Plan Review Details - Permit 03120833
Plan Review Stops For Permit 03120833
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2004-07-22 Cont ID  
Sent By jwitmer Date 2004-07-22 Time 08:35 Rev Time 0.75
Received By jwitmer Date 2004-07-22 Time 08:35 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2004-06-08 Cont ID  
Sent By csiegber Date 2004-07-16 Time 16:20 Rev Time 0.75
Received By jwitmer Date 2004-06-08 Time 16:22 Sent To PC
Notes
2004-06-08 00:00:00REVISION# 1 5/25/04JW

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2004-05-10 Cont ID  
Sent By csiegber Date 2004-06-03 Time 15:40 Rev Time 0.76
Received By jwitmer Date 2004-05-10 Time 14:58 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2004-04-27 Cont ID  
Sent By jwitmer Date 2004-04-27 Time 08:13 Rev Time 3.00
Received By jwitmer Date 2004-04-27 Time 08:13 Sent To  
Notes
2004-04-27 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03120833
 ADD: 314 CLEMATIS ST
 CONT:SHAWE-AGER CONSTRUCTION
 TEL: (561)248-6411
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 3RD REVIEW
 ACTION: DENIED
  
 1) COMMENT# 1 FROM FIRST REVIEW:
 SHEET A2.1 SHOWS THE RECONFIGURATION OF
 THE FRONT ENTRY STAIR.
 1006.1.1 EXIT STAIRWAYS BETWEEN FLOORS
 SHALL BE ENCLOSED IN OR SEPERATED BY
 FIRE RESISTANCE CONSTRUCTION IN ACCORD-
 ANCE WITH 705.2AND TABLE 705.1.2.
  
 THE ISSUE NOT BEING ADDRESSED ON THE
 FRONT EXIT STAIRWAY FROM PREVIOUS
 REVIEWS IS THERE ARE (2) REQUIRED MEANS
 OF EGRESS, THE STAIRWAY SHAFT OR STAIR
 ENCLOSURE,(EXIT) 1006.1.4 THERE SHALL
 BENO ENCLOSED USABLE SPACE WITHIN AN
 EXIT ENCLOSURE. 1006.1.3 A STAIRWELL
 ENCLOS- URE SHALL NOT BE USED FOR ANY
 OTHER PUR-POSE OTHER THAN A MEANS OF
 EGRESS.
 OPENINGS IN EXIT ENCLOSURES OTHER THAN
 UNEXPOSED EXTERIOR OPENINGS SHALL BE
 LIMITED TO THOSE NECESSARY FOR THE EXIT
 ACCESS TO THE ENCLOSURE FROM NORMALLY
 OCCUPIABLE OR HABITABLE ROOMS AND FOR
 EGRESS FROM THE ENCLOSURE.
  
 2) COMMENT# 4 FROM 1ST REVIEW:
 PRIVATE BATHROOMS, 11-4.1.3(11) PRIVATE
 BATHROOMS ARE TO BE ADAPTABLE. THIS
 WILL MEAN TO BE ADAPTABLE THE 5'-0"
 TURNING RADIUS IS IN AFFECT, BATHROOM
 235 APPEARS TO MAKE THIS REQUIREMENT
 INDICATE THE 5'-0" CLEAR TURNING RADIUS
 FOR BATHROOM 210. PROVIDE THE REQUIRED
 BACKING FOR AN ADAPTABLE BATHROOM
 (11-4.16.4) BACKING FOR GRAB BARS.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-03-02 Cont ID  
Sent By jwitmer Date 2004-03-02 Time 08:12 Rev Time 2.66
Received By jwitmer Date 2004-03-01 Time 16:38 Sent To  
Notes
2004-03-02 00:00:00 
 BUILDING PLAN REVIEW
 PERMIT: 03120833
 ADD: 314 CLEMATIS ST
 CONT: RAPP CONSTRUCTION
 TEL: (561)248-6411
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 2ND REVIEW
 ACTION: DENIED
  
 1) COMMENT# 1 FROM FIRST REVIEW:
 SHEET A-2.1 SHOWS A RECONFIGURATION OF
 THE FRONT ENTRY STAIR. THE 2ND FLOOR
 DEMO SHEET ALSO INDICATES A DOOR
 REMOVED FROM HALLWAY 228. THIS RECONFIG-
 URATION WITH RECEPTION AREA ELIMINATES
 THE 1HR RATING OF THE "STAIRWELL SHAFT".
 1006.1.1 EXIT STAIRWAYS BETWEEN FLOORS
 SHALL BE ENCLOSED IN OR SEPERATED BY
 FIRE RESISTANT CONSTRUCTION IN ACCORD-
 ANCE WITH 705.2 AND TABLE 705.1.2.
 TABLE 705.1.2 REQUIRES A 1HR RATED WALL
 AND 1 HR OPENING PROTECTIVES.
 705.1.3.41HR DOORS ARE TO BE USED IN
 STAIRWAYS. AVERAGE TEMP RISE DEVELOPED
 ON THE UNEXPOSED SIDE SHALL NOT EXCEED
 450 DEGREES F AT THE END OF 30 MINUTES
 OF STANDARD FIRE TEST EXPOSURE.
 TABLE 705.1.3.6
 WINDOWS IN SHAFTS, 705.2.3.5 OPENINGS
 IN SHAFT ENCLOSURES SHALLBE PERMITTED
 WHEN LIMITED TO THOSE NECESSARY FOR THE
 PURPOSE OF THE SHAFT. PERMITTED OPENINGS
 INSHAFT ENCLOSURES SHALL BE PROTECTED
 WITH OPENING PROTECTIVES HAVING A FIRE
 RESISTANCE IN ACORDANCE WITH 705.1.2.
 WINDOWS 1HR SEE TABLE 705.1.3.6 FOR
 WIRED GLASS PANELS USE 1HR RATING SIZE
 MAX100 SQ IN, 33"X12".
  
 705.2.2 DOES HAVE AN EXCEPTION TO THE
 SHAFT ENCLOSURE REQUIREMENT 705.2.2(2)
 BUT"ALL 6 REQUIREMENTS MUST BE MET",
 (1) IT IS A PART OF A MEANS OF EGRESS.
 PLANS ALSO INDICATE THAT (2) MEANS OF
 EGRESS ARE REQUIRED AS DOES 1004.1.4.
 THE SECOND ISSUE IS 1006.1.4 THERE
 SHALL BE NO ENCLOSED USABLE SPACE WITHIN
 AN EXIT ENCLOSURE. THERE MUST BE SEPERA-
 TION (1HR) BETWEEN THE ENCLOSED STAIR
 AND LOBBY OR SITTING ROOM! REVISE INDI-
 CATING RATED DOORS WINDOWS USAGE AS WELL
 AS PENETRATIONS INTO AND THROUGH A
 STAIRWELL ENCLOSURE 1006.1.3.1.
  
 2) NOTE# 3 FROM 1ST REVIEW:
 CORRECT, RAMPS 6" OR LESS DO NOT NEED TO
 MEET THE HANDRAIL REGULATIONS BUT THE
 SLOPE AND LANDING REQUIREMENTS OF:
 11.4.8.2 SLOPE & RISE
 11.4.8.4(2) LANDINGS **SEE BOTTOM LAND-
 ING 72"X36" MINIMUM.11-4.3.3 MINIMUM
 WIDTH OF AN ACCESSIBLE ROUTE IS 36".
  
 3) COMMENT# 4 FROM 1ST REVIEW:
 PRIVATE BATHROOMS, 11-4.1.3(11)
 PRIVATE BATHROOMS SHALL BE ADAPTABLE.
 TO BE ADAPTABLE THE SIZE REGULATIONS ARE
 IN AFFECT, AND BACKING REQUIRED. THESE
 REQUIREMENTS AFFECT ROOMS 210 & 235.
  
 4) COMMENT# 7 FROM 1ST REVIEW:
 WILL NEED TO APPLY FOR VARIANCE TO THE B
 OARD OF AJUSTMENT & APPEAL FOR VARIANCE
 TO USE DELUGE CURTIAN.
 THE VARIANCE SHOULD BE FOR A TYPE V
 BUILDING 0-3' FROM PROPERTY LINE REQUIR-
 ING THREE HR WALLS (ZERO % OPENINGS) TO
 ALLOW OPENINGS AT WHAT PERCENT? THE
 WATER CURTAIN SHOULD BE DESIGNED AS THE
 EQUAVALENT FOR A 3HR WALLAS PER NFPA 13
 WATER CURTAIN 5-13.4.
  
 5) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) IMPACT FIXED WINDOWS
 *********IMPORTANT**************
 *********IMPORTANT**************
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-01-14 Cont ID  
Sent By jwitmer Date 2004-01-14 Time 12:51 Rev Time 2.75
Received By jwitmer Date 2004-01-14 Time 12:51 Sent To  
Notes
2004-01-14 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03120833
 ADD: 314 CLEMATIS ST.
 CONT: RAPP CONSTRUCTION
 TEL: (561)248-6411
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST BUILDING REVIW
 ACTION: DENIED
  
 1) SHEET A-2.1 SHOWS A RECONFIGURATION
 OF THE FRONT ENTRY STAIR. THE 2ND FLOOR
 DEMO SHEET ALSO INDICATES A DOOR REMOVED
 FROM HALLWAY 228. THIS RECONFIGURATION
 WITH RECEPTION AREA ELIMINATES THE 1 HR
 RATING OF THE STAIRWELL.
 1006.1.3.1 PENETRATIONS INTO AND
 THROUGH A STAIRWAY ENCLOSURE ASSEMBLY
 ARE PROHIBITED EXCEPT FOR REQUIRED EXIT
 DOORS, DUCTWORK AND EQUIPMENT NECESSARY
 FOR THE INDEPENDENT STAIR PRESSURIZATION
 SPRINKLER PIPING, STANDPIPES AND ELECTRI
 CALCONDUIT SERVING THE STAIRWAY AND
 TERMINATING AT A STEEL BOX NOT EXCEEDING
 16 SQ IN. SUCH PENETRATIONS SHALL BE PRO
 TECTED IN ACCORDANCE WITH 705.4
 1006.1.4 THERE SHALL BE NO ENCLOSED
 USEABLE SPACE WITHIN AN EXIT ENCLOSUE,
 INCLUDING UNDER STAIRS.
  
 2)1012.1.2 EGRESS DOORS SHALL BE SIDE
 SWINGING TYPE. DOORS SHALL SWING IN THE
 DIRECTION OF EGRESS FOR THE FOLLOWING:
 DOUBLE DOORS LEADING TO THE REAR EXIT
 STAIRS.
  
 3) SERVER ROOM 216: RAMP,
 11-4.8.2 SLOPE & RISE. THE LEAST
 POSSIBLE SLOPE SHALL BE USED FOR ANY
 RAMP. THE MAXIMUM SLOPE FOR A RAMP IN
 NEW CONSTRUCTION SHALL BE 1 TO 12. THE
 MAXIMUM RISE FOR RUN SHALL BE 30" (SEE
 FIGURE 16).
 11-4.8.4.(2) LANDINGS. ALL LANDINGS
 ON RAMPS SHALL NOT BE LESS THAN 60"
 CLEAR, & THE BOTTOM OF EACH RAMP SHALL
 HAVE NOT LESS THAN 72" OF STRAIGHT &
 LEVEL CLEARENCE.
 11.4.8.5. HANDRAILS: IF A RAMP HAS
 A RISE GREATER THAN 6" OR A HORIZONTAL
 PROJECTION GREATER THAN 72", THEN IT
 SHALL HAVE HANDRAILS ON BOTH SIDES.
  
 4) PRIVATE BATHROOM 210, INSWING DOOR:
 11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL.
  
 5) THE DOORSCHEDULE DOESN"T INDICATE
 THE RATED DOORS FOR EXIT ACCESS COORIDOR
 OR EXITS. TABLE 705.1.2
  
 6) THE 1/4" DIAMOND WIRE GLASS, PROVIDE
 RATING ON THE GLAZING AND FRAME.SEE
 TABLE 705.1.3.6/ SEC 705.1.3.6.2.
 SEE A-5.1 DETAIL "03", SIZE LIMITATION
 OF 54" VERTICAL TABLE 705.1.3.6.
  
 7) SHEET A2.1 NOTE# 7 NEW WINDOWS AND
 DELUGE CURTAIN.
 705.1.1.2 EVERY EXTERIOR WALL WITHIN
 15 FT. OF THE PROPERTY LINE SHALL BE
 EQUIPPED WITH OPENING PROTECTIVES. THE
 DELUGE SYSTEM WILL REQUIRE GOING TO THE
 BOARD OF ADJUSTMENT & APPEAL FOR A VAR-
 IANCE UNDER ALTERNATE MEANS AND METHODS.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 11 Status P Date 2005-02-10 Cont ID  
Sent By dpalmer Date 2005-02-10 Time 09:12 Rev Time 0.30
Received By dpalmer Date 2005-02-10 Time 09:12 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 10 Status P Date 2005-01-21 Cont ID  
Sent By dpalmer Date 2005-01-21 Time 08:31 Rev Time 0.50
Received By dpalmer Date 2005-01-21 Time 08:31 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 9 Status P Date 2004-10-08 Cont ID  
Sent By dpalmer Date 2004-10-08 Time 13:40 Rev Time 0.25
Received By dpalmer Date 2004-10-08 Time 13:40 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 8 Status F Date 2004-10-08 Cont ID  
Sent By dpalmer Date 2004-10-08 Time 08:15 Rev Time 0.33
Received By dpalmer Date 2004-10-08 Time 08:14 Sent To  
Notes
2004-10-08 00:00:00********* UNSAT ********
  
 1)NOTE: PLEASE SEE TITLE BLOCK TO BE
 REVISED TO CORRELATE WITH NAME ON RECORD
 WITH STATE. APPEARS TO BE A MISPRINT
 FROM AN OLD CAD?
  
 ELECTRICAL OK, NO NEED FOR ELECTRICAL
 CORRECTIONS.
 STAMPED IN ERROR AND VOIDED ELECTRICAL
 SHEETS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2004-09-14 Cont ID  
Sent By csiegber Date 2004-10-06 Time 14:52 Rev Time 1.00
Received By dpalmer Date 2004-09-14 Time 20:12 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 6 Status N Date 2004-09-16 Cont ID  
Sent By dpalmer Date 2004-09-16 Time 20:11 Rev Time 0.25
Received By dpalmer Date 2004-09-16 Time 20:10 Sent To  
Notes
2004-09-16 00:00:00REV FOR FIRE ALARM. N/A
 NEEDS TO BE UNDER FA PERMIT. 04060806

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2004-08-03 Cont ID  
Sent By csiegber Date 2004-08-25 Time 15:52 Rev Time 0.50
Received By btrobaug Date 2004-08-03 Time 16:46 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2004-05-08 Cont ID  
Sent By csiegber Date 2004-07-26 Time 11:19 Rev Time 0.25
Received By dpalmer Date 2004-05-08 Time 18:17 Sent To  
Notes
2004-05-08 00:00:00*** REVISED E-2 ONLY**
 SHEET E-4 IS STILL REDLINED PER NEC
 230.76,230.79, 230.72, 110.27

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-04-17 Cont ID  
Sent By dpalmer Date 2004-04-17 Time 13:20 Rev Time 0.50
Received By dpalmer Date 2004-04-17 Time 13:20 Sent To  
Notes
2004-04-17 00:00:00REVISED SHEETS E-1, E-2 ONLY.
 E-4 STILL REDLINED FOR 230.72,230.76,
 230.79, 110.27.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-02-02 Cont ID  
Sent By dpalmer Date 2004-02-02 Time 07:56 Rev Time 0.50
Received By dpalmer Date 2004-02-02 Time 07:56 Sent To  
Notes
2004-02-02 00:00:00**** REDLINED NOTES ***
  
 ATS, REQ'D TO HAVE A MEANS OF DISC TO
 MEET 230.76,230.79 AND 110.27.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-01-02 Cont ID  
Sent By dpalmer Date 2004-01-02 Time 10:00 Rev Time 1.00
Received By dpalmer Date 2003-12-29 Time 11:13 Sent To  
Notes
2004-01-02 00:00:00*************** UNSAT ***************
  
 1)NOTE: PLEASE PROVIDE MORE INFORMATION
 ON GENERATOR.
 PLEASE PROVIDE MEANS OF DISC PER 230.72
 230.76,230.79.
  
 2)NOTE: PLEASE SUBMIT AIC RATING FOR
 NEW SERVICE MAIN. SHOWN FOR PANELS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2004-09-20 Cont ID  
Sent By nmccray Date 2004-09-20 Time 11:59 Rev Time 0.00
Received By nmccray Date 2004-09-20 Time 11:59 Sent To  
Notes
2004-09-20 00:00:00REVISION SHOULD BE UNDER FIRE ALARM
 PERMIT 04060806

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2004-05-11 Cont ID  
Sent By mcarsill Date 2004-05-11 Time 16:40 Rev Time 0.00
Received By mcarsill Date 2004-05-11 Time 16:40 Sent To  
Notes
2004-05-11 00:00:00PREVIOUSLY APPROVED BY FIRE RESCUE.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2004-04-06 Cont ID  
Sent By mcarsill Date 2004-04-06 Time 15:01 Rev Time 0.00
Received By mcarsill Date 2004-04-06 Time 15:01 Sent To  
Notes
2004-04-06 00:00:001) ENSURE THAT EMERGENCY LIGHTING
 EQUIPMENT IS PRESENT IN THE STAIRWAYS.
  
 2) PROVIDE SEPARATE PLANS AND PERMITS
 FOR FIRE SPRINKLER REMODEL.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-01-29 Cont ID  
Sent By nmccray Date 2004-01-29 Time 10:45 Rev Time 0.00
Received By nmccray Date 2004-01-29 Time 10:45 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-01-02 Cont ID  
Sent By mcarsill Date 2004-01-02 Time 08:16 Rev Time 0.00
Received By mcarsill Date 2004-01-02 Time 08:15 Sent To  
Notes
2004-01-02 00:00:001) DEMOLITION, RENOVATION, AND
 CONSTRUCTION TO COMPLY WITH NFPA 241.
  
 2) PLEASE PROVIDE MORE DETAILS FOR
 NEW EMERGENCY GENERATOR PLANNED FOR
 THE ROOF.
  
 3) PLEASE PROVIDE MORE DETAILS ON
 DELUGE FIRE SPRINKLER HEADS, ITEM # 18
 ON PAGE A.1.
  
 4) THE DOUBLE DOORS FOR THE EXISTING
 EGRESS STAIR VESTIBULE APPEARS TO
 SWING IN THE WRONG DIRECTION. SHOULD
 THEY NOT SWING IN THE DIRECTION OF
 EXIT TRAVEL.
  
 5) SEPARATE PLANS AND PERMITS REQUIRED
 FOR FM 200 RELOCATION FROM EXISTING
 LOCATION TO THE NEW LOCATION.
  
 6) PLEASE EXPLAIN WHY STAIR NEAR
 WAITING 200 IS NOT SEPARATED FROM ALL
 PORTIONS OF THE BUILDING.
  
 7) TACTILE SIGNAGE IS REQUIRED AT
 STAIRWAYS.
  
 8) ALL SHAFTWAYS THAT ARE LARGE ENOUGH
 FOR PERSONS TO FALL INTO MUST BE
 MARKED SHAFTWAY WITH 6" HIGH LETTERS.
  
 9) DOOR FROM RECEPTION 241 MAY SWING
 TOO FAR INTO CORRIDOR.
  
 10) PLEASE PROVIDE PRODUCT APPROVALS
 FOR DIAMOND WIRE GLASS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 14 Status N Date 2005-02-07 Cont ID  
Sent By adarroug Date 2005-02-07 Time 09:36 Rev Time 0.00
Received By adarroug Date 2005-02-07 Time 09:36 Sent To E
Notes
2005-02-07 00:00:00TO DPALMER DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2004-10-06 Cont ID  
Sent By csiegber Date 2004-10-05 Time 15:23 Rev Time 0.00
Received By csiegber Date 2004-10-05 Time 15:23 Sent To E
Notes
2004-10-05 00:00:00TO DP DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2004-08-31 Cont ID  
Sent By csiegber Date 2004-08-31 Time 14:05 Rev Time 0.00
Received By csiegber Date 2004-08-31 Time 14:05 Sent To  
Notes
2004-08-31 00:00:00TO COMM BD#20

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2004-08-25 Cont ID  
Sent By csiegber Date 2004-08-25 Time 15:52 Rev Time 0.00
Received By csiegber Date 2004-08-25 Time 15:52 Sent To E
Notes
2004-08-25 00:00:00TO DP DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2004-08-16 Cont ID  
Sent By csiegber Date 2004-08-16 Time 09:12 Rev Time 0.00
Received By csiegber Date 2004-08-16 Time 09:12 Sent To M
Notes
2004-08-16 00:00:00TO PK DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2004-07-26 Cont ID  
Sent By csiegber Date 2004-07-26 Time 11:19 Rev Time 0.00
Received By csiegber Date 2004-07-26 Time 11:19 Sent To E
Notes
2004-07-26 00:00:00TO DP DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2004-07-26 Cont ID  
Sent By csiegber Date 2004-07-26 Time 11:07 Rev Time 0.00
Received By csiegber Date 2004-07-26 Time 11:07 Sent To M
Notes
2004-07-26 00:00:00TO PK BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2004-07-16 Cont ID  
Sent By csiegber Date 2004-07-16 Time 16:20 Rev Time 0.00
Received By csiegber Date 2004-07-16 Time 16:20 Sent To B
Notes
2004-07-16 00:00:00TO JW DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2004-07-14 Cont ID  
Sent By mjacobs Date 2004-07-14 Time 12:30 Rev Time 0.00
Received By mjacobs Date 2004-07-14 Time 12:30 Sent To B
Notes
2004-07-14 00:00:00SENT TO JW DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-06-03 Cont ID  
Sent By csiegber Date 2004-06-03 Time 15:40 Rev Time 0.00
Received By csiegber Date 2004-06-03 Time 15:40 Sent To B
Notes
2004-06-03 00:00:00TO JW DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-05-05 Cont ID  
Sent By csiegber Date 2004-05-04 Time 15:01 Rev Time 0.00
Received By csiegber Date 2004-05-04 Time 15:01 Sent To  
Notes
2004-05-04 00:00:00TO COMM BD#50

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-04-05 Cont ID  
Sent By csiegber Date 2004-04-02 Time 11:49 Rev Time 0.00
Received By csiegber Date 2004-04-05 Time 10:45 Sent To  
Notes
2004-04-02 00:00:00TO COMM BD#14

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-01-28 Cont ID  
Sent By csiegber Date 2004-01-28 Time 16:15 Rev Time 0.00
Received By csiegber Date 2004-01-28 Time 16:15 Sent To  
Notes
2004-01-28 00:00:00TO COMM BD#31

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-12-16 Cont ID  
Sent By csiegber Date 2003-12-16 Time 12:04 Rev Time 0.00
Received By csiegber Date 2003-12-16 Time 12:04 Sent To  
Notes
2003-12-16 00:00:00TO COMM BD#15

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2004-08-24 Cont ID  
Sent By pkrauss Date 2004-08-24 Time 13:01 Rev Time 0.40
Received By pkrauss Date 2004-08-24 Time 13:01 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2004-08-04 Cont ID  
Sent By csiegber Date 2004-08-16 Time 09:12 Rev Time 0.45
Received By pkrauss Date 2004-08-04 Time 07:30 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2004-05-12 Cont ID  
Sent By csiegber Date 2004-07-26 Time 11:07 Rev Time 0.40
Received By pkrauss Date 2004-05-12 Time 07:01 Sent To  
Notes
2004-05-12 00:00:00PROVISO:
 PLAN SHEET M-1 INDICATES A FLEX DUCT
 PENETRATING A FIRE RESISTANCE RATED
 ASSEMBLY.PER 2001 603.5.5 FLEXIBLE
 DUCTS ARE PROHIBITED THROUGH A FIRE
 RATED ASSEMBLY. FIRE DAMPER IS NOT
 REQUIRED IF IT COMPLIES WITH SECTION
 607.1.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2004-04-20 Cont ID  
Sent By pkrauss Date 2004-04-20 Time 11:13 Rev Time 0.40
Received By pkrauss Date 2004-04-20 Time 11:00 Sent To  
Notes
2004-04-20 00:00:00RESUB/CHANGE TO PLAN SHEET M-1 ONLY.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-02-24 Cont ID  
Sent By pkrauss Date 2004-02-02 Time 09:45 Rev Time 0.40
Received By pkrauss Date 2004-02-02 Time 09:00 Sent To  
Notes
2004-02-24 00:00:00PASSED ON 2-2-04

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-01-06 Cont ID  
Sent By pkrauss Date 2003-12-31 Time 14:17 Rev Time 0.55
Received By pkrauss Date 2003-12-31 Time 13:21 Sent To  
Notes
2003-12-31 00:00:00DENIED:
 1.PLAN SHEET M-1, PLEASE CLARIFY 8 X 8
 DUCT IN THE WAITING ROOM 200, IS THIS
 DUCT RUNNING THROUGH A EGRESS STAIRWAY?
  
 2.PLAN SHEET M-2 EXISTING MECHANICAL
 ROOM.DOES THIS SPACE HAVE ANY TYPE
 OF EXISTING VENTILATION?
  
 3.M-2 INDICATES DETAIL FOR A FIRE
 DAMPER INSTALLATION FOR "WALL TYPE"
 PLEASE PROVIDE DETAIL FOR THE FIRE
 DAMPERS INSTALLED IN THE FLOOR.
  
 4.PLAN SHEET M-2 INDICATES NEW
 EMERGENCY GENERATOR, WILL THIS WORK BE
 DONE AT THIS TIME OR FUTURE?PLEASE
 PROVIDE ADDITIONAL INFORMATION.PLEASE
 PROVIDE MANUFACTURER SUBMITTAL DATA OR
 CUT SHEETS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 4 Status P Date 2004-05-12 Cont ID  
Sent By kstevens Date 2004-05-12 Time 18:34 Rev Time 1.00
Received By kstevens Date 2004-05-12 Time 18:34 Sent To  
Notes
2004-05-12 00:00:00SEPARATE GAS PERMIT REQUIRED - FIELD
 VERIFY BTU'S AND LISTING FOR EXISTING
 GAS GENERATOR

Review Stop P PLUMBING
Rev No 3 Status F Date 2004-04-12 Cont ID  
Sent By kstevens Date 2004-04-12 Time 07:59 Rev Time 0.50
Received By kstevens Date 2004-04-12 Time 07:59 Sent To  
Notes
2004-04-12 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
  
 1) SHTS A2.1, A2.2, A2.5 & A5.2 PROVIDE
 DETAILS FOR ADAPTABILITY FOR ROOMS #210
 AND #235. RESPONSE NOTED, BUT DETAILS
 STILL NEEDED ARE 11-4.16.2 CLEAR FLOOR
 SPACE, 11-4.16.4 BACKING FOR GRAB BARS,
 11-4.19.3 CLEAR FLOOR SPACE, 11-4.21.3
 BACKING FOR SEAT, 11-4.21.4 BACKING FOR
 GRAB BARS, 11-4.21.5 CONTROL LOCATION,
 11-4.21.7 CURBS, AND 11-4.23.3 TURNING A
 AREA. - SEE COMMENT #2 FROM PREVIOUS RE-
 VIEW
 2) THIS IS THE THIRD REJECTION AND A 4
 TIMES THE FEE MAY BE APPLIED FOR PLAN
 REVIEW PER FS 533.80(2)(B).
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2004-02-05 Cont ID  
Sent By kstevens Date 2004-02-05 Time 17:04 Rev Time 1.00
Received By kstevens Date 2004-02-05 Time 17:04 Sent To  
Notes
2004-02-05 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1) SHTS A2.1, A2.2, & A5.2 DETAIL #13.
 ROOM #235 SHALL BE ACCESSIBLE. PROVIDE
 DETAIL FOR 11-4.16 W/C'S, (SEE FIGS. 28
 & 29), 11-4.19 LAVS, (SEE FIGS. 31, & 32
 ), 11-4.21 SHOWERS, (SEE FIGS. 35, 36, &
 37), AND 11-4.23 SHOWER ROOMS. ALSO SHOW
 ALL SUBSECTIONS FOR EACH SECTION. 11-4.3
 .1(11) - RESPONSE NOTED, BUT BATHROOM #
 235 IS NOT ADJACENT TO OFFICE #208.
 OFFICES #234 & #236 ARE ADJACENT TO THIS
 BATHROOM AND ONLY PRIVATE BATHROOMS OF
 ONE OFFICE SHALL BE ADAPTABLE.
 2) SHTS A2.1, A2.2, & A5.2 DETAIL #9.
 ROOM #210 SHALL BE ADAPTABLE. PROVIDE
 DETAILS SHOWING BACKING FOR GRAB BARS,
 CLEAR FLOOR SPACE, TURNING AREA, SHOWER
 CONTROLS, CURB, BACKING FOR SHOWER GRAB
 BARS, ECT. SECTIONS 11-4.1.3(11), 11-4.2
 1 (FIGS 35, 36, 37). - RESPONSE NOTED,
 BUT BATHROOM #210 IS ADJACENT TO OFFICE
 #208 AND CAN BE ADAPTABLE BUT DETAILS
 ARE REQUIRED.
 3) SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
 4) THESE ARE COMMENTS FROM FIRST REVIEW
 THAT ARE BEING REQUIRED FOR THE SECOND
 REVIEW. SEE ATTACHED SHEET CONCERNING
 FS 533.80(2)(B) DESIGN PROFESSIONAL DOC-
 UMENTS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-01-06 Cont ID  
Sent By kstevens Date 2004-01-06 Time 12:03 Rev Time 1.25
Received By kstevens Date 2004-01-06 Time 12:03 Sent To  
Notes
2004-01-06 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1) SHTS A2.1, A2.2, & A5.2 DETAIL #13.
 ROOM #235 SHALL BE ACCESSIBLE. PROVIDE
 DETAIL FOR 11-4.16 WATER CLOSETS, (SEE
 FIGS. 28 & 29), 11-4.19 LAVS, (SEE FIGS.
 31 & 32), 11-4.21 SHOWERS, (SEE FIGS. 35
 36, & 37), AND 11-4.23 SHOWER ROOMS.
 ALSO SHOW ALL SUBSECTIONS FOR EACH SECT-
 ION. 11-4.3.1(11).
 2) SHTS A2.1, A2.2, & A5.2 DETAIL #9.
 ROOM #210 SHALL BE ADAPTABLE. PROVIDE
 DETAIL SHOWING BACKING FOR GRAB BARS,
 CLEAR FLOOR SPACE, TURNING AREA, LAV
 HEIGHT, OPENING FOR WATER CLOSET, SHOWER
 CONTROLS, CURB, BACKING FOR SHOWER GRAB
 BARS ECT. 11-4.1.3(11).
 3) SHTS A2.1, A2.2, & A5.2 DETAIL #11.
 BREAK ROOM SINK SHALL COMPLY WITH SECT-
 ION 11-4.24 AND ALL SUBSECTIONS. PROVIDE
 A DETAIL.
 4) SHT P-1 WATER ISOMETRIC AT DRINKING
 FOUNTAIN. AIR CHAMBERS ARE NOT APPROVED.
 DELETE FROM DIAGRAM.
 5) SHT P-1 SUBMIT WATER & SANITARY ISO-
 METRICS FOR BREAK ROOM SINK. SECTION
 104.3.1.1. WATER HAMMER ARRESTOR REQUIR-
 ED FOR DISHWASHER. SECTION 604.9
 6) SHT P-1 PLUMBING NOTES: #12 AIR
 CHAMBERS ARE NOT APPROVED. DELETE REF-
 ERENCE.
 7) SHT P-2 FOLLOWING INFORMATION REQUIR-
 ED FOR APPLICATION FOR GAS PERMIT.
 SEPARATE PERMIT REQUIRED FOR GAS.
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 C. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2001 FUEL GAS CODE SECS. 401.8
 THRU 402.5.2 AND TABLES 402(1) THRU
 402(34).
 D. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2001 FUEL GAS CODE
 SECS. 502 THRU 506.
 E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]