date 2004-02-18 Time 09:23 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2004-01-03 Cont ID  
Sent By hmoser Date 2003-12-30 Time 17:36 Rev Time 0.25
Received By jleech Date 2004-01-03 Time 06:05 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2004-04-28 Cont ID  
Sent By mmclean Date 2004-04-28 Time 15:15 Rev Time 0.00
Received By mmclean Date 2004-04-28 Time 15:15 Sent To B
Notes
2004-04-28 00:00:00APPROVED REVISION.GIVEN TO ROBERT M

Review Stop Z ZONING
Rev No 1 Status P Date 2003-12-19 Cont ID  
Sent By mmclean Date 2003-12-19 Time 15:06 Rev Time 0.00
Received By mmclean Date 2003-12-19 Time 15:06 Sent To I
Notes
***NONE***