Plan Review Details - Permit 03120778
Plan Review Stops For Permit 03120778
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2004-05-05 Cont ID  
Sent By csiegber Date 2004-08-03 Time 11:31 Rev Time 1.25
Received By alange Date 2004-05-05 Time 10:15 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2005-06-24 Cont ID  
Sent By dpalmer Date 2005-06-24 Time 12:22 Rev Time 0.30
Received By dpalmer Date 2005-06-24 Time 12:21 Sent To  
Notes
2005-06-24 00:00:00************ UNSAT ***************
  
 1)NOTE: PLEASE SEE REVISED PLANS/RISER
 DIAGRAM HAS NOW COME IN BY A NEW
 ARCHITECT. PLEASE SEE PLANS OF RECORD
 ARE DONE BY A COMPLETELY DIFFERENT ARCH.
 IF ORIGINAL ARCH IS NO LONGER ARCH OF
 RECORD, THEN ALL NEW ARCHITECTUAL PLANS
 WILL BE REQUIRED FOR COMPLETE SCOPE. A
 LTR FROM THE OWNERIS ALSO REQUIRED IF
 ORIG ARCH IS BEING RELEASED OR A LTR
 FROM ORIG ARCH RELENQUISHING DUTIES AS
 ARCH OF RECORD. IN EITHER CASE, LTRS ARE
 REQUIRED TO BE ORIGINAL AND NOTORIZED
 UNDER FS 117.
 FS 481
  
 PLEASE NOTE: THERE ARE CODE COMMENTS FOR
 REVSIONS SUBMITTED , HOWEVER THESE ARE
 NOT COMMENTED AT THIS TIME DUE TO ABOVE
 COMMENT.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2004-07-19 Cont ID  
Sent By dpalmer Date 2004-07-19 Time 14:38 Rev Time 0.50
Received By dpalmer Date 2004-07-19 Time 14:38 Sent To B
Notes
2004-07-19 00:00:00ARCH CAME IN AND CORRECTED PLANS.
  
 SENT TO AL FOR PROCESSING OF PLANS.

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2004-07-12 Cont ID  
Sent By dpalmer Date 2004-07-12 Time 18:23 Rev Time 0.50
Received By dpalmer Date 2004-07-12 Time 18:11 Sent To M
Notes
2004-07-12 00:00:00*********** UNSAT ****************
 ********** UNSAT 4TH TIME ***********
  
 1)NOTE: PLEASE SEE LOAD CALCULATIONS
 STILL NOT MEET 220.31B.
 PLEASE SEE COMMENTS FROM PREVIOUS REVIEW
 -S.
 DERATING OF LOADS ON PANEL 'B' IS BEING
 TAKEN TWICE. THIS IS NOT PERMITTED.
  
  
 2)NOTE: PER LAST CONVERSATION WITH
 MR JAMES DEMARS, HIS LEGAL SIGNATURE
 WOULD BE USED UPON SIGNING AND SEALING
 OF PLANS. SIGNATURE ON PLANS DO NOT
 CORRELATE WITH PREVIOUS LETTERS.
 MR. DEMARS WAS TOLD HIS LEGAL SIGNATURE
 WAS REQUIRED PER FLORIDA STATUES. HE WAS
 ASKED TO SIGN AS PREVIOUS CORRESPONDENCE
 LETTER PERTAINING TO THE 4X FEE.
 THIS IS REQUIRED ON ALL SHEETS AND FOR
 ALL TRADES THAT CONTAIN A TITLE BLOCK
 FOR ARCHITECT OF RECORD.
 FS 481.221.
  
 PLEASE SEE A 4X FEE WILL BE PENDING PER
 MEETING WITH NEIL MELICK BLDG OFFICAL.
 ONE COPY OF ELECTRICAL PLANS ARE BEING
 REATINED FOR RECORD AND SHALL BE PLACED
 INTO PREVIOUS FILE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
 PLEASE CALL IN ORDER TO SET UP A MEETING
 IF SO DESIRED.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2004-06-16 Cont ID  
Sent By csiegber Date 2004-07-09 Time 09:40 Rev Time 1.00
Received By dpalmer Date 2004-06-16 Time 18:30 Sent To P
Notes
2004-06-16 00:00:00************ UNSAT 3 TIME ***********
  
 PLEASE SEE NOTES FROM PREVIOUS TWO
 REVIEWS.
  
 1)NOTE: PLEASE SUBMIT LOAD CALCUALTIONS
 TO MEET 2002 NEC.ART 220
 PLEASE SEE ADDTIONAL LOADS BEING ADDED
 TO EXISTING DO NOT FALL UNDER THE SAME
 LOAD CALCULATIONS AS NEW.
 PLEASE SEE 220.31B. PLEASE SEE LOADS
 ON PLANS/PANELS DO NOT MEET 220.
  
 2)NOTE: PLEASE SEE NOTE #9, THIS STILL
 SHOWS SD'S TO BE WIRED AHEAD OF SWITCH-
 -ING ON BATH AND KIT LIGHTING CIRCUIT,
 AND BEDRMSD TO BE ARC FAULT.?
 PLEASE SEE ALL SD'S ARE REQUIRED TO BE
 WIRED IN-LINE W/ EACH OTHER. IF SD'S IN
 BEDROOMS ARE REQUIRED TO BE ARC FAULT
 PROTECTED, THIS WOULD BE THAT ENTIRE
 BRANCH CIRCUIT. NOT JUST THAT SD.
  
 3)NOTE: PLEASE SEE NOTICE WAS GIVEN TO
 DESIGN PROFESSIONAL ON PREVIOUS REVIEW
 PERTAINING TO FS 553.80(2)(B).
 WHICH REQUIRES: " THE LOCAL GOVERMENT
 SHALL IMPOSE, EACH TIME AFTER THE THIRD
 SUCH REVIEW THE PLANS ARE REJECTED FOR
 THAT CODE VIOLATION A FEE OF FOUR TIMES
 THE AMOUNT OF THE PORTION OF THE PERMIT
 FEE ATTRIBUTED TO PLAN REVIEW".
 PLEASE SEE ATTACHED BZ 242709 $1,227.98
 THIS FEE MUST BE PAID BEFORE PLANS MAY
 BE RESUBMITTED FOR REVIEW.
 ONE SET OF ELECTRICAL PLANS ARE BEING
 RETAINED FOR FILE.
  
 PLEASE SEE THESE NOTES MUST BE ADDRESSED
 IF THERE ARE ANY QUESTIONS,PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-05-19 Cont ID  
Sent By csiegber Date 2004-06-11 Time 16:18 Rev Time 0.75
Received By dpalmer Date 2004-05-19 Time 08:49 Sent To M
Notes
2004-05-19 00:00:00********** UNSAT *************
  
 1)NOTE: PLEASE SEE NOTES ON FIRST REVIEW
 PERTAINING TO ELECTRICAL LOAS CALCULAT-
 IONS PER NEC 220.
 PLEASE SUBMIT LOAD CALCS TO MEET 220 FOR
 RESIDENTIAL.
  
 2)NOTE: PLEASE SEE NOTE# 9 MENTIONS
 SMOKE DETECTORS TO BE ON BATH/KIT CIR-
 -CUIT, PLEASE SEE 2002 NEC, ALL OUTLETS,
 RECETPS/LTS, FANS AND SMOKE DETECTORS
 MUST BE ON ARC FAULT CIRCUITS.
 SD WILL BE REQ'D IN THIS ADAPTABLE
 SLEEPING ROOM.
  
 3)NOTE: PLEASE SUBMIT NOTORIZED LETTER
 FOR SIGNATURE. MUST CONTAIN ALL LEGAL
 INFORMATION THAT IS REQ'D OF NOTARY.
 MUST ALSO BE SIGNED AND SEALED PER ARCH.
 PLEASE ALSO REMOVE NOTE IN THE MIDDLE
 OF ELECTRICAL PLANS WHICH HAS NOTHING
 TO DO WITH ELECTRICAL CODE COMPLIANCE.
 ANY RESPONSE TO BLDG DEPT COMMENTS MAY
 BE DONE IN A PROFESSIONAL MANNER IN
 LETTER FORM.
 WE WILL BE RETAINING ONE COPY OF EACH
 ELECTRICAL SUBMITTED PLANS FOR RECORD.
  
 4)NOTE: PLEASE SEE NOTE #6 FROM FIRST
 REVIEW. SHOWS ATTACHED TO GRND ROD AND
 COLD WATER BUT NOT TO REQ'D FOOTER STEEL
 PER 250.50
  
 5)NOTE: PLEASE SEE ATTACHED COPY OF
 FS 553.80(2)(B) WITH RESPECT TO DESIGN
 PROFESSIONALS.
  
  
 PLEASE REMOVE ALL/OLD VOIDED SHEEST AND
 ONLY INSERT NEW SHEETS FOR TWO COMPLETE
 SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-05-04 Cont ID  
Sent By csiegber Date 2004-05-18 Time 16:02 Rev Time 0.50
Received By dpalmer Date 2004-05-04 Time 07:15 Sent To P
Notes
2004-05-04 00:00:00************ UNSAT *************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 2 )NOTE: PLEASE SUBMIT LOAD CALCULATIONS
 PER PER 220. LOADS FROM PANEL "B" CAN
 NOT BE DERATED TWICE.
 PLEASE ALSO SEE LOADS FOR A/C'S PER
 220.
  
 3)NOTE: PLEASE SEE 424.3B FOR OCP OF
 8KW HEAT.
  
 4)NOTE: SD REQ'D IN CABANA RM. THIS IS
 AN ADAPTABLE SLEEPING RM PER NFPA-72
  
 5)NOTE: PLEASE ALSO PROVIDE ARC FAULT
 PROTECTION PER 210.12. 2002 NEC.
  
 6)NOTE: PLEASE SHOW GROUNDING FOR PANEL
 'B' TO BOND TO NEW FOOTER STEEL AND ANY
 METALLIC WATER PIPE.
 250.50/250.32
  
 7)NOTE: PLEASE PROVIDE COPY OF DRVIERS
 LICENSE FOR VERIFICATION OF LEGAL
 SIGNATURE. WE HAVE NOW STARTED A FILE
 FOR ARCH'S AND ENGINEER'S SIGNATURES.
 THIS MUST BE HOW LICENSE WAS SIGNED WITH
 THE STATE. ANY PERSONEL INFORMATION LIKE
 ADDRESS AND LICENSE # MAY BE CROSSED OUT
 FS 481.221
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2005-06-16 Cont ID  
Sent By shill Date 2005-06-16 Time 12:29 Rev Time 0.00
Received By shill Date 2005-06-16 Time 12:29 Sent To E
Notes
2005-06-16 00:00:00TO DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2004-08-03 Cont ID  
Sent By csiegber Date 2004-08-03 Time 11:31 Rev Time 0.00
Received By csiegber Date 2004-08-03 Time 11:31 Sent To B
Notes
2004-08-03 00:00:00TO AL DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2004-07-09 Cont ID  
Sent By csiegber Date 2004-07-09 Time 09:40 Rev Time 0.00
Received By csiegber Date 2004-07-09 Time 09:40 Sent To E
Notes
2004-07-09 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2004-06-11 Cont ID  
Sent By csiegber Date 2004-06-11 Time 16:18 Rev Time 0.00
Received By csiegber Date 2004-06-11 Time 16:18 Sent To E
Notes
2004-06-11 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-05-18 Cont ID  
Sent By csiegber Date 2004-05-18 Time 16:02 Rev Time 0.00
Received By csiegber Date 2004-05-18 Time 16:02 Sent To E
Notes
2004-05-18 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-05-17 Cont ID  
Sent By csiegber Date 2004-05-17 Time 09:03 Rev Time 0.00
Received By csiegber Date 2004-05-17 Time 09:03 Sent To Z
Notes
2004-05-17 00:00:00RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-04-30 Cont ID  
Sent By csiegber Date 2004-04-30 Time 14:40 Rev Time 0.00
Received By csiegber Date 2004-04-30 Time 14:40 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-03-25 Cont ID  
Sent By mmclean Date 2004-04-30 Time 14:16 Rev Time 0.00
Received By csiegber Date 2004-03-25 Time 11:20 Sent To Z
Notes
2004-03-25 00:00:00RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-12-16 Cont ID  
Sent By csiegber Date 2003-12-16 Time 10:03 Rev Time 0.00
Received By csiegber Date 2003-12-16 Time 10:03 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2004-07-14 Cont ID  
Sent By pkrauss Date 2004-07-14 Time 07:26 Rev Time 0.25
Received By pkrauss Date 2004-07-14 Time 07:13 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2004-06-29 Cont ID  
Sent By dpalmer Date 2004-07-12 Time 18:23 Rev Time 0.25
Received By pkrauss Date 2004-06-29 Time 14:25 Sent To  
Notes
2004-06-29 00:00:00PLANS ARE NOT SIGNED, SEALED BY THE
 ARCHITECT.PLEASE HAVE ARCHITECT
 APPROVE THE PLANS OR REMOVE TITLE BLOCK.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-05-27 Cont ID  
Sent By jleech Date 2004-06-28 Time 19:39 Rev Time 0.30
Received By pkrauss Date 2004-05-27 Time 07:19 Sent To P
Notes
2004-05-27 00:00:00DENIED:
 ENERGY CALCULATIONS INDICATE A "NEW
 SINGLE FAMILY", SHOULD READ NEW
 ADDITION.THE ENERGY CALCULATIONS
 INDICATE A UNDUCTED SYSTEM AND THE
 PLANS INDICATE A SPLIT SYSTEM.PLEASE
 CORRECT ENERGY CALCULATIONS.
  
 BATHROOM SHALL HAVE A WINDOW WITH A
 MINIMUM OF 3 SQ FT OPEN SPACE OR HAVE
 MECHANICAL EXHAUST 2001 FBC(M) 402.3.1
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-06-28 Cont ID  
Sent By jleech Date 2004-06-28 Time 19:39 Rev Time 0.25
Received By jleech Date 2004-06-28 Time 19:39 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-05-29 Cont ID  
Sent By dpalmer Date 2004-06-16 Time 18:54 Rev Time 0.33
Received By jleech Date 2004-05-29 Time 09:37 Sent To B
Notes
2004-05-29 00:00:00SHOW SINK ON RISER DIAGRAM.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 3 Status P Date 2004-08-03 Cont ID  
Sent By sgraham Date 2004-08-03 Time 11:13 Rev Time 0.00
Received By sgraham Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2004-04-30 Cont ID  
Sent By csiegber Date 2004-05-17 Time 09:03 Rev Time 0.00
Received By mmclean Date 2004-04-30 Time 14:16 Sent To I
Notes
2004-04-30 00:00:00DENIED, CONVENANT TO RESTRICT USE OF
 ACCESSORY STRUCTURE.MINIMUM 6"
 SEPARATION BETWEEN ROOM OF HOUSE WALKING
 SEE ROBIN SINGER 659-8031 MM

Review Stop Z ZONING
Rev No 1 Status F Date 2003-12-17 Cont ID  
Sent By csiegber Date 2004-03-25 Time 11:20 Rev Time 0.00
Received By mmclean Date 2003-12-17 Time 11:24 Sent To  
Notes
2003-12-17 00:00:00CALLED CONTR AND REQUESTED 2 COPY OF
 LEGAL SURVEY FILE T MM