Plan Review Details - Permit 03120934
Plan Review Stops For Permit 03120934
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2004-06-18 Cont ID  
Sent By jwitmer Date 2004-06-18 Time 12:43 Rev Time 1.50
Received By jwitmer Date 2004-06-18 Time 12:43 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2004-06-03 Cont ID  
Sent By csiegber Date 2004-06-16 Time 12:06 Rev Time 0.55
Received By jwitmer Date 2004-06-03 Time 11:08 Sent To PC
Notes
2004-06-03 00:00:00PLANS CODE COMPLIANT, CONTRACTOR TO PICK
 UP PLANS, SUBMIT TO PB COUNTY FOR IMPACT
 FEE ASSESSMENT.J WITMER

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2004-05-06 Cont ID  
Sent By jwitmer Date 2004-05-06 Time 15:49 Rev Time 3.50
Received By jwitmer Date 2004-05-06 Time 15:49 Sent To  
Notes
2004-05-06 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03120934
 ADD: 2275 PALM BEACH KAKES BLVD
 CONT: HALLMARK BUILDERS
 TEL: (561)512-5517
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 NOTE: TABLE 308.2 B ALLOWS 120 GAL OF
 COMBINATION OF IA, IIB, IC FOTNOTE (2)
 CONTAINING NOT MORE THAN THE EXEMPT
 AMOUNTS OF FLAMMABLE LIQUIDS.
  
 NOTE: SPRAY BOOTH TO BE UNDER SEPERATE
 PERMIT AS PER DESIGN PROFESSIONAL
 RESPONCE. PULL INFORMATION FROM PLANS.
 SPRAY BOOTH WILL AT TIME OF PERMITTING
 REQUIRE FIRE SPRINKLER INFORMATION.
  
 1) ARCH RESPONCE TO PULL FOAM BANDS TO
 BE CEMENT BANDS, ADDITIONAL INFO: HOW
 WILL THEY BE ATTACHED TO THE WALL.
  
 2) FROM PREVIOUS REVIEW (5C & D):
 THE SOUND ADVISE TOWER IS ABOVE 35'
 MEAN ROOF HEIGHT, ENGINEER TO PROVIDE
 NAILING PATTERN FOR PLYWOOD ROOF SHEATH-
 ING. ZONES 1,2 & 3. WHEN THE ROOFING
 PRODUCTS ARE SUBMITTED FOR THE TOWER
 REMEMBER THAT THERE IS HIGHER PRESSURES
 TABLE 1606.2D 35'-40'= 1.09 MULTIPLIER.
  
 3) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) STORM SHUTTERS
 B) EXTERIOR SWING DOORS IF SOLID 026/027
 C)OVERHEAD GARAGE DOORS
 D) ALL ROOFING ASSEMBLIES
 E) TRUSS ANCHORS
  
 *********IMPORTANT**********
 4)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 5) SINCE STORM SHUTTERS WILL BE USED
 FL BLD CODE 2001 SECTION 103.6,
 1606.1.4, 1707.4 & 3401.7.2.4.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING
 OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL PRES-
 SURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
  
 6) PLANS INDICATE THAT THE FLAT ROOF
 WILL BE 90# MODIFIED BITUMEN, BUT THE
 PRODUCT TESTING REPORT IS FOR SINGLE
 PLY ROOFING SYSTEM? WHICH IS IT?
  
 7) MISSING THE ROOFING REPORT FOR THE
 CONCRETE ROOF TILE? NOTE HIGHER PRES-
 SURES WILL APPLY TO THE SOUND ADVISE TOW
 ER.
  
 8) THE NEW DRAWINGS ARE MISSING PAGES
 FOUND IN THE OLD PLANS.
  
 9) BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 10) FL S S 481.219 CERTIFICATE OF PART-
 NERSHIP AND CORPORATION(3) FOR THE PUR-
 POSES OF THIS SECTION, A CERTIFICATE OF
 AUTHORIZATION SHALL BE REQUIRED FOR A
 CORPORATION, PARTNERSHIP, OR PERSON
 OPERATING UNDER A FICTITIOUS NAME.
 WHEN THERE IS NO CERTIFICATE OF AUT
 HORIZATION, ARCHITECTS MUST USE ONLY
 THEIR NAME ON THE TITLE BLOCK, NOT THE
 CORPORATION.
  
 11) TUMAY CONSULTING ENGINEERING, INC
 RULE 61G15-23.002 WHEN A BUSINESS IS
 INCORPARATED, PARTNERS OR FICTITIOUS
 NAME IS USED THE CERTIFICATE OF AUTHOR-
 IZATION NUMBER MUST ALSO BE IN THE
 TITLE BLOCK.
  
 12) DESIGN ENGINEERING & SUPPLY, DPBR &
 ENGINEERING BOARD HAVE NO CERTIFICATE OF
 AUTHORIZATION NOR"FICTITIOUS NAME" ON
 FILE. 61G15-23.002,P.E. TO PUT THEIR
 NAME AND P.E. NUMBER IN TITLE BLOCK ONLY
  
 13)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-03-04 Cont ID  
Sent By jwitmer Date 2004-03-04 Time 13:02 Rev Time 4.33
Received By jwitmer Date   Time   Sent To  
Notes
2004-03-04 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03120934
 ADD: 2275 PALM BEACH LAKES BLVD
 CONT: HALLMARK BUILDERS
 TEL: (561)512-5517
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 2ND REVIEW
 ACTION: DENIED
  
 1) QUESTION# 1 FROM 1ST PLAN REVIEW:
 THE TYPES OF COMBUSTIBLE LIQUIDS PRO-
 VIDED FROM THE FIRST PLAN REVIEW MAY
 HAVE SOME DESCREPANCIES. PROVIDE THE MAN
 UFACTURES FLASH POINT AND BOILING POINTS
 FOR THE LIST PROVIDED. EXAMPLE CLEARCOAT
 LOOKS LIKE IT MAY BE A CLASS II WITHA
 BOILING POINT OF 104.INCLUDE THE BREAK
 DOWN FOR LACQUERS AND LACQUER THINNERS.
 ALSO PROVIDE THE MSDS SHEETS. ON MANY
 MSDS SHEETS THEY WILL REQUIRE A EYE WASH
  
 2) COMMENT# 2 FROM 1ST REVIEW, 407.1.3.5
 SPRAY BOOTHS SHALL BE PROTECTED BY AN
 AUTOMATIC SUPRESSION SYSTEM. A NOTE ON
 THE DRAWINGS DOESN'T MEET THE REQUIRE-
 MENTS OF THE CODE.
 104.2.1 W.P.B. ADMINISTRATIVE CODE
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR
 OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES.
 SUCH INFORMATION SHALL BE SPECIFIC
 AND THE TECHNICAL CODES "SHALL NOT BE
 CITED AS A WHOLE OR IN PART, NOR THE
 TERM "LEGAL" OR ITS RQUIVALENT BE USED
 AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION".
  
 3) ONCE WE RECEIVE THE FLASH POINT AND
 BOILING POINT OF THE LIQUIDS TO BE
 STORED AND THE METHOD OF STORAGE (IF
 RATED FIRE CABINETS WILL BE REQUIRED)
 IF REQUIRED,SUBMIT CUT SHEETS, THEN THE
 OCCUPANCY WILL BE ASSIGNED.
 EXAMPLE; CLEARCOAT ON THE ENTERNET THIS
 LIQUID IS INDICATED AS A CLASS II LIQUID
 WITH A FLASH POINT OF 105.
 THE SECOND CONCERN IS TO PROVIDE
 MSDS SHEETS FOR THESE CHEMICALS, SOME
 CHEMICALS REQUIRE A EYE WASH FOR 15 MIN.
  
 4) THE NOTE INDICATING THE 2 HR RATING
 IS OK,BUT PROVIDE THE GA FILE DETAIL ON
 THE PLAN FOR THE INSPECTOR TO BE ABLE TO
 INSPECT BY.
  
 5)NOTE 5 FROM 1ST REVIEW, HAS BEEN
 PARTIALLY IGNORED.
 5A) THE FOAM TRIM CAN NOT BE USED IN THE
 FIRE DISTRICT. F102.7 ARCHITECTURAL TRIM
 ON BUILDINGS IN THE FIRE DISTRICT SHALL
 BE CONSTRUCTED OF NON-COMBUSTIBLE
 MATERIALS OR FIRE RETARDANT TREATED
 WOOD.
 5B) THE USE OF PLYWOOD FOR WALLS HAS
 BEEN DELETED FROM SOME PAGES,S3,S5 STILL
 HAVEDETAILS WITH THE USE OF WOOD AS WELL
 AS THE 3 MEMBER GIRDER IS A VERTICAL
 WALL SECTION!!!!!!
 5C) THE USE OF PLYWOOD HAS BEEN REMOVED
 FROM THE EXTERIOR TOWER WALL DIAPHRAM
 WHAT MATERIAL WILL MAKE THE WALL
 DIAPHRAM?
 5D) PLANS INDICATE ROOF SHEATHING ABOVE
 THE 35'-0" ELEVATION, ENG TO PROVIDE
 ATTACHMENT AND SPACING, REMEMBER ROOF
 ZONE #3 EDGE ZONES, NEGATIVE PRESSURES.
  
 7) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) GLAZED SWING DOORS
 B) GLAZED SWING DOORS W/ SIDELIGHTS
 C) GLAZED SWING DOORS W/ SIDELIGHTS &
 TRANSOMS
 D) MULLIONS, VERTICAL & HORIZONTAL
 E)WINDOWS
 F) STORM SHUTTERS IF IMPACT GLAZING IS
 NOT USED.
 G) LOUVERS
 H) EFIS- FOAM MOLDINGS
 I) ROOF ASSEMBLIES
 J) TRUSS ANCHORS
  
 8) ***********IMPORTANT***************
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 9) 1707.4.5.1 MULLIONS OCCURRING
 BETWEEN INDIVIDUAL WINDOW AND GLASS
 DOOR ASSEMBLIES. TESTING REPORTS ARE
 REQUIRED BY AN APPROVED TESTING
 LABORATORY OR BE ENGINEERED.
 PROVIDE PRODUCT TESTING REPORTS!!!!!!!!!
  
 10) 1707.4.5.2 MULLIONS SHALL BE DESIGN-
 ED TO TRANSFER THE DESIGN PRESSURE LOADS
 APPLIED BY THE WINDOW OR DOOR ASSEMBLIES
 TO THE ROUGH OPENING SUBTRATE.
 PROVIDE PRODUCT TESTING REPORTS!!!!!!!
  
 11) COMMENT 16 FROM 1ST REVIEW: RETURN
 COMMENT SHEET INDICATES BOTTOM CHORD
 LIVE LOAD ADDED TO PLANS NO CLOUD OR
 DELTA INDICATING CHANGE? WHERE?
  
 12) PLANS INDICATE THE USE OF SEMCO
 STRAPS, REMOVE FROM PLANS!!!!! OUT OF
 BUSSINSS SINCE 1999! NO STATE APPROVALS
 ARE AVAILABLE.
 TRUSS ANCHOR SCHEDULE REMOVE THE WORD
 "SUBSTITUTE"
 104.2.1 W.P.B. ADMINISTRATIVE CODE
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR
 OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES.
 SUCH INFORMATION SHALL BE SPECIFIC
 AND THE TECHNICAL CODES "SHALL NOT BE
 CITED AS A WHOLE OR IN PART, NOR THE
 TERM "LEGAL" OR ITS EQUIVALENT BE USED
 AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION".
  
 13) ON THE SOUND ADVISE BUILDING HOW
 WILL THE NICHE BE ACHIEVED?
  
 14) ROOFS REQUIRE DRAINAGE, PROVIDE
 GUTTER SYSTEM THAT COMPLIES WITH SECTION
 1503.4.3 SIZING & DISCHARGE.
  
 15) 1503.4.4 PROTECTION AGAINST DECAY &
 TERMITES. CONDENSATE LINES & ROOF DOWN
 SPOUTS SHALL DISCHARGE AT LEAST 1 FT.
 AWAY FROM THE STRUCTURE SIDEWALL,
 WHETHER BY UNDERGROUND PIPING, TAIL EX-
 TENSIONS, OR SPLASH BLOCKS.
  
 16) A NEW NOTICE OF COMMENCEMENT MUST BE
 RECORDED. ONCE THE NOTICE OF COMMENCE-
 MENT IS RECORDED WORK MUST BE STARTED
 WITHIN 90 DAYS OR RERECORDED.
  
 17)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-01-15 Cont ID  
Sent By jwitmer Date 2004-01-15 Time 07:15 Rev Time 1.50
Received By jwitmer Date 2004-01-15 Time 07:15 Sent To  
Notes
2004-01-15 00:00:00 
 BUILDING PLAN REVIEW
 PERMIT: 03120934
 ADD: 2275 PALM BEACH LAKES BLVD
 CONT: HALLMARK
 TEL: (561)512-5517
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST REVIEW
 ACTION: DENIED
  
 1)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 PROVIDE TYPES OF FLAMMIBLE AND COMBUST-
 IBLE MATERIALS TO BE STORED AND THE
 AMOUNTS TO BE STORED, THIS WILL DETER-
 MINE WHAT TYPE OF OCCUPANCY THE SPRAY
 BOOTH AND SURROUNDING WORK AREA WILL BE
 CLASSIFIED AS. FOR THIS REVIEW THE CLASS
 IFICATION WILL BE HAZARDOUS; H2, DEFLAG-
 RATION HAZARDS INCLUDE CLASS I,II AND
 III-A FLAMMABLE LIQUIDS IN OPEN CONTAIN-
 ERS OR CONTAINERSPRESSURED AT MORE THAN
 15 PSI.
 PROVIDE INFORMATION FROM TABLE 308.2B
 FOR "EXEMPTION" EXEMPT QUANITIES OF H2
 MATERIALS.
  
 2) SPRAY BOOTH: 407.1.3.5 SPRAY BOOTHS
 WHERE FLAMMABLE MATERIALS ARETO BE USED
 SHALL BE PROTEDCTED BY AN AUTOMATIC
 SPRINKLER SYSTEM.
  
 3) PLANS DO NOT INDICATE FIRE SPRINKLERS
 FOR A TYPE V BUILDING, H2 OCCUPANCY,
 TABLE 500 REQUIRES EITHER 1HR PROTECTED
 FOR 7,500 SQ FT OR UNPROTECTED, SPRINK-
 LERED FOR 4,000 SQ FT. WITH THE ADDITION
 GROSS AREA IS 7003.15= 55'X127'-4".
 ONCE AMOUNTS OF FLAMMIBLE LIQUIDS ARE
 CONFIRMED AND THE AMOUNTS ARE ALLOWABLE
 BY TABLE 308.2B THE H2 OCCUPANCY WILL
 BE DOWN GRADED TO STORAGE, TYPE V BUILD-
 ING, UNPROTECTED.SPECIAL STORAGE OCC.
 411.5.1.
  
 4) OCCUPANCY SEPERATION, SEPERATION
 FROM THE WORK AREA TO BUSINESS OCCUPANCY
 REQUIRES A (2HR WALL) 1 1/2 HR OPENING
 PROTECTIVES).
  
 5) THIS BUILDING IS LOCATED IN A FIRE
 DISTRICT, F102.2.7 ARCHITECTURAL TRIM ON
 BUILDINGS LOCATED IN A FIRE DISTRICT
 SHALL BE CONSTRUCTED OF NONCOMBUSTIBLE
 MATERIALS OR FIRE RETARDANT TREATED
 WOOD. PROVIDED FIRE RESISTANCE RATING
 BASED ON TESTS CONDUCTED IN ACCORDANCE
 WITH ASTM 119.
 THE ARCH AND STRUCTURAL PAGES BOTH
 INDICATE USE CDX PLYWOOD ON THE FRONT
 AND BACK OF THE TOWER & WALL EXTENSIONS,
 THIS CONSTITUTES TYPE VI CONSTRUCTION,
 NOT ALLOWED IN THE "FIRE DISTRICT".
 F102.1. THIS ALSO INCLUDES GIRDER TRUSS-
 ES MAKING UP WALL PANELS OF TOWER.
  
 6)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 PLANS INDICATE MULTIPLE PAGES, (2) A2,
 (3) A4,PLEASAE PULL OLD SHEETS, OR IF
 ALL SHEETS ARE APPLICABLE RENUMBER, ALSO
 DESIGNATE WHICH DETAILS BELONG TO WHICH
 BUILDING.
 DOOR & WINDOW OPENINGS BELONGING TO
 SOUND ADVISE AND ARE "NEW" DO NOT SHOW
 UP ON THE DOOR WINDOW SCHEDULE.
  
 7) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) GLAZED SING DOORS
 B) GLAZED SWING DOORS W/ SIDELIGHTS
 C) GLAZED SWING DOORS W/ SIDELIGHTS &
 TRANSOM
 D) MULLIONS, VERTICAL & HORIZONTAL
 E) WINDOWS
 F) STORM SHUTTERS IF IMPACT GLAZING
 NOT USED
 G) LOUVERS
 H) PANEL WALLS, INCLUDING EFIS, FOAM
 MOLDINGS
 I) ROOFING ASSEMBLIES
  
 8)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 9)1707.4.5.1 MULLIONS OCCURRING
 BETWEEN INDIVIDUAL WINDOW AND GLASS
 DOOR ASSEMBLIES. TESTING REPORTS ARE
 REQUIRED BY AN APPROVED TESTING
 LABORATORY OR BE ENGINEERED.
  
 10) 1707.4.5.2 MULLIONS SHALL BE DESIGN-
 ED TO TRANSFER THE DESIGN PRESSURE LOADS
 APPLIED BY THE WINDOW OR DOOR ASSEMBLIES
 TO THE ROUGH OPENING SUBTRATE.
  
 11)PROVIDE STORM PANEL INFORMATION WITH
 INSTALLATION SCHEDULE AND KEY PLAN WITH
 SPECIFIC ANCHORS AND MOUNTING TO BE USED
 FOR ALL NON-IMPACT GLAZING.
 FBC 1606.1.4.
  
 12)FL BLD CODE 2001 SECTION 103.6,
 1606.1.4, 1707.4 & 3401.7.2.4.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING
 OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL PRES-
 SURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
  
 13)1707.4.4.2 TAPERED BUCKS:
 SHALL EXTEND BEYOND THE INTERIOR FACE
 OF THE WINDOW OR DOOR FRAME SUCH THAT
 FULL SUPPORT OF THE FRAME IS SUPPORTED.
  
  
 14) 1606.4.4 ANCHOR METHODS. PROVIDE
 INFORMATION FOR INSTALLATION OF DOOR
 AND WINDOW BUCKS.
  
 15) FL BLD CODE 104.2.1.2
 0DDITIONAL INFORMATION REQUIRED,
 DISCREPANCY, SHEET A-4 CARSMETIC ELE.
 VS. S3 SPECIFICATION AS A COSTAL ZONE,
 HIGHER NEGITIVE PRESSURES, INDICATE
 THESE INCREASED PRESSURES FOR ALL OPEN-
 INGS, INDICATE FOR ALL ELEVATIONS,
 BOTH BUILDINGS.
  
 16) S3 INDICATES ENGINEERING CRITERIA,
 TRUSSES NO BOTTOM CHORD LIVE LOAD,
 10 LBS. (TABLE 1604.1)
  
 17) TRUSS ANCHOR SCHEDULE, RE-EVALUATE
 TO FLORIDA SPECIFIC, SEE VALUES IN
 USP CATOLOG IN GRAY SHADING NO ADDITION-
 AL STRESS ON STEEL CALCULATIONS.
 1609.4.3 LOAD REDUCTION.
 WHEN STRUCTURAL EFFECTS DUE TO TWO OR
 MORE LOADS IN COMBINATION WITH DEAD LOAD
 ARE INVESTIGATED IN LOAD COMBINATIONS OF
 1609.4.1 OR 1609.4.2, THE COMBINED
 EFFECTS DUE TO THE TWO OR LOADS MULTI-
 PLIED BY 0.75 PLUS EFFECTS DUE TO DEAD
 LOADS SHALL NOT BE LESS THAN THE EFFECTS
 FROM THE LOAD COMBINATION OF THE DEAD
 LOAD PLUS THE LOAD PRODUCING THE LARGEST
 EFFECTS. INCREAS IN ALLOWABLE STRESS SPE
 CIFIED IN THE MATERIALS SECTIONS OF THIS
 CODE OR A REFRENCED STANDARD SHALL NOT
 BE USED WITH THESE LOAD COMBINATIONS
 EXCEPT THAT A DURATION OF LOAD INCREASE
 SHALL BE PERMITTED IN ACCORDANCE WITH
 CHAPTER 23.
  
 18)1511.7 ROOF MOUNTED MECHANICAL UNIT
 S SHALL BE MOUNTED ON CURBS RAISED A
 MINIMUM OF 8 INCHES ABOVE THE ROOF SUR-
 FACE, OR WHERE ROOFING MATERIALS EXTEND
 BENEATH THE UNIT, ON RAISED EQUIPMENT
 SUPPORTS PROVIDING A MINIMUM CLEARENCE
 HEIGHT IN ACCORDANCE WITH TABLE 1511.7.
 MECH. 301.13 WIND RESISTANCE
 MECHANICAL EQUIPMENT, APPLIANCES AND SUP
 PORTS THAT ARE EXPOSED TO WIND SHALL BE
 DESIGNED AND INSTALLED TO RESIST THE
 WIND PRESSURES ON THE EQUIPMENT & THE
 SUPPORTS AS DETERMINED IN ACCORDANCE
 WITH THE FL BLD CODE. THIS MAY BE ACCOMP
 LISHED BY DESIGN OR BY APPLICATION OF
 SECTION 301.13.1.
  
 19)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2004-06-02 Cont ID  
Sent By dpalmer Date 2004-06-02 Time 10:01 Rev Time 0.33
Received By dpalmer Date 2004-06-02 Time 10:01 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2004-04-28 Cont ID  
Sent By dpalmer Date 2004-04-28 Time 18:42 Rev Time 0.33
Received By dpalmer Date 2004-04-28 Time 18:41 Sent To  
Notes
2004-04-28 00:00:00*** UNSAT ***
  
 1)NOTE: PLEASE SEE PREVIOUS NOTES.
 IT WAS REQUESTED ALL OLD VOIDED SHEETS
 BE REMOVED FROM SETS AND ONLY INSERT
 NEW SHEETS. THERE ARE TWO NEW ELECTRICAL
 SHEETS IN EACH SET DATED 4/8/04, HOWEVER
 THERE IS ONLY 1.01 AND 2.01?
 PLEASE SUBMIT THE REQ'D COMPLETED SETS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-02-17 Cont ID  
Sent By dpalmer Date 2004-02-17 Time 15:49 Rev Time 1.00
Received By dpalmer Date 2004-02-17 Time 14:28 Sent To  
Notes
2004-02-17 00:00:00**** UNSAT ******
  
 1)NOTE: PLEASE SEE NOTE #3 FROM FIRST
 REVIEW. A CLEAR FLOOR SPACE IS SHOWN
 ON PLANS, HOWEVER NO REFERENCE IS MADE
 TO CLASS/LOCATION/ PER NEC.
 PLEASE SEE THAT PLANS NOTE A PRE-FAB
 BOOTH WITH ELEC LTS AND FANS AND NO
 DETAIL FOR CIRCUITING/DISC MEANS IS
 PROVIDED? PLEASE CLARIFY.
 IS THIS GOING TO BE PANEL "P"? IF SO,
 PLEASE SHOW ON PLANS.
  
 PLEASE SEE THAT NEW SETS OF PLANS CAME
 IN WITH OUT POWER PLANS/ SHEETS.
 PLEASE REMOVE ANY AND ALL OLD/VOIDED
 SHEETS AND INSERT NEW SHEETS INTO TWO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SEE THAT PLANS ARE COMING BACK
 FOR OTHER COMMETS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-12-31 Cont ID  
Sent By dpalmer Date 2003-12-31 Time 13:46 Rev Time 1.00
Received By dpalmer Date 2003-12-31 Time 13:41 Sent To  
Notes
2003-12-31 00:00:00************* UNSAT **************
  
 1)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH PANEL SCHEDULE.
 SOME SHOWN AS XX.
  
 2)NOTE: PLEASE CLARIFY NEW/ EXISTING
 REQ'D SIGN CIRCUIT PER 600.5
 APPEARS TO BE SHOWN ON PANEL SCHEDULE,
 PLEASE SHOW ON PLANS.
  
 3)NOTE: PLEASE SHOW/LABEL AND MAP AREA
 FOR SPRAY BOOTH PER NEC 516 AND LABEL
 AREAS ON PLANS FOR NEC 511.
 PLEASE CLARIFY IF LIGHTING ETC WILL BE
 PART OF BOOTH? PLEASE ALSO PROVIDE
 APPLICABLE MANF. SPECS FOR BOOTH.
  
 4)NOTE: PLEASE INLCUDE ADDRESS OF JOB
 ON TITLE BLOCK AS REQ'D UNDER FS
 FAC 61G1-16.004, 61G15-23.002.
  
 5)NOTE: PLEASE INCLUDE FOOTER STEEL AS
 PART OF THER GROUNDING ELECTRODE SYSTEM
 PER 250.50
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
 PLEASE SEE FIRE REVIEW COMMENTS AS THEY
 WILL HAVE A DIRECT AFFECT ON ELECTRICAL
 PLANS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2004-04-29 Cont ID  
Sent By mcarsill Date 2004-04-29 Time 11:47 Rev Time 0.00
Received By mcarsill Date 2004-04-29 Time 11:46 Sent To  
Notes
2004-04-29 00:00:001) SINCE THE BUILDING IS LOCATED IN
 THE CITY FIRE LIMITS, THE ROOF
 COVERING SHALL MEET EITHER A OR B
 CLASSIFICATION.
  
 2) SEPARATE PLANS AND PERMITS REQUIRED
 FOR SPRAY BOOTH, FIRE SUPPRESSION SYSTEM
 AND APPURTENANT EQUIPMENT.
  
 3) COULD NOT LOCATE COMMENT RESPONSE
 # 8 ON PLAN REVIEW RESPONSE LETTER.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2004-02-13 Cont ID  
Sent By mcarsill Date 2004-02-13 Time 13:49 Rev Time 0.00
Received By mcarsill Date 2004-02-13 Time 13:49 Sent To  
Notes
2004-02-13 00:00:001) PRE-MANUFACTURED FOAM BANDING SHOWN
 ON A-4. ALL ARCHITECTURAL TRIM
 LOCATED IN THE FIRE LIMTS SHALL
 BE NON-COMBUSTIBLE. FOAM ALSO SHOWN
 ON SECTIONS SHEET. PLEASE SEE
 APPENDIX F OF THE LOCAL AMENDMENTS TO
 THE FLORIDA BUILDING CODE.
  
 2) COULD NOT LOCATE NOTE ON FLOOR
 PLAN REGARDING BUILDING ADDRESS.
  
 3) COULD NOT LOCATE NOTES REGARDING
 FIRE LIMITS.
  
 4) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATION INFORMATION.
  
 5) PLEASE DISPLAY PROPOSED MIXING
 ROOM LOCATION ON FLOOR PLANS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-12-29 Cont ID  
Sent By mcarsill Date 2003-12-29 Time 17:06 Rev Time 0.00
Received By mcarsill Date 2003-12-29 Time 17:06 Sent To  
Notes
2003-12-29 00:00:001) THIS LOCATION APPEARS TO BE LOCATED
 IN THE CITY FIRE LIMITS. PLEASE
 SEE APPENDIX F, LOCAL AMENDMENTS TO
 THE FLORIDA BUILDING CODE. CERTAIN
 RESTRICTIONS APPLY.
  
 2) SEPARATE PLANS AND PERMITS
 REQUIRED FOR THE PREFAB BOOTH AND
 MIXING BOOTH. THE PAINT BOOTH SHALL
 BE EQUIPPED WITH FIRE SUPPRESSION
 EQUIPMENT.
  
 3) A TWO-HOUR FIRE SEPARATION IS
 REQUIRED BETWEEN THE GARAGE AND OTHER
 PORTIONS OF THE BUILDING. DOORS
 WITHIN THIS WALL SHALL BE AT LEAST
 1 1/2 FIRE RATED.
  
 4) PLEASE INDICATE HOW FLAMMABLE
 OR COMBUSTIBLE LIQUIDS WILL BE STORED
 IN GARAGE.
  
 5) BUILDING ADDRESS REQUIRED. A MINIMUM
 OF 6" HIGH NUMBERS ARE REQUIRED.
  
 6) DOOR SCHEDULE INDICATES NO RATED
 FIRE DOORS.
  
 7) A MINIMUM OF THREE FEET CLEARANCE
 IS REQUIRED ALL THE WAY AROUND THE
 SPRAY BOOTH. THE SPRAY BOOTH IS TO
 BE PROPERLY GROUNDED, VENTED, AND
 FIRE SUPPRESSION PROTECTED. THE
 EXHAUST DUCT IS TO BE PROPER SIZE AND
 HEIGHT TO VENT FLAMMBLE OR COMBUSTIBLE
 LIQUIDS.
  
 8) EXIT SIGNS ABOVE DOOR LEADING
 FROM RECEPTION AREA INTO GARAGE IS NOT
 NEEDED.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2005-03-17 Cont ID  
Sent By adarroug Date 2005-03-17 Time 09:08 Rev Time 0.00
Received By adarroug Date 2005-03-17 Time 09:08 Sent To FIRE
Notes
2005-03-17 00:00:00TO "F" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-03-02 Cont ID  
Sent By adarroug Date 2005-03-02 Time 11:17 Rev Time 0.00
Received By adarroug Date 2005-03-02 Time 11:17 Sent To M
Notes
2005-03-02 00:00:00TO "M" BOX/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-01-20 Cont ID  
Sent By mjacobs Date 2005-01-20 Time 14:41 Rev Time 0.00
Received By mjacobs Date 2005-01-20 Time 14:41 Sent To  
Notes
2005-01-20 00:00:00TO "COMM BD#10/REV"

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-06-16 Cont ID  
Sent By csiegber Date 2004-06-16 Time 12:06 Rev Time 0.00
Received By csiegber Date 2004-06-16 Time 12:06 Sent To B
Notes
2004-06-16 00:00:00TO JW DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-05-28 Cont ID  
Sent By csiegber Date 2004-05-28 Time 15:16 Rev Time 0.00
Received By csiegber Date 2004-05-28 Time 15:16 Sent To  
Notes
2004-05-28 00:00:00TO COMM BD#40

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-04-28 Cont ID  
Sent By csiegber Date 2004-04-28 Time 16:05 Rev Time 0.00
Received By csiegber Date 2004-04-28 Time 16:04 Sent To  
Notes
2004-04-28 00:00:00TO COMM BD#59

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-02-12 Cont ID  
Sent By csiegber Date 2004-02-12 Time 14:53 Rev Time 0.00
Received By csiegber Date 2004-02-12 Time 14:53 Sent To  
Notes
2004-02-12 00:00:00TO COMM BD#53

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-01-15 Cont ID  
Sent By mmclean Date 2004-02-12 Time 14:52 Rev Time 0.00
Received By csiegber Date 2003-12-17 Time 10:31 Sent To  
Notes
2003-12-23 00:00:0012/17/03 TO Z
 TO COMM BD#5

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2005-03-16 Cont ID  
Sent By pkrauss Date 2005-03-16 Time 15:27 Rev Time 0.25
Received By pkrauss Date 2005-03-16 Time 15:27 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status N Date 2005-03-09 Cont ID  
Sent By pkrauss Date 2005-03-09 Time 14:15 Rev Time 0.20
Received By pkrauss Date 2005-03-09 Time 13:43 Sent To  
Notes
2005-03-09 00:00:00PLANS ARE TO BE SIGNED, SEALED AND DATED
 BY THE ENGINEER OF RECORD PER FS 471.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2005-01-22 Cont ID  
Sent By pkrauss Date 2005-01-22 Time 10:57 Rev Time 0.35
Received By pkrauss Date 2005-01-22 Time 10:50 Sent To  
Notes
2005-01-22 00:00:00SEE PROVISO FROM REVIEW DATED 3-3-04

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-03-03 Cont ID  
Sent By pkrauss Date 2004-03-03 Time 11:22 Rev Time 0.45
Received By pkrauss Date 2004-03-03 Time 10:54 Sent To  
Notes
2004-03-03 00:00:00PLEASE NOTE SEPARATE PERMIT REQUIRED FOR
 THE MIXING & SPRAY BOOTH.PROVIDE
 PLANS, CUT SHEETS AND THE FOLLOWING
 INFORMATION WITH MECHANICAL PERMIT
 APPLICATION.
  
 1.LOCATION OF MIXING ROOM IN RETLATION
 TO THE SPRAY BOOTH.
  
 2.SHOW COMPLIANCE WITH NFPA 33 FOR
 REQUIREMENTS FOR TERMINATION OF EXHAUST,
 PIPING,, PROTECTION & SPRINKLER SYSTEMS.
  
 3.CUT SHEETS SUBMITTED FOR THE MIXING
 ROOM DO NOT INDICATE AN EXHAUST FOR THIS
 AREA.PLEASE CLARIFY.
  
 HVAC FOR THE REST OF THE BUILDING IS
 CODE COMPLIANT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-01-07 Cont ID  
Sent By pkrauss Date 2004-01-07 Time 13:04 Rev Time 1.15
Received By pkrauss Date 2004-01-07 Time 12:34 Sent To  
Notes
2004-01-07 00:00:00DENIED:
 1.CU-1 LOCATED ON THE ROOF SHALL
 COMPLY WITH 2001 FBC 1511.7 FOR HEIGHT
 REQUIREMENT BEWTEEN THE ROOF SURFACE &
 THE BOTTOM OF THE SUPPORT RAIL (SEE
 ATTACHED).
  
 2.CONDENSATE SHALL DISCHARGE A MINIMUM
 OF 12" FROM THE BUILDING STRUCTURE PER
 2001 FBC 1503.4.4.
  
 3.PLEASE PROVIDE MANUFACTURER
 SUBMITTAL DATA FOR THE SPRAY/MIXING
 BOOTH AND VENTILATION DETAILS WITH
 PERMIT APPLLICATION.INDICATE DISTANCE
 BETWEEN EXHAUST TERMINATION AND PROPERTY
 LINES ADJACENT BUILDINGS AND FRESH AIR
 INTAKES.SHOW COMPLIANCE WITH NFPA 33,
 AND 2001 FBC(M) CHAPTER 5.SEE COMMENTS
 BY FIRE DEPT. AND BUILDING.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 4 Status P Date 2005-02-09 Cont ID  
Sent By kstevens Date 2005-02-09 Time 11:01 Rev Time 0.62
Received By kstevens Date 2005-02-09 Time 11:01 Sent To  
Notes
2005-02-09 00:00:00REVISION OK - CHANGED LOCATION OF THE
 EYE WASH - SANT. & WATER

Review Stop P PLUMBING
Rev No 3 Status P Date 2004-05-05 Cont ID  
Sent By pschmitz Date 2004-05-05 Time 15:15 Rev Time 2.00
Received By pschmitz Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2004-03-04 Cont ID  
Sent By kstevens Date 2004-02-23 Time 17:40 Rev Time 0.50
Received By kstevens Date 2004-02-23 Time 17:40 Sent To  
Notes
2004-02-23 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 A) COMMENTS FROM PREVIOUS REVIEW HAVE
 NOT BEEN ADDRESSED SUFFICIENTLY. COMMENT
 NUMBERS SHALL REMAIN THE SAME FOR CLAIR-
 ITY.
 3) SHT A3 (CHANGED FROM A2) FLOOOR PLAN
 URINAL SHALL BE ACCESSIBLE PER SECTION
 11-4.22.5. PROVIDE A DETAIL SHOWING
 COMPLIANCE WITH SECTION 11-4.18 AND ALL
 SUBSECTIONS.
 4) PROVIDE A ROOF PLAN. SHOW PRIMARY AND
 SECONDARY ROOF DRAINS AND THEIR LOCATION
 AND SHOW SIZE OF DRAINS AND PIPE SIZES.
 5) SUBMIT CALCULATIONS FOR PRIMARY AND
 SECONDARY ROOF DRAINS PER SECTIONS 1106
 & 1107 AND ALL SUBSECTIONS. SHOW 1/2
 AREA OF ALL VERTICAL WALLS INCLUDING
 PARAPETS ADDED TO CLACULATIONS. SHOW
 AREAS OF ROOFS THAT DRAIN ONTO ROOF FROM
 ABOVE ADDED TO CALCULATIONS.
 ----------NO DETAIL WAS SUBMITTED FOR
 THE URNAL---------NO CALCULATIONS SHOW-
 ING 1/2 AREA OF VERTICAL WALLS ADDED TO
 SQUARE FOOTAGE OF ROOF. NO AREA OF UPPER
 ROOF WAS SHOWN BEING ADDED TO CALCULAT-
 IONS. NO PRIMARY ROOF DRAINS ARE SHOWN.
 ONLY SCUPPER DRAINS WERE SHOWN. (SECOND-
 ARY DRAINS) - NO NEW SECTION OF ROOF IS
 SHOWN BEING ADDED TO EXISTING ROOF.-----
 NEW COMMENT********
 1B) SUBMIT A DETAIL SHOWING ALL SECOND-
 ARY SCUPPERS SHOWING HEIGHT & WIDTH AND
 SHOW HEIGHT OF FLOW LINE OFF ROOF AS RE-
 QUIRED IN SECTION 1503.4.2 OF THE FBC
 BUILDING.
 2B) REFERENCED ON SHEET A10 IS TABLE
 1106.3 FOR HORIZONTAL PIPING. NO PIPING
 IS SHOWN. SUBMIT A STORM RISER DIAGRAM.
 3B) REFERENCED ON SHEET A10 IS TABLE
 1106.6 INDICATING THAT GUTTERS ARE BEING
 USED. NO GUTTERS ARE SHOWN. PLEASE
 CLAIRFY.
 4B) A CERTIFICATE OF AUTHORIZATION IS
 REQUIRED PER FS 481.219
 *******NEW COMMENTS
 5B) UPON CONVERSING WITH BLDG PLAN RE-
 VIEWER, I SEE THAT THERE ARE MODIFICAT-
 IONS TO THE OTHER BLDG. (SOUND ADVISE)
 THIS WILL REQUIRE CALCULATIONS FOR THE
 EXISTING ROOF OF THAT BLDG. SHOWING THE
 SQUARE FOOTAGE OF THE ROOF AND SHOWING
 1/2 AREA OF ALL VERTICAL WALLS INCLUDING
 PARAPETS. A ROOF PLAN WILL BE REQUIRED
 SHOWING PRIMARY AND SECONDARY ROOF
 DRAINS AND THERE LOCATION. SHOW SIZES OF
 ROOF DRAINS, PIPING SIZES, GUTTERS,
 RAIN WATER LEADERS, DOWNSPOUTS ECT.
 SECTIONS 1106 & 1107 AND ALL SUBSECTIONS
 6B) MSDS SHEETS FOR ALL HAZADOUS MATER-
 IALS. REVIEW OF THESE SHEETS MAY CAUSE
 MORE COMMENTS TO BE FORTHCOMMING. ALSO
 AN EYEWASH AND/OR EMERGENCY SHOWER MAY
 BE REQUIRED.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-01-09 Cont ID  
Sent By kstevens Date 2004-01-09 Time 11:24 Rev Time 0.80
Received By kstevens Date 2004-01-09 Time 11:24 Sent To  
Notes
2004-01-09 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) SHT A2 DEMO PLAN, ALL ABANDONED OR
 CAPPED PLUMBING LINES SHALL BE INSPECTED
 PRIOR TO COVERING.
 2) SHT A2 FLOOR PLAN, 11-4.22.2 DOORS
 SHALL NOT SWING INTO THE CLEAR FLOOR
 SPACE REQUIRED FOR ANY FIXTURE.
 3) SHT A2 FLOOR PLAN, URNAL SHALL BE
 ACCESSIBLE PER SECTION 11-4.22.5. PLEASE
 PROVIDE A DETAIL SHOWING COMPLIANCE WITH
 SECTION 11-4.18 AND ALL SUBSECTIONS.
 4) PROVIDE A ROOF PLAN SHOW PRIMARY AND
 SECONDARY ROOF DRAINS AND THEIR LOCATION
 AND SHOW SIZE OF DRAINS AND PIPE SIZES.
 5) SUBMIT CALCULATIONS FOR PRIMARY AND
 SECONDARY ROOF DRAINS PER SECTIONS 1106
 AND 1107 AND ALL SUBSECTIONS. SHOW 1/2
 AREA OF ALL VERTICAL WALLS INCLUDING
 PARAPETS ADDED TO CALCULATIONS. SHOW
 AREAS OF ROOFS THAT DRAIN ONTO ROOF FROM
 ABOVE ADDED TO CALCULATIONS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2003-12-22 Cont ID  
Sent By csiegber Date 2003-12-17 Time 10:31 Rev Time 0.00
Received By mmclean Date 2003-12-22 Time 16:47 Sent To I
Notes
***NONE***