| Plan Review Stops For Permit 03120577 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2004-02-26 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2004-02-26 |
Time |
15:48 |
Rev Time |
0.50 |
| Received By |
jwitmer |
Date |
2004-02-26 |
Time |
15:48 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2004-01-15 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2004-01-15 |
Time |
16:44 |
Rev Time |
0.50 |
| Received By |
jwitmer |
Date |
2004-01-15 |
Time |
16:44 |
Sent To |
|
|
| Notes |
| 2004-01-15 00:00:00 | COMMENTS SAME FROM 1ST REVIEW, | | | PLANS INDICATE REVISED ON 01/05/04 | | | AND BUILDING REVIEW COMPLETED ON 1/13/04 | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2004-01-13 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2004-01-13 |
Time |
11:57 |
Rev Time |
0.75 |
| Received By |
jwitmer |
Date |
2004-01-13 |
Time |
11:57 |
Sent To |
PC |
|
| Notes |
| 2004-01-13 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT: 03120577 | | | ADD: 107 N OLIVE AVE | | | CONT: LWP CONSTRUCTION SERVICES INC | | | TEL: (321)436-9394 | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | | | | 1ST REVIEW | | | ACTION: DENIED | | | | | | 1) PLANS, SPECIFICATIONS,REPORTS OR | | | OTHER DOCUMENTS PREPARED BY THE DESIGN | | | PROFESSIONAL AND BEING FILED FOR PUBLIC | | | RECORD SHALL HAVE THE SIGNATURE AND | | | SEAL OF THE DESIGN PROFESSIONAL AFFIXED | | | TO THE DOCUMENT. | | | FL STATE STAT: 61G15-23.002 ENGINEERS | | | FL ATATE STAT: 61G16.003 ARCHITECTS | | | | | | 2)FL BLD CODE 104.2.1.2 | | | ADDITIONAL INFORMATION REQUIRED, | | | SHEET# 08 INDICATES A RAISED WATER HEAT- | | | ER PLATFORM, NO DETAIL FOR INSTALATION, | | | DETAILS TO BE APPROVED BY ENGINEER OF | | | RECORD. | | | | | | 3)FL BLD CODE 104.2.1.2 | | | ADDITIONAL INFORMATION REQUIRED, | | | SHEET#09 FRAMING NOTES (1) PREPARATION | | | AREA DETAILS FOR SPECIFICATIONS ON THE | | | FRAMING NEEDEDFOR THE VALENCE AND MENU | | | BOARD, SHEET# 17 HAS NO ADDITIONAL INFO. | | | | | | 4)FL BLD CODE 104.2.1.2 | | | ADDITIONAL INFORMATION REQUIRED, | | | SHEET# 02 GENERAL NOTE# 20, PLANS DO NOT | | | INDICATE IF THE RESTROOM IS TO BE RENO- | | | VATED, NOR DOES THE RESTROOM INDICATE A | | | 5'-0" TURNING RADIUS. WIDTH OF RESTROOM | | | DOOR? | | | | | | 5) 11-4.1.6(2) DUTY TO PROVIDE ACCESS- | | | IBLE FEATURES IN THE EVENT OF DISPROPOR- | | | TIONALITY. INDICATE COMPLIANCE. | | | | | | 6)1204.2 SURROUNDING MATERIALS; | | | THE WALLS & FLOORS OF ALL PUBLIC REST- | | | ROOMS SHALL BE LINED WITH NONABSORBANT | | | MATERIALS TO A HEIGTH OF 4'-0" ABOVE THE | | | FLOOR. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2004-02-19 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-02-19 |
Time |
15:31 |
Rev Time |
0.50 |
| Received By |
dpalmer |
Date |
2004-02-19 |
Time |
15:31 |
Sent To |
|
|
| Notes |
| 2004-02-19 00:00:00 | PLEASE NOTE; PLANS SUBMITTED FOR SIGNS | | | MUST BE SUBMITTED UNDER SEPARATE SIGN | | | PERMIT APPLICATION. | | | | | | | | | IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2004-01-15 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-01-15 |
Time |
08:02 |
Rev Time |
1.00 |
| Received By |
dpalmer |
Date |
2004-01-15 |
Time |
07:41 |
Sent To |
|
|
| Notes |
| 2004-01-15 00:00:00 | ************ UNSAT ***************** | | | | | | 1)NOTE: PLEASE SEE 700.12E FOR CIRCUIT- | | | -ING EM/EXT LTS. | | | | | | 2)NOTE: PLEASE SEE 220.12A FOR MIN LOAD | | | REQUIRED FOR SHOW WINDOW(S). PLEASE SEE | | | THAT PANEL IS ONLY SHOWING ONE CIRCUIT. | | | 200VA PER LINEAR FT. | | | | | | 3)NOTE: PLANS MENTION TO PLACE RECEPTS | | | ABOVE CEILING FOR "PLUG-IN" SIGNAGE. | | | RECEPTS ARE NOT PERMITTED TO BE ABOVE | | | THE DROP CEILING. CORDS MUST BE VISABLE | | | FOR ITS ENTIRE LENGTH. NEC 410 | | | | | | 4)NOTE: PLEASE SEE OCP SHOWN FOR AHU. | | | SHOWS 60A OCP FOR 5KW HEAT. PLEASE | | | VERIFY OCP, MIN IS 125% 424.3B AND MAX | | | TYP IS 150%. | | | | | | 5)NOTE: PLEASE SEE 210.8B3 FOR ALL | | | RECEPTS IN KITCEHN AREA TO BE GFI. | | | PANEL SCHEDULE DOES NOT INDICATE THIS. | | | | | | 6)NOTE: PLEASE VERIFY THREE LOCATIONS | | | FOR CIRCUIT A-17? | | | | | | 7)NOTE: PLEASE ALSO SEE OCP FOR FOR CU | | | SHOWN AT 60A'S. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2003-12-23 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-12-23 |
Time |
16:41 |
Rev Time |
0.33 |
| Received By |
dpalmer |
Date |
2003-12-23 |
Time |
16:41 |
Sent To |
|
|
| Notes |
| 2003-12-23 00:00:00 | *************** UNSAT ************* | | | | | | 1)NOTE: PLANS ARE REQ'D TO BE SIGNED, | | | DATED AND SEALED BY THE ENGINEER OF | | | RECORD. 471.025 | | | PLEASE ALSO SEE THAT ALL SHEETS MUST | | | CONTAIN A TITLE BLOCK AS SET FORTH UNDER | | | FS 471 AND FAC 61G15-23.002 | | | PLEASE PROVIDE ALL LICENSE # 'S AS REQ'D | | | UNDER THE ABOVE REFERENCED FS'S/FAC'S | | | ALL SHEETS/ BOTH SETS. | | | | | | 2)NOTE: PLEASE PROVIDE ALL CIRCUITING | | | ON PLANS AND CORRELATE W/ SUBMITTED | | | PANEL SCHEDULE(S). | | | PLEASE ALSO SUBMIT SIZE OF EXISTING | | | SERVICE AND LOAD CALCULATIONS. 215.5 | | | PLEASE SHOW ALL LOAD CALCS PER 220 | | | PLEASE ALSO SEE 700.12E | | | | | | 3)NOTE: PLEASE SEE 210.62 FOR SHOW | | | WINDOW RECEPT REQUIREMENTS. DIRECTLY | | | ABOVE WINDOW. | | | | | | 4)NOTE: PLEASE SEE 600.5A FOR SIGN | | | CIRCUIT REQUIRED AT ENTRANCE. | | | | | | DUE TO PLANS NOT BEING COMPLETE AT THIS | | | TIME, THERE MAY BE OTHER COMMENTS TO | | | FOLLOW. | | | | | | PLEASE SEE ADMIN CODE 104 FOR CHANGE IN | | | USE AND POSSIBLE WORK THAT MAY BE REQ'D | | | TO BRING SPACE UP TO CODE. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2004-02-20 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2004-02-20 |
Time |
15:55 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2004-02-20 |
Time |
15:55 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2004-01-16 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2004-01-16 |
Time |
15:59 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2004-01-16 |
Time |
15:59 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2003-12-18 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2003-12-18 |
Time |
17:24 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2003-12-18 |
Time |
17:24 |
Sent To |
|
|
| Notes |
| 2003-12-18 00:00:00 | 1) PLANS NOT SIGNED AND SEALED. | | | | | | 2) FIRE SPRINKLER PLANS DO NOT REFLECT | | | FIRE SPRINKLER PROTECTION IN THE | | | BATHROOM. ALSO THE NEW FREEZER SHALL | | | BE FIRE SPRINKLER PROTECTED. | | | | | | 3) PLANS NEED TO INDICATE INTERIOR | | | FINISH CLASSIFICATION INFORMATION | | | FOR WALLS AND CEILINGS. | | | | | | 4) PLEASE INDICATE FIRE EXTINGUISHER | | | LOCATIONS. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2004-02-11 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-02-11 |
Time |
10:51 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-02-11 |
Time |
10:51 |
Sent To |
|
|
| Notes |
| 2004-02-11 00:00:00 | TO COMM BD#27 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2004-01-14 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-01-14 |
Time |
10:03 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-01-14 |
Time |
10:03 |
Sent To |
|
|
| Notes |
| 2004-01-14 00:00:00 | TO COMM BD#2 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2004-01-26 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2004-01-26 |
Time |
07:24 |
Rev Time |
0.00 |
| Received By |
pkrauss |
Date |
2003-12-10 |
Time |
16:48 |
Sent To |
|
|
| Notes |
| 2003-12-10 00:00:00 | TO COMM BD#18 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2004-01-26 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2004-01-26 |
Time |
07:24 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
2004-01-26 |
Time |
07:22 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2003-12-29 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2003-12-29 |
Time |
09:21 |
Rev Time |
0.15 |
| Received By |
pkrauss |
Date |
2003-12-29 |
Time |
09:14 |
Sent To |
|
|
| Notes |
| 2003-12-29 00:00:00 | NO MECHANICAL PLANS SUBMITTED FOR REIVEW | | | PLEASE PROVIDE THE FOLLOWING INFORMATION | | | WITH MECHANICAL PERMIT APPLICATION. | | | 1.OUTSIDE AIR CALCULATIONS PER 2001 | | | FBC(M) 403.3. | | | | | | 2.EQUIPMENT SCHEDULE - INDICATE | | | LOCATION OF CONDENSER UNITS SHOULD A | | | SPLIT SYSTEM BE INSTALLED. | | | | | | 3.PROVIDE MANUFACTURER SUBMITTAL DATA | | | FOR THE FREEZER/REFRIGERATOR & DELI | | | COOLER. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2004-02-27 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2004-02-27 |
Time |
17:35 |
Rev Time |
1.00 |
| Received By |
kstevens |
Date |
2004-02-27 |
Time |
17:35 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2004-02-23 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2004-02-23 |
Time |
10:54 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2004-02-23 |
Time |
10:54 |
Sent To |
|
|
| Notes |
| 2004-02-23 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FLORIDA ADMIN. CODE | | | FLORIDA STATUTES. | | | | | | COMMENTS FROM PREVIOUS REVIEWS HAVE NOT | | | BEEN ADDRESSED: (12-22-03 & 1-24-04) - | | | NUMBERS WILL BE THE SAME FOR CLAIRITY. | | | 2) CONTACT RODNEY COMPO, ENVIRONMENTAL | | | COMPLIANCE, FOR GREASE INTERCEPTOR RE- | | | QUIREMENTS. WASTE ORD. #2938-96 - (561) | | | 837-4074. | | | 6) SHT 24 FLOOR DRAINS ARE NOT APPROVED | | | FOR INDIRECT WASTE. FLOOR SINKS ARE RE- | | | QUIRED PER SECTION 802.3 | | | 7) ALL SHEETS - THE DATE THAT THE SIGNA- | | | TURE AND SEAL IS AFFEIXE AS PROVIDED | | | HEREIN SHALL BE ENTERED ON SAID PLANS | | | IMMEDIATELY UNDER THE SIGNATURE OF THE | | | PROFESSIONAL ENGINEER. 61G15-23.002(1) | | | AND FS 471.025. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2004-01-24 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2004-01-24 |
Time |
07:01 |
Rev Time |
1.00 |
| Received By |
kstevens |
Date |
2004-01-24 |
Time |
07:01 |
Sent To |
|
|
| Notes |
| 2004-01-24 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | FLORIDA ADMIN. CODE | | | FLORIDA STATUTES | | | | | | COMMENTS FROM PREVIOUS REVIEW HAVE NOT | | | BEEN ADDRESSED: (12-22-03) - NUMBERS | | | WILL BE THE SAME FOR CLAIRITY. | | | 1) ROUTE PLANS TO THE DEPT. OF BUSINESS | | | REGULATION HOTEL & RESTURANT DIVISION | | | FOR REVIEW PRIOR TO RESUMBITTING TO THE | | | CITY FOR REVIEW. (954) 958-5520. SECTION | | | 101.4.7 - (PLANS MUST BE STAMPED AND | | | COPIES OF THE SPECIFICATION SHEETS ATT- | | | ACHED TO PLANS). | | | 2) CONTACT RODNEY COMPO, ENVIRONMENTAL | | | COMPLIANCE, FOR GREASE INTERCEPTOR RE- | | | QUIREMENTS. WASTE ORD #2938-96- (561) | | | 837-4074. | | | 5) SHT 08 SANT. RISER DIAGRAM DOES NOT | | | MEET CODE REQUIREMENTS. A TRAP IS REQ- | | | UIRED FOR THE MOP SINK AND BOTH FLOOR | | | SINKS. 1002.1 | | | 6) SHT 24 FLOOR DRAINS ARE NOT APPROVED | | | FOR INDIRECT WASTE. FLOOR SINKS ARE RE- | | | QUIRED PER SECTION 802.3 | | | 7) ALL SHEETS - THE DATE THAT THE SIGNA- | | | TURE AND SEAL IS AFFIXED AS PROVIDED | | | HEREIN SHALL BE ENTERED ON SAID PLANS | | | IMMEDIATELY UNDER THE SIGNATURE OF THE | | | PROFESSIONAL ENGINEER. 61G15-23.002(1) | | | AND FS 471.025. | | | NEW COMMENT******* | | | 1B SEE ATTACHED SHEET CONCERNING FLORIDA | | | STATUTE 533.80(2)(B). | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2003-12-22 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-12-22 |
Time |
08:19 |
Rev Time |
1.00 |
| Received By |
kstevens |
Date |
2003-12-19 |
Time |
18:54 |
Sent To |
|
|
| Notes |
| 2003-12-22 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | FBC-2001 CHAPTER 11 | | | FLA. ADMIN. CODE | | | FLA. STATUTES | | | | | | 1) ROUTE PLANS TO THE DEPT. OF BUSINESS | | | REGULATION HOTEL & RESTURANT DIVISION | | | FOR REVIEW PRIOR TO RESUBMITTING TO THE | | | CITY FOR REVIEW. (954) 958-5520 | | | SECTION 101.4.7 | | | 2) CONTACT RODNEY COMPO, ENVIRONMENTAL | | | COMPLIANCE, INDUSTRIAL PRETREATMENT FOR | | | GREASE INTECEPTOR REQUIREMENTS. WASTE | | | ORD. 2938-96. (561) 837-4074 | | | 3) SHT 04 EQUIPMENT LEGEND #15 NOT LOCA- | | | TED ON FLOOR PLAN. PLEASE CLAIRFY. SEC. | | | 104.2.1 | | | 4) WATER FILTER SHALL COMPLY WITH NSF | | | STANDARDS. SUBMIT MANUF. SPECIFICATION | | | SHEET.SECTION 303.4 | | | 5) SHT 08 SANT. RISER DIAGRAM DOES NOT | | | MEET CODE REQUIREMENTS. A TRAP IS REQ- | | | UIRED FOR THE MOP SINK AND BOTH FLOOR | | | SINKS. 1002.1 | | | 6) SHT 24 FLOOR SINKS ARE NOT APPROVED | | | FOR INDIRECT WASTE. FLOOR SINKS ARE RE- | | | QUIRED PER SECTION 802.3 | | | 7) ALL SHEETS - THE DATE THAT THE SIGNA- | | | TURE AND SEAL IS AFFIXED AS PROVIDED | | | HEREIN SHALL BE ENTERED ON SAID PLANS | | | IMMEDIATELY UNDER THE SIGNATURE OF THE | | | PROFESSIONAL ENGINEER. 61G15-23.002(1) | | | FS 471.025. | | | 8) ALL SHEETS - ENGINEERS SHALL LEGIBLY | | | INDICATE THEIR NAME, ADDRESS AND LICENSE | | | NUMBER ON EACH SHEET. IF PRACTICING | | | THROUGH A DULY AUTHORIZED ENGINEERING | | | BUSINESS, THE NAME, ADDRESS, AND CERTIF- | | | ICATE OF AUTHORIZATION NUMBER OF THE | | | ENGINEERING BUSINESS IS REQUIRED ON EACH | | | SHEET. 61G15-23.002(2) - FS 471.025 | | | 9) SHT 04 SHOW CLEAR FLOOR SPACE AND | | | TURNING AREA IN ACCESSIBLE TOILET ROOM. | | | SECTION 11-4.22.3 | | | 10) RPZ BACKFLOW REQUIRED ON WATER SERV- | | | ICE. SECTION 608.13.2 | | | 11) THERMAL EXPANSION CONTROL REQUIRED | | | PER 607.3.2. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|