Plan Review Details - Permit 03120591
Plan Review Stops For Permit 03120591
Review Stop B BUILDING (STRUCTURAL)
Rev No 11 Status P Date 2005-08-02 Cont ID  
Sent By jwitmer Date 2005-08-02 Time 06:35 Rev Time 0.00
Received By pschmitz Date 2005-09-30 Time 15:08 Sent To PC
Notes
2005-08-02 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03120591
 ADD: 533 CLEMATIS ST.
 CONT: SHAKMAN
 TEL: (561)239- 9018
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 SUBMITTAL SHOP DRAWINGS REVIEW
 ACTION: REVIEWED/ PROVISO
 AUGUST 02/05
 1) PLANS DO NOT INDICATE THE SIZE OF THE
 FORMED BY THE TRIANGULAR AREA FORMED BY
 THE TREAD, RISER AND BOTTOM OF GUARD
 RAIL. 1015.6 (1)A 6 INCH (152 MM)
 SPHERE SHALL NOT PASS THROUGH THE
 TRIANGULAR OPENING FORMED BY A TREAD,
 RISER AND BOTTOM OF A GUARDRAIL.
  
 2) PLANS DO NOT INDICATE HANDRAILS OR
 EXTENTIONS: 11-4.9.4(2) IF HANDRAILS ARE
 NOT CONTINUOUS, THEY SHALL EXTEND AT
 LEAST 12 INCHES (305 MM) BEYOND THE
 TOP RISER AND AT LEAST 12 INCHES
 (305 MM) PLUS THE WIDTH OF ONE TREAD
 BEYOND THE BOTTOM RISER.AT THE
 TOP, THE EXTENSION SHALL BE PARALLEL
 WITH THE FLOOR OR GROUND SURFACE.
 AT THE BOTTOM, THE HANDRAIL SHALL
 CONTINUE TO SLOPE FOR A DISTANCE OF
 THE WIDTH OF ONE TREAD FROM THE
 BOTTOM RISER; THE REMAINDER OF THE
 EXTENSION SHALL BE HORIZONTAL (SEE
 FIGURE 11-19(C) AND
 FIGURE 11-19(D)).HANDRAIL
 EXTENSIONS SHALL COMPLY WITH 11-4.4.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 10 Status F Date 2005-07-22 Cont ID  
Sent By jwitmer Date 2005-07-22 Time 10:27 Rev Time 0.55
Received By jwitmer Date 2005-07-22 Time 10:27 Sent To PC
Notes
2005-07-22 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03120591
 ADD: 533 CLEMATIS ST.
 CONT: SHAKMAN
 TEL: (561)239- 9018
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 SUBMITTAL SHOP DRAWINGS REVIEW
 ACTION: DENIED
  
 1) PLANS DO NOT INDICATE THE SIZE OF THE
 FORMED BY THE TRIANGULAR AREA FORMED BY
 THE TREAD, RISER AND BOTTOM OF GUARD
 RAIL. 1015.6 (1)A 6 INCH (152 MM)
 SPHERE SHALL NOT PASS THROUGH THE
 TRIANGULAR OPENING FORMED BY A TREAD,
 RISER AND BOTTOM OF A GUARDRAIL.
  
 2) PLANS DO NOT INDICATE HANDRAILS OR
 EXTENTIONS: 11-4.9.4(2) IF HANDRAILS ARE
 NOT CONTINUOUS, THEY SHALL EXTEND AT
 LEAST 12 INCHES (305 MM) BEYOND THE
 TOP RISER AND AT LEAST 12 INCHES
 (305 MM) PLUS THE WIDTH OF ONE TREAD
 BEYOND THE BOTTOM RISER.AT THE
 TOP, THE EXTENSION SHALL BE PARALLEL
 WITH THE FLOOR OR GROUND SURFACE.
 AT THE BOTTOM, THE HANDRAIL SHALL
 CONTINUE TO SLOPE FOR A DISTANCE OF
 THE WIDTH OF ONE TREAD FROM THE
 BOTTOM RISER; THE REMAINDER OF THE
 EXTENSION SHALL BE HORIZONTAL (SEE
 FIGURE 11-19(C) AND
 FIGURE 11-19(D)).HANDRAIL
 EXTENSIONS SHALL COMPLY WITH 11-4.4.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status P Date 2005-01-27 Cont ID  
Sent By jwitmer Date 2005-01-27 Time 08:54 Rev Time 0.75
Received By jwitmer Date 2005-01-27 Time 08:50 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2005-01-18 Cont ID  
Sent By jwitmer Date 2005-01-18 Time 08:47 Rev Time 0.75
Received By jwitmer Date 2005-01-18 Time 08:47 Sent To  
Notes
2005-01-18 00:00:0001-18-05 REVISION SUBMIT WINDOW, MULLION
 & EXTERIOR DOOR REVISIONS PLUS SHEET
 S-4.

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2004-11-23 Cont ID  
Sent By jwitmer Date 2004-11-23 Time 08:03 Rev Time 0.25
Received By jwitmer Date 2004-11-23 Time 08:02 Sent To PC
Notes
2004-11-23 00:00:0011-23-04 CERTIFICATION OF CODE
 COMPLIANCE (WELD CERTIFICATION)JW

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2004-10-22 Cont ID  
Sent By jwitmer Date 2004-10-22 Time 12:57 Rev Time 0.55
Received By jwitmer Date 2004-10-22 Time 12:41 Sent To PC
Notes
2004-10-22 00:00:0010-22-04 REV: 9-07-04/ 9-22-04JW

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2004-10-04 Cont ID  
Sent By csiegber Date 2004-10-20 Time 16:51 Rev Time 1.00
Received By jwitmer Date 2004-10-04 Time 13:33 Sent To PC
Notes
2004-10-04 00:00:00REVISION STOREFRONT ARCH ALUMINIUMJW

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2004-08-25 Cont ID  
Sent By csiegber Date 2004-09-22 Time 14:53 Rev Time 0.55
Received By jwitmer Date 2004-08-25 Time 10:03 Sent To  
Notes
2004-08-25 00:00:00REVISIONS A) LETTER FOR 2X8 FLOOR JOIST
 B) FOOTER & COLUMN REVISION

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-06-30 Cont ID  
Sent By csiegber Date 2004-08-20 Time 11:36 Rev Time 0.00
Received By jwitmer Date 2005-01-27 Time 08:49 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-06-19 Cont ID  
Sent By jwitmer Date 2004-06-19 Time 08:35 Rev Time 2.22
Received By jwitmer Date 2004-06-19 Time 08:14 Sent To PC
Notes
2004-06-19 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03120591
 ADD: 533 CLEMATIS ST
 CONT: SHAKMAN CONSTRUCTION
 TEL: (561)756-0540
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 2ND REVIEW
 ACTION: DENIED
  
 NOTE: THIS REVIEW IS THE RESULTS OF A
 MEETING WITH SHERRY PILAND/ NEIL MELICK
 AS TO WHAT PARTS OF THE BUILDING WILL
 FALL UNDER THE HISTORIC PERVIEW AND
 WHAT
 PARTS WILL FALL UNDER BUILDING FOR
 REVIEW.
  
 1) COMMENT# 4 FROM PREVIOUS REVIEW:
 903.8.1 BUILDINGS 3 STORIES OR MORE.
 ANY
 BUILDING 3 STORIES SHAL BE EQUIPPED
 WITH
 AN APPROVED AUTOMATIC FIRE SPRINKLER
 SYSTEM INSTALLED IN ACCORDANCE WITH
 903.1
 RESPONCE: EXISTING SYSTEM, GC TO SUBMIT
 FIRE SPRINKLER DRAWINGS AS PART OF THIS
 SUBMITTAL.
 NO FIRE SPRINKLER PLANS WERE SUBMITTED!
  
 2) COMMENT# 14 FROM PREVIOUS REVIEW:
 FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS: STOREFRONT SYSTEM
 RESPONCE: GC SHALL SUBMIT THE TEST
 REPORTS REQUIRED FOR THESES ITEMS.
 NO PRODUCT TESTING REPORTS SUBMITTED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1,
 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 3) COMMENT #20 FROM PREVIOUS REVIEW
 DEALS WITH REINFORCED AREAS FOR
 ADAPTABLE BATHROOMS THERE IS NO
 INFORMA-
 TION FOR BACKING FOR THE SHOWER, TAKEN
 FROM FLORIDA ACCESSIBILITY CODE AND THE
 FAIR HOUSING CODE.
  
 4) COMMENT #21 FROM PREVIOUS REVIEW:
 DEALS WITH THE FIRST FLOOR ENTRY DOORS.
 SHEET A-0 INDICATES THAT THERE IS A
 2'-6" SET BACK, SHEET A2.1 INDICAES A
 PAIR OF 3'-0" OVERHANGING INTO THE
 RIGHT OF WAY 6".
  
 5) GUIDELINES FOR REHABILITING HISTORIC
 BUILDINGS, FLORIDA BUILDING CODE,APPX.
 D
 THE SAME MEETING BETWEEN NEIL MELICK,
 SHERRY PILAND AND MYSELF, IT WAS
 DISCUSS
 ED THAT THE WINDOWS WOULD NOT BE
 REPLACED, HISTORIC RECOMMENDATIONS. THE
 TOPIC OF ENERGY RETROFITTING WAS
 DISCUSS
 ED. SINCE THE WINDOWS WERE NOT TO BE
 RE-
 PLACED IT WAS DETERMINED TO HELP MAKE
 THE BUILDING MORE ENERGY EFFICIENT AND
 WORK ING WITH THE EXISTING WINDOWS, TO
 IMPROVE THERMAL EFFICIENCY WITH
 WEATHER-
 STRIPPING, CAULKING, INTERIOR SHADES,
 AND IF HISTORICLLY APPROPRIATE, BLINDS
 AND AWNINGS.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-01-13 Cont ID  
Sent By jwitmer Date 2004-01-13 Time 13:34 Rev Time 3.33
Received By jwitmer Date 2004-01-13 Time 12:43 Sent To  
Notes
2004-01-13 00:00:00 
 BUILDING PLAN REVIEW
 PERMIT: 03120591
 ADD: 533 CLEMATIS STREET
 CONT: SHAKMAN CONSTRUCTION
 TEL: (561)239-9018
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST BUILDING REVIEW:
 ACTION: DENIED
 NOTE:
 3401.7.2.6 WHEN REPAIRS AND ALTERA-
 TIONS AMOUNTING TO MORE THAN 50% OF THE
 VALUE OF THE EXISTING BUILDING ARE MADE
 DURING ANY 12 MONTH PERIOD, THE BUILDING
 OR STRUCTURE SHALL BE MADE TO CONFORM TO
 THE REQUIREMENTS FOR A NEW BUILDING OR
 STRUCTURE OR BE ENTIRELY DEMOLISHED.
  
  
 1)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 A SURVEY OR PLOT PLAN INDIATING THE PROP
 ERTY LINES, AND THE DISTANCE AWAY FROM
 THE PROPERTY LINE?THE DISTANCE THE
 BUILDING STEPS BACK AT THE 2ND AND 3RD
 FLOORS? WINDOW SIZES VS WALL %/ FLOOR.
 705.1.1.2 EVERY EXTERIOR WALL WITHIN
 15' OF A PROPERTY LINE SHALL BE EQUIPPED
 WITH APPROVED OPENING PROTECTIVES.
  
 2)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 STAIR# 2, IS THIS A FIRE ESCAPE OR CON-
 SIDERED A EXTERIOR STAIR? A EXTERIOR
 STAIR SHALL COMPLY WITH 1006.2.4, WITH
 OPENING PROTECTIVES.
  
 3) STAIR# 2 EXIT DOOR ON THE 2ND & 3RD
 FLOORS, 1012.1.4 DURING ITS SWING, ANY
 DOOR IN A MEANS OF EGRESS SHALL LEAVE
 UNOBSTRUCTED AT LEAST 1/2 OF THE
 REQUIRED WIDTH OF LANDING.
  
 4) 903.8.1 BUILDINGS 3 STORIES OR MORE.
 ANY BUILDING 3 STORIES OR MORE IN HEIGHT
 SHALL BE EGUIPPED WITH AN APPROVED AUTO-
 MATIC SPRINKLER SYSTEMINSTALLED IN
 ACCORDANCE WITH 903.1. A STRAIGHT
 NFPA 13 SYSTEM WILL BE REQUIRED.
  
 5) EXISTING STAIRS, 1007.1.1(3) EXTERIOR
 AND INTERIOR EXIT STAIRWAYS SHALL BE CON
 STRUCTED OF NONCOMBUSTIBLE MATERIALS
 THROUGHOUT IN THE FOLLOWING BUILDINGS:
 (3) ALL OTHER BUILDINGS 3 STORIES OR
 MORE IN HEIGHT OR OCCUPIED BY MORE THAN
 40 PERSONS ABOVE OR BELOW THE LEVEL OF
 EXIT DISCHARGE.
  
 6) DISCREPANCY, SHEET A2.0 NOTE 11 INDI-
 CATES THAT THIS FLOOR WILL REMAIN A WOOD
 FLOOR SYSTEM VS S1,NOTE THIS AREA TO
 REMAIN "EXPOSED EARTH SLAB"?
  
 7) SHEET A-2.0 DEMO NOTES, INDICATE THE
 USE OF CALCULTED FLOOR ASSEMBLIES
 709.6.2.1, WHAT THE PLANS DO NOT INDI-
 CATE IS THE FASTENING SCHEDULE FOR THE
 3 LAYERS OF DRYWALL.
  
 8) DRAFTSTOPPING 2305.2.2(2) FLOOR/
 CEILING ASSEMBLIES,(2) MULTIFAMILY,
 TWO OR MORE UNITS R2, IN THE FLOOR/
 CEILING ASSEMBLIES ABOVE AND IN LINE
 WITH THE TENANT SEPAERATION, WHEN TENANT
 SEPERATION WALLS DO NOT EXTEND TO THE
 FLOOR SHEATHING ABOVE.
  
 9) SHEET S-2 INDICATES A DETAIL# 4, WOOD
 JOIST TO WALL CONNECTION, WHERE IS THIS
 USED? PLANS INDICATE THE REMOVAL OF
 THREE COURSES (FACE SHELL) HOW WILL THE
 REMAINDER OF THE WALL BE HELD IN PLACE?
  
 10) SHEET S-2 DETAIL# "CONNECTION A"
 THIS DETAIL INDICATES THE USE OF HILTI
 HIT SYSTEM, IS THIS TO GO INTO THE
 TERRA COTTA BLOCK, THE REMOVAL OF THE
 FACE SHELL IS DESIGNATED FOR THE OPPO-
 SITE SIDE OF THE WALL, ALSO HOW MANY
 COURSES ABOVE AND BELOW THIS SYSTEM?
  
 11) SHEET S-2 INDICATES HOW THE ELEVATOR
 PENTHOUSE IS TO BE BUILT, SIDEWALLS,
 PLYWOOD, TYPE V BUILDING SIDEWALLS ARE
 TO BE NONCOMBUSTIBLE.
  
 12) S-3 INDICATES THE LIVE LOADS FOR THE
 2ND & 3RD STORY AS 80 LBS FOR LIVE,
 STAIRS ARE TO BE 100 LBS/ SQ FT.
  
 13) STAIRWELL PROTECTION.
 SHEET M.2.1 3RD FLOOR STAIR WELL HAS A
 12"X12" RA RUNNING THROUGH THE STAIRWELL
 1006.1.3.1 PENETRATIONS INTO &
 THROUGH A STAIRWELL ENCLOSURE ASSEMBLY
 ARE PROHIBITED EXCEPT FOR REQUIRED EXIT
 DOORS, DUCTWORK & EQUIPMENT FOR INDE-
 PENDENT STAIR PRESSURIZATION, SPRINKLER
 PIPING, STANDPIPES AND ELECTRICAL CON-
 DUIT SERVING THE STAIRWAY AND TERMINAT-
 ING AT A STEEL BOX NOT EXCEEDING 16 SQ
 INCHES.
  
 14)FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS: FRONT ENTRY DOORS
  
 15) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 16)1503.4.2 OVERFLOW DRAINS SHALL BE
 THE SAME SIZE AS ROOF DRAINS, INSTALLED
 WITH THE INLET FLOW LINE LOCATED 2"
 ABOVE THE LOWEST POINT OF THE ROOF LINE.
 OVERFLOW SCUPPERS SHALL BE A MINIMUM OF
 4"IN HEIGTH AND SHALL BE PLACED IN WALLS
 OR PARARETS WITH THE INLET FLOW LINE
 NOT LESS THAN 2" ABOVE THE ROOF SURFACE.
  
 17) 1503.4.4 PROTECTION AGAINST DECAY &
 TERMITES. CONDENSATE LINES & ROOF DOWN
 SPOUTS SHALL DISCHARGE AT LEAST 1 FT.
 AWAY FROM THE STRUCTURE SIDEWALL,
 WHETHER BY UNDERGROUND PIPING, TAIL EX-
 TENSIONS, OR SPLASH BLOCKS.
  
 18)1511.7 ROOF MOUNTED MECHANICAL UNIT
 S SHALL BE MOUNTED ON CURBS RAISED A
 MINIMUM OF 8 INCHES ABOVE THE ROOF SUR-
 FACE, OR WHERE ROOFING MATERIALS EXTEND
 BENEATH THE UNIT, ON RAISED EQUIPMENT
 SUPPORTS PROVIDING A MINIMUM CLEARENCE
 HEIGHT IN ACCORDANCE WITH TABLE 1511.7.
 MECH. 301.13 WIND RESISTANCE
 MECHANICAL EQUIPMENT, APPLIANCES AND SUP
 PORTS THAT ARE EXPOSED TO WIND SHALL BE
 DESIGNED AND INSTALLED TO RESIST THE
 WIND PRESSURES ON THE EQUIPMENT & THE
 SUPPORTS AS DETERMINED IN ACCORDANCE
 WITH THE FL BLD CODE. THIS MAY BE ACCOMP
 LISHED BY DESIGN OR BY APPLICATION OF
 SECTION 301.13.1.
  
 19) FAIR HOUSING ACCESSIBLE ROUTE 4.3
 SHOW AN ACCESSIBLE ROUTE FOR THE SITE.
 INDICATE THE HANDICAPPED PARKING, ACCESS
 ISLES, AND ROUTE TO THE ELEVATOR. ALSO
 PROVIDE INFORMATION FOR ROUTE FOR PUBLIC
 TRANSPORTATION.
 INDICATE ALL SIDEWALKS, RAMPS,
 STAIRS, AND CURB CUTS.4.4/ 4.5
  
 20) SHEET A2.5 WATER CLOSET GRAB BARS,
 THE DETAIL INDICATES A 24" SIDE GRAB BAR
 BUT FIG 604.5.1 INDICATES A MINIMUM OF
 42" PLUS 12" FROM THE BACK WALL.
  
 21) SHEET A-6.1 FIRST FLOOR FRONT ENTRY
 DOORS VS PROPERTY LINE NOT GIVEN.
 3203.1 DOORS SHALL NOT OPEN OR
 PROJECT UPON PUBLIC PROPERTY.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2005-08-18 Cont ID  
Sent By dpalmer Date 2005-08-18 Time 19:30 Rev Time 0.30
Received By dpalmer Date 2005-08-18 Time 19:30 Sent To  
Notes
2005-08-18 00:00:00REDLINED 620.23 AND 620.24
 LTS FOR BOTH STILL SHOWN ON ONE CIRCUIT
 FOR LIGHTING.

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2005-08-11 Cont ID  
Sent By dpalmer Date 2005-08-11 Time 14:04 Rev Time 1.50
Received By dpalmer Date 2005-08-11 Time 13:38 Sent To  
Notes
2005-08-11 00:00:00********** PROVISO ***********
  
 1)NOTE: PLEASE SEE ELEVATRO MACHINE ROOM
 AND PIT REQUIRES EACH A SEPARATE BRANCH
 CIRCUIT FOR LIGHTING AND RECEPTS.
 PLEASE ALSO SEE MISSING GFI RECEPT TO BE
 LOCATED ON ELEVATOR MACHINE RM.
 620.23,620.24
  
 2)NOTE: PLEASE SEE EM LTS AND EXT LTS
 REFERENCE TO A NOTE #2 TYP.
 PLEASE SEE NOTE #2 ON "FIRST AND SECOND
 FLR NOTES"REFERS TO ALL EM/EXT LTS TO
 BE WIRED AHEAD OF APT UNIT LIGHTING
 SWITCHES.
 PLEASE SEE 210.25, COMMON AREA BRANCH
 CIRCUITS MAY NOT BE CIRCUITED TO
 DWELLING/APT UNITS.
 PLEASE SEE PLANS FOR COMMON AREA APPEAR
 TO BE CIRCUITED CORRECTLY TO A HOUSE
 PANEL.
  
 PLEASE SUBMIT THE ABOVE INFORMATION.
 NOTE #1 TO BE REVISED ON PLANS,CAN BE 8
 1/2 X 11'S FOR REVISED PANEL SCHEDULE
 AND ELEV RM LAYOUTS.
 NOTE #2 CAN BE REVISED IN LTR FORM.
  
 PLEASE SUBMIT BEFORE FINAL/CO.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2005-01-31 Cont ID  
Sent By dpalmer Date 2005-01-31 Time 08:53 Rev Time 0.33
Received By dpalmer Date 2005-01-31 Time 08:41 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2004-06-25 Cont ID  
Sent By dpalmer Date 2004-06-25 Time 15:52 Rev Time 0.33
Received By dpalmer Date 2004-06-25 Time 15:51 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2004-06-07 Cont ID  
Sent By dpalmer Date 2004-06-07 Time 14:15 Rev Time 0.75
Received By dpalmer Date 2004-06-07 Time 14:15 Sent To  
Notes
2004-06-07 00:00:00*************** UNSAT **************
  
 1)NOTE: IN RESPONSE TO PREVIOUS NOTES,
 A CERTIFICATE OF AUTHORIZATION # WAS ADD
 -ED TO SHEETS. THE FIRM NAME CORRESPOND-
 ING TO THAT CA# HAS NOW CHANGED.
 PLEASE SEE SOME SHEETS STILL CONTAIN
 OTHER FIRM NAME AND PLEASE SEE TITLE
 BLOCK ALSO CONTAINS OLD FIRM NAME EVEN
 ON REVISED SHEETS.
 OLD SHEETS WERE NOT CORRECTED.
 PLEASE SEE FS 471.023/ FAC 61G15-23.002
 THIS IS REQUIRED ON ALL SHEETS WHEATHER
 OR NOT COMMENT IS MADE FROM OTHER REVIEW
 -ERS.
  
  
  
 2)NOTE: PLEASE SEE NEW ELECTRICAL SHEETS
 ARE NOW SEALED BY A NEW ENGINEER AND OLD
 SHEETS CONTAIN A DIFFERENT ENGINEER?
 PLEASE SEE FS 471.025 WHICH REQUIRES A
 "SIGNATURE". THIS SIGNATURE MUST BE AS
 SHOWN ON SEAL. NEW ENGINEERFIRST NAME
 ONLY CONTAINS AN INITIAL. PLEASE SIGN
 W/ LEGAL SIGNATURE.
  
 3)NOTE: NOTE: ARC FAULT PROTECTION WILL
 BE REQ'D FOR SD'S IN SLEEPING AREAS
 PER 210.12 EVEN IF ON KITCHEN LT CIRCUIT
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLYINSERT NEW SHEETS INTO COMPLETE
 SETS FOR REVIEW AND STAMPING.
 ONE SET OF OLD SHEETS MAY BE SUBMITTED
 FOR REFERENCE. SOME REVIEWS MAY REQUIRE
 THIS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-03-03 Cont ID  
Sent By dpalmer Date 2004-03-03 Time 11:29 Rev Time 1.50
Received By dpalmer Date 2004-03-03 Time 10:43 Sent To  
Notes
2004-03-03 00:00:00************* UNSAT ***************
  
 1)NOTE: PLEASE PLUMB COMMENTS ON FIRST
 REVIEW. TITLE BLOCKS ARE REQ'D TO HAVE
 ALL LICENSE #'S AS REQ'D UNDER
 FS 471.023 BE LISTED. THIS IS REQ'D FOR
 ALL SHEETS AND ALL TRADES. COMMENT WAS
 NOT MADE BY ELECTRICAL REVIEW DUE TO
 PLUMB MAKING COMMENT.
 PLEASE NOTE: COMMENT IS NOW BEING MADE
 BY ELECTRICAL AND NOT PLUMB HOWEVER
 THIS IS REQ'D PER FAC 61G15-23.002 FOR
 ALL.
  
 2)NOTE: PLEASE SEE PLANS NOW SHOW CIR-
 -CUITING AS REQUESTED ON FIRST REVIEW.
 PLEASE SEE 210.11C1, PLANS SHOW ONLY
 ONE SMALL APPLIANCE CIRCUIT.
  
 3)NOTE: PLEASE SEE 220.16A FOR MIN LOAD
 TO BE IN LOAD CALCULATIONS.
 SHOWN AS 1 KVA?
  
 4)NOTE: PLEASE CORRELATE CIRCUITS ON
 PLANS WITH PANEL SCHEDULE. PLEASE SEE
 SD'S AND STILL SHOWN ON WITH KITCHEN
 LTS? CIRCUIT # SEEMS TO AHVE BEEN
 CHANGED ON PLAN, BUT NOT PANEL SCHEDULES
  
 5)NOTE: PLEASE SEE EQUIPMENT GROUNDING
 CONDUCTORS HAVE NOW BEEN ADDED, HOWEVER
 PLEASE SEE 250.24. EQUIPMENT GROUNDING
 CONDUCTORS ARE ONLY INSTALLED AFTER THE
 FIRST MEANS OF DISC. AS SHOWN PARALLELS
 THE NEUTRAL. 250.6
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-12-23 Cont ID  
Sent By dpalmer Date 2003-12-23 Time 13:19 Rev Time 1.00
Received By dpalmer Date 2003-12-23 Time 13:18 Sent To  
Notes
2003-12-23 00:00:00*************** UNSAT **************
  
 PLEASE SEE COMMENTS FROM OTHER PLANS
 REVIEWERS, AS THEY MAY HAVE AN AFFECT ON
 ELECTRICAL PLANS.
  
 1)NOTE: PLEASE SEE 210.52 FOR RECEPT
 SPACING. SEE W/IN 6' OF EDGE OF WALL AND
 2' OF WALL.
  
 2)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS. PLEASE SEE SOME MISSING.
 APT 2-1, APT 2-2.
  
 3)NOTE: PLEASE SEE 700.12E FOR CIRCUIT-
 -ING OF EM/EXT LTS.
  
 NOTE # 2 NOT PERMITTED.
 4)NOTE: PLEASESHOWS SD'S AS REQUIRED
 PER NFPA-8-1.
 PLEASE ALSO SEE 210.12 FOR CIRCUITING
 OF SD'S. PANEL SCHEDULE SHOWS SD'S W/
 KITCHEN LTS.
  
 5)NOTE: PLEASE SEE 250.24 FOR PLACEMENT
 OF EQUIPMENT GROUNDING CONDUCTOR.
 NONE UNTIL AFTER THE FIRST MEANS OF
 DISC.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-9717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2005-02-14 Cont ID  
Sent By nmccray Date 2005-02-14 Time 14:53 Rev Time 0.00
Received By nmccray Date 2005-02-14 Time 14:53 Sent To  
Notes
2005-02-14 00:00:00REVISION DATED 01-20-05

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2004-07-08 Cont ID  
Sent By nmccray Date 2004-07-08 Time 14:57 Rev Time 0.00
Received By nmccray Date 2004-07-08 Time 14:57 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-02-20 Cont ID  
Sent By mcarsill Date 2004-02-20 Time 16:03 Rev Time 0.00
Received By mcarsill Date 2004-02-20 Time 16:03 Sent To  
Notes
2004-02-20 00:00:00PLANS ARE APPROVED PROVISO IF ACCEPTED
 BY THE CONSTRUCTION SERVICES DEPT.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-12-18 Cont ID  
Sent By mcarsill Date 2003-12-18 Time 16:33 Rev Time 0.00
Received By mcarsill Date 2003-12-18 Time 16:32 Sent To  
Notes
2003-12-18 00:00:001) TACTILE SIGNAGE IS REQUIRED AT
 STAIRWELL DOORS.
  
 2) ALL SHAFTWAYS THAT ARE LARGE ENOUGH
 FOR PERSONS TO FALL INTO MUST BE MARKED
 "SHAFTWAY" WITH 6" HIGH LETTERS.
  
 3) NO FIRE SPRINKLER PLANS PROVIDED
 WITH DRAWINGS.
  
 4) PLEASE INDICATE ON THE PLANS, THE
 REQUIRED EMERGENCY LIGHTS WITHIN STAIRS
 1 & 2.
  
 5) PLEASE PROVIDE MORE DETAILS FOR
 NOTE # 4 ON PAGE A-6.1.
  
 6) A KNOX-BOX WILL BE REQUIRED FOR
 THE BUILDING.
  
 7) ELEVATOR WARNING SIGNS ARE REQUIRED
 FOR THE BUILDING AT EACH ELEVATOR
 OPENING.
  
 8) NO ELEVATION DRAWINGS PROVIDED WITH
 PLANS.
  
 9) WHY ARE THE JANITOR'S CLOSET AND
 LAUNDRY ROOM DOORS NOT FIRE RATED.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 17 Status N Date 2005-09-07 Cont ID  
Sent By adarroug Date 2005-09-07 Time 08:40 Rev Time 0.00
Received By adarroug Date 2005-09-07 Time 08:40 Sent To M
Notes
2005-09-07 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 16 Status N Date 2005-08-31 Cont ID  
Sent By adarroug Date 2005-08-31 Time 10:54 Rev Time 0.00
Received By adarroug Date 2005-08-31 Time 10:54 Sent To P
Notes
2005-08-31 00:00:00TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 15 Status N Date 2005-08-10 Cont ID  
Sent By adarroug Date 2005-08-10 Time 17:22 Rev Time 0.00
Received By adarroug Date 2005-08-10 Time 17:22 Sent To E
Notes
2005-08-10 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 14 Status N Date 2005-07-06 Cont ID  
Sent By adarroug Date 2005-07-06 Time 14:46 Rev Time 0.00
Received By adarroug Date 2005-07-06 Time 14:46 Sent To B
Notes
2005-07-06 00:00:00TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2005-04-19 Cont ID  
Sent By adarroug Date 2005-04-19 Time 15:56 Rev Time 0.00
Received By adarroug Date 2005-04-19 Time 15:56 Sent To B
Notes
2005-04-19 00:00:00TO "LMARTINEZ" DESK

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2005-03-01 Cont ID  
Sent By adarroug Date 2005-03-01 Time 16:14 Rev Time 0.00
Received By adarroug Date 2005-03-01 Time 16:14 Sent To M
Notes
2005-03-01 00:00:00TO "M"BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2005-02-22 Cont ID  
Sent By adarroug Date 2005-02-22 Time 16:16 Rev Time 0.00
Received By adarroug Date 2005-02-22 Time 16:16 Sent To M
Notes
2005-02-22 00:00:00TO "M" BOX/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2005-01-25 Cont ID  
Sent By mjacobs Date 2005-01-25 Time 10:18 Rev Time 0.00
Received By mjacobs Date 2005-01-25 Time 10:13 Sent To  
Notes
2005-01-25 00:00:00TO "COMM BD#47"/REV.

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2004-12-29 Cont ID  
Sent By mjacobs Date 2004-12-29 Time 13:38 Rev Time 0.00
Received By mjacobs Date 2004-12-29 Time 13:38 Sent To B
Notes
2004-12-29 00:00:00TO "JW" DESK.

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2004-11-19 Cont ID  
Sent By csiegber Date 2004-11-19 Time 14:25 Rev Time 0.00
Received By csiegber Date 2004-11-19 Time 14:25 Sent To B
Notes
2004-11-19 00:00:00TO JW DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2004-10-20 Cont ID  
Sent By csiegber Date 2004-10-20 Time 16:51 Rev Time 0.00
Received By csiegber Date 2004-10-20 Time 16:51 Sent To B
Notes
2004-10-20 00:00:00TO JW DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2004-09-22 Cont ID  
Sent By csiegber Date 2004-09-22 Time 14:53 Rev Time 0.00
Received By csiegber Date 2004-09-22 Time 14:53 Sent To B
Notes
2004-09-22 00:00:00TO JW DESK/SUBMITTAL
 STOREFRONT PA & STOREFRONT SHO DRAWINGS

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-08-20 Cont ID  
Sent By csiegber Date 2004-08-20 Time 11:36 Rev Time 0.00
Received By csiegber Date 2004-08-20 Time 11:36 Sent To B
Notes
2004-08-20 00:00:00TO JW DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-06-25 Cont ID  
Sent By csiegber Date 2004-06-25 Time 12:37 Rev Time 0.00
Received By csiegber Date 2004-06-25 Time 12:37 Sent To  
Notes
2004-06-25 00:00:00TO COMM BD#39

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-05-24 Cont ID  
Sent By alange Date 2004-05-24 Time 13:13 Rev Time 0.00
Received By alange Date 2004-05-24 Time 13:12 Sent To  
Notes
2004-05-24 00:00:00TO COMM BD #51

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-02-19 Cont ID  
Sent By csiegber Date 2004-02-19 Time 15:53 Rev Time 0.00
Received By csiegber Date 2004-02-19 Time 15:52 Sent To  
Notes
2004-02-19 00:00:00TO COMM BD#16

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-01-13 Cont ID  
Sent By csiegber Date 2004-02-19 Time 15:52 Rev Time 0.00
Received By csiegber Date 2003-12-11 Time 16:21 Sent To  
Notes
2003-12-11 00:00:00TO COMM BD#9

Review Stop M MECHANICAL (A/C)
Rev No 7 Status P Date 2005-09-07 Cont ID  
Sent By tgordon Date 2005-09-07 Time 10:57 Rev Time 0.20
Received By tgordon Date 2005-09-07 Time 10:57 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2005-03-04 Cont ID  
Sent By pkrauss Date 2005-03-04 Time 07:40 Rev Time 0.55
Received By pkrauss Date 2005-03-04 Time 07:05 Sent To  
Notes
2005-03-04 00:00:00PROVISO:
 1.A MINIMUM OF 4" AROUND THE AHU IS
 REQUIRED PER 2001 FBC(M)603.1.3.
 2.AUXILIARY DRAIN PAN WITH OVERFLOW
 PROTECTION REQUIRED PER 2001
 FBC(M)307.2.3.
 3.DRYER EXHAUST SHALL TERMINATE
 OUTSIDE THE BUILDING AND BE NON-SCREENED
 WITH A BACKDRAFT DAMPER PER 2001
 FBC(M)504.4.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status F Date 2005-02-03 Cont ID  
Sent By pkrauss Date 2005-02-03 Time 07:11 Rev Time 1.00
Received By pkrauss Date 2005-02-03 Time 07:11 Sent To  
Notes
2005-02-03 00:00:00DENIED:
 1.PLAN SHEET M2.1 SECOND AND THIRD
 FLOOR, AHU2-3 & 3-3,THE OUTSIDE AIR
 APPEARS TO TERMINATE IN THE KITCHEN.
 OUTSIDE AIR IS TO BE DUCTED TO A CLOSE
 PROXIMITY OR INTO THE RETURN AIR SO THE
 OUTSIDE AIR WILL BE CIRCULATED THROUGH
 THE AHU.
  
 2.RETURN AIR TO RTU-1 IS NOT SIZED
 PROPERLY.PER 2001 FBC(M)601.4,
 BALANCED RETURN REQUIRED.
  
 3.RETURN AIR GRILLE TO RTU-1 IS
 TERMINATING AT A RATED WALL BUT A FIRE
 DAMPER IS NOT INDICATED.
  
 4.PLANS DO NOT INDICATE THE VENTING
 OR TERMINATION OF THE DRYER EXHAUST.
 PLEASE CLARIFY.
  
 PLEASE NOTE, LOUVERED DOOR IS PART OF
 THE RETURN AIR PLENUM AND SHALL BE NON
 COMBUSTIBLE PER 2001 FBC(M)602.2.1.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2004-07-01 Cont ID  
Sent By pkrauss Date 2004-07-01 Time 15:44 Rev Time 0.45
Received By pkrauss Date 2004-07-01 Time 15:44 Sent To  
Notes
2004-07-01 00:00:00PROVISO:
 1.PER FAIR HOUSING ACT; SEE PLAN SHEET
 A2.4 FIGURE 2 FOR HEIGHT REQUIREMENTS
 FOR ENVIRONMENTAL CONTROLS AND SWITCHES.
  
 2.AUXILIARY DRAIN PAN WITH OVERFLOW
 PROTECTION REQUIRED PER 2001 FBC(M)
 307.2.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2004-06-10 Cont ID  
Sent By pkrauss Date 2004-06-10 Time 12:20 Rev Time 0.40
Received By pkrauss Date 2004-06-10 Time 10:47 Sent To  
Notes
2004-06-10 00:00:00DENIED:
 SEE COMMENT #1 BY DEWEY PALMER,
 ELECTRICAL PLAN REVIEW.PLANS ARE
 OTHERWISE CODE COMPLIANT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2004-03-04 Cont ID  
Sent By pkrauss Date 2004-03-04 Time 07:01 Rev Time 0.45
Received By pkrauss Date 2004-03-04 Time 06:53 Sent To  
Notes
2004-03-04 00:00:00DENIED:
 1.REFERENCE RESPONSE LETTER,
 MECHANICAL; COMMENT/RESPONSE #2 -
 OUTSIDE AIR PROVIDED THROUGH HALLWAY.
 PER 2001 FBC(M) 403.2.1 #1 VENTILATION
 AIR SHALL NOT BE RECIRCULATED FROM ONE
 DWELLING TO ANOTHER OR DISSIMILAR
 OCCUPANCIES.
  
 2.REFERENCE RESPONSE LETTER,
 MECHANICAL - RESPONSE TO COMMENT #5,
 VERTICAL RUNS MOVERD TO A FIRE RATED
 SHAFT WEST OF THE ELEVATOR.PLANS DO
 NOT INCLUDE A DETAIL OR UL # FOR THE
 SHAFT ASSEMBLY.PLEASE PROVIDE DETIALS
 FOR THE CONSTURCTION OF THE SHAFT.
  
 3.COMMENT/RESPONSE #7, REFRIGERANT
 LINES MOVED INTO SHAFT.PLEASE NOTE
 SHAFT ENCLOSURE SHALL BE FIRE-RESISTANT
 AND VENTED TO THE OUTSIDE OR TO THE
 SPACE SERVED BY THE SYSTEM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-12-29 Cont ID  
Sent By pkrauss Date 2003-12-29 Time 12:44 Rev Time 1.35
Received By pkrauss Date 2003-12-29 Time 12:44 Sent To  
Notes
2003-12-29 00:00:00DENIED:
 PLEASE PROVIDE THE FOLLOWING INFORMATION
 FOR REVIEW:
 1.OUTSIDE AIR CALCULATIONS PER 2001
 FBC(M) TABLE 403.3.
  
 2.INDICATE LOCATION OF THE OUTSIDE AIR
 DUCT TO THE AHU'S LOCATED ON THE 2ND
 FLOOR.
  
 3.PROVIDE MINIMUM VENTILATION REQUIRE-
 MENTS FOR THE 1ST FLOOR PER 403.4.1.
  
 4.PLAN SHEET M2.1 INDICATES THE SUPPLY
 AND RETURN DUCTS FROM RTU-1 PENETRATING
 THROUGH A STAIR WELL ENCLOSURE.PER
 2001 FBC 1006.1.3.1, DUCTWORK IS NOT
 ALLOWED TO PENETRATE A STAIRWAY
 ENCLOSURE, PLEASE CLARIFY.
  
 5.PLAN SHEET M2.1 DUCTWORK FROM RTU-1,
 DUCTS PENETRATING ONLY ONE FLOOR OF A
 BUILDING REQUIRING THE PROTECTION OF
 VERTICAL OPENINGS SHALL HAVE A FIRE
 DAMPER.DUCTS THAT PENETRATE MORE THAN
 ONE FLOOR SHALL BE PROTECTED BY A SHAFT
 ENCLOSURE PER 2001 FBC(M) 607.1.2 #3 &
 607.4 RESPECTIVELY.
  
 6.PLAN SHEET M6.1 CONDENSING UNIT
 DETAIL, HEIGHT REQUIREMENT FROM THE
 ROOF SURFACE TO THE BOTTOM OF THE
 SUPPORT RAIL SHALL COMPLY WITH 2001 FBC
 1511.7.
  
 7.REFRIGERANT PIPING SHALL COMPLY WITH
 15-1992 SUB SECTION 11.12.3(B) & 11.12.4
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 6 Status P Date 2005-09-30 Cont ID  
Sent By pschmitz Date 2005-09-30 Time 15:09 Rev Time 0.00
Received By pschmitz Date 2005-09-30 Time 15:09 Sent To  
Notes
2005-09-30 00:00:00REVISION, WATER HAMMER ARRESTORS

Review Stop P PLUMBING
Rev No 5 Status P Date 2005-09-20 Cont ID  
Sent By kstevens Date 2005-09-20 Time 13:41 Rev Time 1.25
Received By kstevens Date 2005-09-20 Time 13:41 Sent To  
Notes
2005-09-20 00:00:00REVISION #8 APPROVED FOR SHEETS P2.1,
 P2.2, P5.1, & P5.2. SHEET P5.3 REVISION
 DENIED. REMOVED ALL REQUIRED WATER
 HAMMER ARRESTORS FROM RISER DIAGRAMS.
 SECTION 604.9

Review Stop P PLUMBING
Rev No 4 Status P Date 2004-07-08 Cont ID  
Sent By kstevens Date 2004-07-08 Time 11:50 Rev Time 3.50
Received By kstevens Date 2004-07-08 Time 11:50 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2004-06-15 Cont ID  
Sent By kstevens Date 2004-06-15 Time 17:43 Rev Time 0.50
Received By kstevens Date 2004-06-15 Time 17:43 Sent To  
Notes
2004-06-15 00:00:00DENIED
 REFERENCE: FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME, ADDRESS AND LICENSE NUMBER ON EACH
 SHEET. IF PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS, ENGIN-
 EERS, ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME AND LICENSE NUMBER, AS WELL
 AS, THE NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. A TITLE BLOCK
 WILL SATISFY THIS REQUIREMENT. FAC
 61G15-23.002(2) - FS 471.025
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2004-02-28 Cont ID  
Sent By kstevens Date 2004-02-28 Time 10:08 Rev Time 1.00
Received By kstevens Date 2004-02-28 Time 10:08 Sent To  
Notes
2004-02-28 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 A) COMMENT #4 FROM PREVIOUS REVIEW NOT
 COMPLETLY ANSWERED. SHT P5.2 REMOVAL OF
 HUB DRAIN AND CONDENSATE LINE DRAINING
 IN TO IT IS NOT DELETED AS SUGGESTED.
 B) COMMENT #5 FROM PREVIOUS REVIEW:
 WORK SHEET FROM RODNEY COMPO REQUIRED AT
 TIME OF PERMIT ISSUANCE. PLEASE SUBMIT.
 C) COMMENT #6 FROM PREVIOUS REVIEW RE-
 SPONSE NOTED, BUT AIR CHAMBERS ARE STILL
 SHOWN ON WATER RISER DIAGRAMS. ALSO THE
 WATER HAMMER ARRESTORS SHALL BE SHOWN ON
 THE RISER DIAGRAM AT THE W/M, D.W. & THE
 ICE MAKER.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-12-22 Cont ID  
Sent By kstevens Date 2003-12-22 Time 14:13 Rev Time 2.00
Received By kstevens Date 2003-12-22 Time 14:13 Sent To  
Notes
2003-12-22 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLA. ADMIN. CODE
 FLA. STATUTES
  
 1) SHT A2.2 SUBMIT CALCULATIONS FOR
 PRIMARY AND SECONDARY ROOF DRAINS PER
 SECTIONS 1106, AND 1107 WITH ALL SUBSEC-
 TIONS FOR EXISTING ROOF. SHOW 1/2 AREA
 OF ALL VERTICAL WALLS & AREA OF ROOFS
 THAT DRAIN DOWN TO THE ROOF FROM ABOVE.
 INDICATE SIZE OF DOWNSPOUTS & SUBMIT A
 DETAIL FOR ALL OPENINGS IN THE PARAPET
 WALLS SHOWING ALL DIMENTIONS. IF PRIMARY
 AND SECONDARY DRAINS DRAIN THROUGH THE
 SAME OPENING, THE OPENING SHALL BE SIZED
 ACCORDINGLY.
 2) SHT P0.1 GENERAL SPECIFICATIONS #2, &
 PLUMBING LEGEND. AIR CHAMBERS ARE NOT
 APPROVED, DELETE FROM PLANS. 604.9
 3) SHT P0.1 DEMO NOTES: ALL CAPPED AND
 ABANDONED PLUMBING LINES SHALL BE INSP-
 ECTED PRIOR TO COVERING.
 4) SHT P2.1 HUB DRAIN IN SPRINKLER CON-
 TROL ROOM #103 SHOWS 1" CONDENSATE
 DRAINING INTO IT. CONDENSATE SHALL DRAIN
 SEPARATELY OUTSIDE OF THE BLDG. AND TIE
 INTO STORM, A CATCH BASIN, OR A DRY WELL
 A RELIEF VENT IS REQUIRED AS CONDENSATE
 EXITS THE BLDG. SAFE WASTE'S ARE NOT
 APPROVED. SECTION 90-125(5) CITY CODE.
 5) GREASE INTERCEPTOR SHALL BE SIZED BY
 UTILITY DEPT. CONTACT RODNEY COMPO, EN-
 VIRONMENTAL COMPLIANCE, INDUSTRIAL PRE-
 TREATMENT WASTE ORD. 2938-96 (561) 837-
 4074.
 6) SHT P5.3 ALL WATER RISER DIAGRAMS,
 AIR CHAMBERS ARE NOT APPROVED, DELETE
 FROM RISERS. WATER HAMMER ARRESTORS RE-
 QUIRED BY 604.9 (ICE MAKERS/WASHMACHINES
 & DISH WASHERS), SHALL BE LOCATED NEAR
 THE FIXTURES IN AN "EFFECTIVE RANGE" NOT
 IN THE CEILING AT THE TOP OF THE DROPS.
 7) SHTS P5.3 & P0.1 SUBMIT MANUF. SPECS.
 SHEETS FOR TANKLESS WATER HEATER. MUST
 SHOW LISTING FOR W/H.
 8) IF PRACTICING THROUGH A DULY AUTHOR-
 IZED ENGINEERING BUSINESS, ENGINEERS
 SHALL INDICATE THEIR CERTIFICATE OF
 AUTHORIZATION ON THE TITLE BLOCK OF EACH
 SHEET. 61G15-23.002(2) & FS 471.025
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]