Plan Review Details - Permit 03120697
Plan Review Stops For Permit 03120697
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2005-01-14 Cont ID  
Sent By alange Date 2005-01-14 Time 09:05 Rev Time 0.50
Received By alange Date 2005-01-14 Time 09:05 Sent To  
Notes
2005-01-14 00:00:00RESTAMP OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-04-05 Cont ID  
Sent By alange Date 2004-04-05 Time 09:40 Rev Time 1.00
Received By alange Date 2004-04-05 Time 09:40 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-03-19 Cont ID  
Sent By alange Date 2004-03-19 Time 08:28 Rev Time 0.50
Received By alange Date 2004-03-19 Time 08:28 Sent To  
Notes
2004-03-19 00:00:00DENIED
 1.NONE OF THE CORRECTIONS HAVE BEEN
 MADE TO THE 2-18-04 BUILDING PLAN
 REVIEW.SEE ATTACHED REVIEW.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-02-18 Cont ID  
Sent By kstevens Date 2004-03-18 Time 12:29 Rev Time 2.00
Received By alange Date 2004-02-18 Time 10:30 Sent To  
Notes
2004-02-18 00:00:00DENIED
 1. THE NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY
 COURTHOUSEAND A COPY SUBMITTED TO THIS
 OFFICE
 BEFORE A PERMIT CAN BE ISSUED.BLANK
 FORMS ARE AVAILABLE FROM THIS OFFICE.
 2.SUBMIT 2 COPIES OF ALL PRODUCT
 APPROVALS REQUIRED.CARADCO NOT LISTED
 ON THE FBC PRODUCT APPROVAL SITE.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1,
 2003ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATIONPLEASE SEE THE STATE WEBSITE
 AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
 3.ENERGY CALCULATIONS NOT SIGNED.
 4.BUILDING IN IN FLOOD ZONE "A"
 SUBMIT AN ELEVATION CERTIFICATE.
 5.FBC 3401.7.2.6WHEN ALTERATIONS
 AMOUNTING TO MORE THAN 50% OF THE VALUE
 OF THE EXISTING BUILDING DURING A 12
 MONTH PERIOD, THE BUILDING SHALL BE
 MADE TO CONFORM TO THE REQUIREMENTS FOR
 A NEW BUILDING.
 IMPROVED VALUE 90,498 PROJECT
 VALUE 97,000
 ART LANGE
 BUIDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2005-05-12 Cont ID  
Sent By btrobaug Date 2005-05-12 Time 13:33 Rev Time 0.50
Received By btrobaug Date 2005-05-12 Time 13:07 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2005-04-07 Cont ID  
Sent By btrobaug Date 2005-04-07 Time 10:01 Rev Time 0.50
Received By btrobaug Date 2005-04-07 Time 09:08 Sent To  
Notes
2005-04-07 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} ANY REVISIONS MADE TO AN ENGINEERED
 SET OF WRAWINGS MUST BE MADE BY THE
 DESIGNER OF RECORD. F.S.471.
  
 2} CU #2 NEEDS A DISCONNECT.
  
 3} 210.63 RECEP @CU EQUIP.
  
 4} COMPLY WITH 210.52(E).
  
 5} COMPLY WITH 905.2.2 FBC RE: SD'S @
 STAIRWELLS.
  
 6} 210.52(D) SECOND FLOOR BATH.
  
 7} 905.2.2 2ND FLOOR STAIRS.
  
 PLEASE SEE APPROVED PLANS AND CORRELATE
 WITH REVISIONS BEFORE RESUBMITTING.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status N Date 2004-04-03 Cont ID  
Sent By btrobaug Date 2004-04-03 Time 07:58 Rev Time 0.33
Received By btrobaug Date 2004-04-03 Time 07:41 Sent To  
Notes
2004-04-03 00:00:00ROUTED TO ELEC IN ERROR./WRT.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-03-17 Cont ID  
Sent By alange Date 2004-03-30 Time 09:55 Rev Time 0.50
Received By btrobaug Date 2004-03-17 Time 13:57 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-02-09 Cont ID  
Sent By csiegber Date 2004-03-11 Time 12:32 Rev Time 0.75
Received By btrobaug Date 2004-02-09 Time 12:56 Sent To P
Notes
2004-02-09 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE RISER DIAGRAM SHOWS #3/0 FEEDERS
 TO PANEL "A",THE PANEL SCHEDULE
 INDICATES #2/0,PLEASE CORRELATE.
  
 2} PLEASE CHECK ELECTRICAL NOTES. #16
 SPECS.#12 WIRE,BUT PANEL SCHEDULE SHOWS
 #14. #37 SHOULD REFER TO 250.66 FOR GEC
 ART.
  
 3} THE OVERHEAD RISER WOULD APPEAR TO BE
 IN VIOLATION OF 230.9(A) AND/OR (B).SEE
 SHEET A-4 ELEVATION. INDICATE
 COMPLIANCE.
  
 4} PLEASE SEE RECEPTS SERVING
 KITCHEN COUNTERSPACE TO MEET 210.52C-
 SEC'S 1,2,3,4 AND 5
  
 5} PLEASE SHOW OUTLET SPACING PER
 210.52. 2',6',12' RULE.SEVERAL LOCATIONS
 DO NOT COMPLY, SEE REVIEWED SET.
  
 6} THE CONDENSER DISCONNECTS DO NOT
 APPEAR TO COMPLY WITH 110.26.
  
 7} SMOKE DETECTORS AT THE STAIRWELLS TO
 COMPLY WITH 905.2.2 FBC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2005-05-05 Cont ID  
Sent By adarroug Date 2005-05-05 Time 14:25 Rev Time 0.00
Received By adarroug Date 2005-05-05 Time 14:25 Sent To E
Notes
2005-05-05 00:00:00TO "BTROBAUG" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-03-31 Cont ID  
Sent By adarroug Date 2005-03-31 Time 13:35 Rev Time 0.00
Received By adarroug Date 2005-03-31 Time 13:35 Sent To E
Notes
2005-03-31 00:00:00TO "DPALMER" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-01-10 Cont ID  
Sent By mjacobs Date 2005-01-10 Time 12:12 Rev Time 0.00
Received By mjacobs Date 2005-01-10 Time 12:12 Sent To B
Notes
2005-01-10 00:00:00TO "AL" DESK/RESTAMP.

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-10-25 Cont ID  
Sent By csiegber Date 2004-10-25 Time 13:42 Rev Time 0.00
Received By csiegber Date 2004-10-25 Time 13:42 Sent To M
Notes
2004-10-25 00:00:00TO PK BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-03-30 Cont ID  
Sent By alange Date 2004-03-30 Time 09:55 Rev Time 0.00
Received By alange Date 2004-03-30 Time 09:55 Sent To E
Notes
2004-03-30 00:00:00TO BT DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-03-11 Cont ID  
Sent By csiegber Date 2004-03-11 Time 12:32 Rev Time 0.00
Received By csiegber Date 2004-03-11 Time 12:32 Sent To E
Notes
2004-03-11 00:00:00TO BT DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-02-06 Cont ID  
Sent By csiegber Date 2004-02-06 Time 10:48 Rev Time 0.00
Received By csiegber Date 2004-02-06 Time 10:48 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-03-03 Cont ID  
Sent By csiegber Date 2004-02-06 Time 10:48 Rev Time 0.00
Received By csiegber Date 2004-02-03 Time 16:41 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-11-05 Cont ID  
Sent By pkrauss Date 2004-11-05 Time 09:03 Rev Time 0.35
Received By pkrauss Date 2004-11-05 Time 09:02 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-02-11 Cont ID  
Sent By csiegber Date 2004-10-25 Time 13:43 Rev Time 0.40
Received By pkrauss Date 2004-02-11 Time 15:34 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-03-18 Cont ID  
Sent By kstevens Date 2004-03-18 Time 12:29 Rev Time 0.33
Received By kstevens Date 2004-03-18 Time 12:29 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-02-09 Cont ID  
Sent By btrobaug Date 2004-03-17 Time 14:13 Rev Time 1.00
Received By kstevens Date 2004-02-09 Time 16:07 Sent To M
Notes
2004-02-09 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SHT P-3 SANT. RISER DIAGRAM, MASTER
 BATH SHOWER SHALL BE MINIMUM OF 2" PIPE
 TABLE 709.1
 2) SHT P-3 SANT. RISER DIAGRAM, WASH
 MACHINE REQUIRES A STANDPIPE, AND THE
 CLEANOUT SHALL BE LOCATED MINIMUM OF 4
 FEET ABOVE FLOOR. 406.3 - 708.10
 3) SHT P-3 WATER RISER DIAGRAM, AIR
 CHAMBERS ARE NOT APPROVED. 604.9 PLEASE
 DELETE FROM RISER.
 4) SHT P-3 WATER HEATER DETAIL, WATER
 HEATERS INSTALLED ABOVE THE GROUND FLOOR
 SHALL BE INSTALLED IN A PAN. 804.5
 5) SHT P-3 WATER HEATER DETAIL, THERMAL
 EXPANSION CONTROL REQUIRED IF THERE IS A
 RPZ BACKFLOW ON THE WATER SERVICE TO THE
 RESIDENCE. 607.3.2
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2004-02-05 Cont ID  
Sent By csiegber Date 2004-02-06 Time 10:48 Rev Time 0.00
Received By csiegber Date 2004-02-05 Time 10:47 Sent To I
Notes
2004-02-06 00:00:00PER MM STAMPED PLANS/DEE