Plan Review Details - Permit 03120818
Plan Review Stops For Permit 03120818
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2004-03-31 Cont ID  
Sent By pkrauss Date 2004-03-31 Time 11:32 Rev Time 1.00
Received By jwitmer Date 2004-03-19 Time 07:55 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2004-03-04 Cont ID  
Sent By jwitmer Date 2004-03-04 Time 10:26 Rev Time 0.50
Received By jwitmer Date 2004-03-04 Time 10:26 Sent To  
Notes
2004-03-04 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03120818
 ADD: 1801 PALM BEACH LAKES# 136
 CONT: THE FOSHEE CO
 TEL: (904)398-6667 DURWOOD FOSHEE
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 3RD REVIEW
 ACTION: DENIED
  
 1) SUBMIT THE ORIGINAL PERMIT APPLICA-
 TION.
 2) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
 3) PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
 ARCHITECT IS SEALING PLAN IN LOCATION
 WHERE ENGINEER OF RECORD IS TO SIGN &
 SEAL PLANS.
 NO ENGINEER OF RECORD HAS SIGNED &
 SEALED PLANS.SEE ATTACHED FL STATUTE
 553.80(2)(B)
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-02-03 Cont ID  
Sent By jwitmer Date 2004-02-03 Time 16:04 Rev Time 0.55
Received By jwitmer Date 2004-02-03 Time 16:04 Sent To  
Notes
2004-02-03 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03120818
 ADD: 1801 PALM BEACH LAKES BLVD
 SUITE# 136
 CONT: THE FOSHEE CO INC
 TEL: (904)993-7297
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 SECOND REVIEW
 ACTION: DENIED
 1) PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
 PLANS ARE COPIES OF SIGNATURE NOT
 WET ORIGINAL SIGNATURES!
  
 SEE ELEC FOR OTHER REQUIREMENTS FOR
 ENGINEER OF RECORD
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-01-06 Cont ID  
Sent By jwitmer Date 2004-01-06 Time 12:49 Rev Time 1.00
Received By jwitmer Date 2004-01-06 Time 12:28 Sent To  
Notes
2004-01-06 00:00:00 
 BUILDING PLAN REVIEW
 PERMIT: 03120818
 ADD: 1801 PALM BEACH LAKES BLVD
 SUITE# 136
 CONT: THE FOSHEE CO INC
 TEL: (904)993-7297
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 2) 413.8 AUTOMATIC FIRE SPRINKLER
 SYSTEM, TO BE SUPPLIED WITH BUILDING
 PERMIT SET OF PLANS.
  
 1204.2 SURROUNDING MATERIALS;
 THE WALLS & FLOORS OF ALL PUBLIC REST-
 ROOMS SHALL BE LINED WITH NONABSORBANT
 MATERIALS TO A HEIGTH OF 4'-0" ABOVE THE
 FLOOR.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2004-03-23 Cont ID  
Sent By btrobaug Date 2004-03-23 Time 16:25 Rev Time 0.75
Received By btrobaug Date 2004-03-23 Time 15:37 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2004-03-03 Cont ID  
Sent By dpalmer Date 2004-03-03 Time 14:28 Rev Time 0.33
Received By dpalmer Date 2004-03-03 Time 14:28 Sent To  
Notes
2004-03-03 00:00:00************** UNSAT *************
  
 1)NOTE: PLEASE ADDRESS PREVIOUS REVIEW
 COMMENTS.
  
 2)NOTE: OLD PLANS ARE REQUIRED TO BE
 PICKED UP, REMOVE OLD/VOIDED SHEETS AND
 RESUBMIT COMPLETE SETS FOR REVIEW AND
 STAMPING. WHEN PLANS ARE RESUBMITTED,
 BE SURE TO SUBMIT APPLICATION ETC.
  
 3)NOTE: PLEASE SEE FS 553.80(2)(B)
 SEE COPY ATTACHED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-01-30 Cont ID  
Sent By dpalmer Date 2004-01-30 Time 14:46 Rev Time 0.75
Received By dpalmer Date 2004-01-30 Time 14:46 Sent To  
Notes
2004-01-30 00:00:00************* UNSAT **************
  
 1)NOTE: PLEASE PROVIDE ALL LICENSE #'S
 ON TITLE BLOCKS AS REQ'D UNDER FAC 61G15
 -23.002 FOR ENGS AND 61G1-16.004 FOR
 ARCHS. PLEASE INCLUDE CERTIFICATE OF
 AUTHORIZATION #'S AS REQ'D UNDER FS 471.
 023 FOR ENGS AND FS 481.219 FOR ARCHS.
 THIS IS REQ'D ON ALL SHEETS.
 PLEASE SEE ARCH SHEETS ARE STILL SEALED
 COPIES SIGNATURE? PLEASE SEE FS 481.221
 PLANS MUST HAVE ORIGINAL SUGNATURE, DATE
 AND SEAL.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-12-29 Cont ID  
Sent By dpalmer Date 2003-12-29 Time 07:42 Rev Time 0.50
Received By dpalmer Date 2003-12-29 Time 07:34 Sent To  
Notes
2003-12-29 00:00:00************** UNSAT ***************
  
 1)NOTE: PLANS MUST CONTAIN ORIGINAL
 SIGNATURE BY THE ARCH AND ENGINEER OF
 RECORD PER FS 481.221 AND FS 471.025
 PLEASE SEE THAT BOTHS SETS MUST CONTAIN
 ORIG SIG FOR ALL TRADES WEATHER OR NOT
 COMMENT IS MADE FROM OTHER REVIEWERS.
  
 2)NOTE: PLEASE CLARIFY/SHOW RECEPTS
 REQ'D FOR "SHOW" WINDOW. PER 210.62, AND
 220.12A
  
 3)NOTE: PLEASE CLARIFY CIRCUITING FOR
 EM/EXT LTS PER 700.12E
  
 4)NOTE: PLEASE NOTE OR SHOW TRACK LIGHT-
 ING LOADS PER 220.12B.
  
 NOTE: JUST AN FYI, THESTATE OF FL
 ADOPTED THE 2002 NEC 7/1/2003.
 PLANS NOTE 1993 OR LATEST ADOPTED. THIS
 IS ONLY A NOTE FOR INFORMATION.
  
 5)NOTE: PLEASE INCLUDE ALL LICENSE #`S
 ON TITLE BLOCK AS SET FORTH PER FAC
 61G15-23.002.
 REQ'D ALSO FOR ARCH'S PER 61G1-16.004
 OF THE FAC.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2004-03-23 Cont ID  
Sent By mcarsill Date 2004-03-23 Time 16:58 Rev Time 0.00
Received By mcarsill Date 2004-03-23 Time 16:58 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-01-29 Cont ID  
Sent By mcarsill Date 2004-01-29 Time 07:10 Rev Time 0.00
Received By mcarsill Date 2004-01-29 Time 07:10 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2003-12-24 Cont ID  
Sent By mcarsill Date 2003-12-24 Time 15:36 Rev Time 0.00
Received By mcarsill Date 2004-01-29 Time 07:10 Sent To  
Notes
2003-12-24 00:00:001) PROVIDE SEPARATE AND PERMITS FOR
 FIRE SPRINKLER REMODEL.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 BUREAU OF FIRE PREVNETION

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-03-05 Cont ID  
Sent By csiegber Date 2004-03-05 Time 14:45 Rev Time 0.00
Received By csiegber Date 2004-03-05 Time 14:45 Sent To  
Notes
2004-03-05 00:00:00TO COMM BD#53

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-02-25 Cont ID  
Sent By csiegber Date 2004-02-25 Time 14:37 Rev Time 0.00
Received By csiegber Date 2004-02-25 Time 14:37 Sent To  
Notes
2004-02-25 00:00:00TO COMM BD#13

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-01-27 Cont ID  
Sent By csiegber Date 2004-01-27 Time 10:59 Rev Time 0.00
Received By csiegber Date 2004-01-27 Time 10:59 Sent To  
Notes
2004-01-27 00:00:00TO COMM BD#60

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-12-16 Cont ID  
Sent By csiegber Date 2003-12-16 Time 10:29 Rev Time 0.00
Received By csiegber Date 2003-12-16 Time 10:29 Sent To  
Notes
2003-12-16 00:00:00TO COMM BD#12

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2004-03-31 Cont ID  
Sent By pkrauss Date 2004-03-31 Time 11:32 Rev Time 0.35
Received By pkrauss Date 2004-03-31 Time 11:32 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-02-18 Cont ID  
Sent By pkrauss Date 2004-02-18 Time 16:10 Rev Time 0.40
Received By pkrauss Date 2004-02-18 Time 15:48 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-12-31 Cont ID  
Sent By pkrauss Date 2003-12-31 Time 13:04 Rev Time 0.45
Received By pkrauss Date 2003-12-31 Time 12:53 Sent To  
Notes
2003-12-31 00:00:00DENIED:
 PLEASE PROVIDE THE FOLLOWING INFORMATION
 FOR REVIEW:
 1.OUTSIDE AIR CALCULATIONS PER 2001
 FBC(M) TABLE 403.3.
  
 2.PLAN SHEET M2 DETAIL 4, CONDENSATE
 FROM THE RTU TO CONNECT TO THE FLOOR
 DRAIN IN TENANTS SPACE.CONDENSATE
 SHALL DISCHARGE INTO THE STORM DRAIN NOT
 INTO THE SANITARY PER CITY CODE SEC.
 90-125(B)(5).PLEASE CLARIFY.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 4 Status P Date 2004-03-20 Cont ID  
Sent By kstevens Date 2004-03-20 Time 14:46 Rev Time 0.60
Received By kstevens Date 2004-03-20 Time 14:46 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2004-03-03 Cont ID  
Sent By kstevens Date 2004-03-03 Time 10:01 Rev Time 0.25
Received By kstevens Date 2004-03-03 Time 10:01 Sent To  
Notes
2004-03-03 00:00:00DENIED
 REFERENCE: FLORIDA ADMIN. CODE
 FLORIDA STATUTES
  
 CERTIFICATE OF AUTHORIZATION IS REQUIRED
 PER 61G1-16.00.004(2) & FS 481.219 ON
 THE TITLE BLOCK OF EACH SHEET.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2004-02-03 Cont ID  
Sent By kstevens Date 2004-02-03 Time 14:25 Rev Time 0.33
Received By kstevens Date 2004-02-03 Time 14:25 Sent To  
Notes
2004-02-03 00:00:00DENIED
  
 PLUMBING OK - SEE COMMENTS BY ELECTRICAL
 PLAN REVIEW CONCERNING ORIGINAL SIGNAT-
 URES AND CERTIFICATE OF AUTHORIZATIONS
 ECT.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-01-05 Cont ID  
Sent By kstevens Date 2004-01-05 Time 18:09 Rev Time 0.50
Received By kstevens Date 2004-01-05 Time 18:09 Sent To  
Notes
2004-01-05 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FLA. ADMIN. CODE
 FLA. STATUTES
  
 1) ORIGINAL SIGNATURE REQUIRED ON ALL
 SEALED PLANS. FS481.221 & FS 471.025.
 SIGNATURES ARE COPIES OR STAMPS OF THE
 SIGNATURES.
 2) ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME, ADDRESS, AND LICENSE NUMBER
 ON EACH SHEET. IF PRACTICING THROUGH A
 DULY AUTHORIZED ENGINEERING BUSINESS,
 ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME AND LICENSE NUMBER, AS WELL AS. THE
 NAME, ADDRESS, AND CERTIFICATE OF AUTH-
 ORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. 61G15-23.002(2)
 FS 471.025.
 3) A DRINKING FOUNTAIN IS REQUIRED PER
 TABLE 403.1. (ALSO SEE SECTION 410.1)
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]