Plan Review Details - Permit 03120577
Plan Review Stops For Permit 03120577
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-02-26 Cont ID  
Sent By jwitmer Date 2004-02-26 Time 15:48 Rev Time 0.50
Received By jwitmer Date 2004-02-26 Time 15:48 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-01-15 Cont ID  
Sent By jwitmer Date 2004-01-15 Time 16:44 Rev Time 0.50
Received By jwitmer Date 2004-01-15 Time 16:44 Sent To  
Notes
2004-01-15 00:00:00COMMENTS SAME FROM 1ST REVIEW,
 PLANS INDICATE REVISED ON 01/05/04
 AND BUILDING REVIEW COMPLETED ON 1/13/04
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-01-13 Cont ID  
Sent By jwitmer Date 2004-01-13 Time 11:57 Rev Time 0.75
Received By jwitmer Date 2004-01-13 Time 11:57 Sent To PC
Notes
2004-01-13 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03120577
 ADD: 107 N OLIVE AVE
 CONT: LWP CONSTRUCTION SERVICES INC
 TEL: (321)436-9394
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 2)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 SHEET# 08 INDICATES A RAISED WATER HEAT-
 ER PLATFORM, NO DETAIL FOR INSTALATION,
 DETAILS TO BE APPROVED BY ENGINEER OF
 RECORD.
  
 3)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 SHEET#09 FRAMING NOTES (1) PREPARATION
 AREA DETAILS FOR SPECIFICATIONS ON THE
 FRAMING NEEDEDFOR THE VALENCE AND MENU
 BOARD, SHEET# 17 HAS NO ADDITIONAL INFO.
  
 4)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 SHEET# 02 GENERAL NOTE# 20, PLANS DO NOT
 INDICATE IF THE RESTROOM IS TO BE RENO-
 VATED, NOR DOES THE RESTROOM INDICATE A
 5'-0" TURNING RADIUS. WIDTH OF RESTROOM
 DOOR?
  
 5) 11-4.1.6(2) DUTY TO PROVIDE ACCESS-
 IBLE FEATURES IN THE EVENT OF DISPROPOR-
 TIONALITY. INDICATE COMPLIANCE.
  
 6)1204.2 SURROUNDING MATERIALS;
 THE WALLS & FLOORS OF ALL PUBLIC REST-
 ROOMS SHALL BE LINED WITH NONABSORBANT
 MATERIALS TO A HEIGTH OF 4'-0" ABOVE THE
 FLOOR.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-02-19 Cont ID  
Sent By dpalmer Date 2004-02-19 Time 15:31 Rev Time 0.50
Received By dpalmer Date 2004-02-19 Time 15:31 Sent To  
Notes
2004-02-19 00:00:00PLEASE NOTE; PLANS SUBMITTED FOR SIGNS
 MUST BE SUBMITTED UNDER SEPARATE SIGN
 PERMIT APPLICATION.
  
  
 IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-01-15 Cont ID  
Sent By dpalmer Date 2004-01-15 Time 08:02 Rev Time 1.00
Received By dpalmer Date 2004-01-15 Time 07:41 Sent To  
Notes
2004-01-15 00:00:00************ UNSAT *****************
  
 1)NOTE: PLEASE SEE 700.12E FOR CIRCUIT-
 -ING EM/EXT LTS.
  
 2)NOTE: PLEASE SEE 220.12A FOR MIN LOAD
 REQUIRED FOR SHOW WINDOW(S). PLEASE SEE
 THAT PANEL IS ONLY SHOWING ONE CIRCUIT.
 200VA PER LINEAR FT.
  
 3)NOTE: PLANS MENTION TO PLACE RECEPTS
 ABOVE CEILING FOR "PLUG-IN" SIGNAGE.
 RECEPTS ARE NOT PERMITTED TO BE ABOVE
 THE DROP CEILING. CORDS MUST BE VISABLE
 FOR ITS ENTIRE LENGTH. NEC 410
  
 4)NOTE: PLEASE SEE OCP SHOWN FOR AHU.
 SHOWS 60A OCP FOR 5KW HEAT. PLEASE
 VERIFY OCP, MIN IS 125% 424.3B AND MAX
 TYP IS 150%.
  
 5)NOTE: PLEASE SEE 210.8B3 FOR ALL
 RECEPTS IN KITCEHN AREA TO BE GFI.
 PANEL SCHEDULE DOES NOT INDICATE THIS.
  
 6)NOTE: PLEASE VERIFY THREE LOCATIONS
 FOR CIRCUIT A-17?
  
 7)NOTE: PLEASE ALSO SEE OCP FOR FOR CU
 SHOWN AT 60A'S.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-12-23 Cont ID  
Sent By dpalmer Date 2003-12-23 Time 16:41 Rev Time 0.33
Received By dpalmer Date 2003-12-23 Time 16:41 Sent To  
Notes
2003-12-23 00:00:00*************** UNSAT *************
  
 1)NOTE: PLANS ARE REQ'D TO BE SIGNED,
 DATED AND SEALED BY THE ENGINEER OF
 RECORD. 471.025
 PLEASE ALSO SEE THAT ALL SHEETS MUST
 CONTAIN A TITLE BLOCK AS SET FORTH UNDER
 FS 471 AND FAC 61G15-23.002
 PLEASE PROVIDE ALL LICENSE # 'S AS REQ'D
 UNDER THE ABOVE REFERENCED FS'S/FAC'S
 ALL SHEETS/ BOTH SETS.
  
 2)NOTE: PLEASE PROVIDE ALL CIRCUITING
 ON PLANS AND CORRELATE W/ SUBMITTED
 PANEL SCHEDULE(S).
 PLEASE ALSO SUBMIT SIZE OF EXISTING
 SERVICE AND LOAD CALCULATIONS. 215.5
 PLEASE SHOW ALL LOAD CALCS PER 220
 PLEASE ALSO SEE 700.12E
  
 3)NOTE: PLEASE SEE 210.62 FOR SHOW
 WINDOW RECEPT REQUIREMENTS. DIRECTLY
 ABOVE WINDOW.
  
 4)NOTE: PLEASE SEE 600.5A FOR SIGN
 CIRCUIT REQUIRED AT ENTRANCE.
  
 DUE TO PLANS NOT BEING COMPLETE AT THIS
 TIME, THERE MAY BE OTHER COMMENTS TO
 FOLLOW.
  
 PLEASE SEE ADMIN CODE 104 FOR CHANGE IN
 USE AND POSSIBLE WORK THAT MAY BE REQ'D
 TO BRING SPACE UP TO CODE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2004-02-20 Cont ID  
Sent By mcarsill Date 2004-02-20 Time 15:55 Rev Time 0.00
Received By mcarsill Date 2004-02-20 Time 15:55 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-01-16 Cont ID  
Sent By mcarsill Date 2004-01-16 Time 15:59 Rev Time 0.00
Received By mcarsill Date 2004-01-16 Time 15:59 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-12-18 Cont ID  
Sent By mcarsill Date 2003-12-18 Time 17:24 Rev Time 0.00
Received By mcarsill Date 2003-12-18 Time 17:24 Sent To  
Notes
2003-12-18 00:00:001) PLANS NOT SIGNED AND SEALED.
  
 2) FIRE SPRINKLER PLANS DO NOT REFLECT
 FIRE SPRINKLER PROTECTION IN THE
 BATHROOM. ALSO THE NEW FREEZER SHALL
 BE FIRE SPRINKLER PROTECTED.
  
 3) PLANS NEED TO INDICATE INTERIOR
 FINISH CLASSIFICATION INFORMATION
 FOR WALLS AND CEILINGS.
  
 4) PLEASE INDICATE FIRE EXTINGUISHER
 LOCATIONS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-02-11 Cont ID  
Sent By csiegber Date 2004-02-11 Time 10:51 Rev Time 0.00
Received By csiegber Date 2004-02-11 Time 10:51 Sent To  
Notes
2004-02-11 00:00:00TO COMM BD#27

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-01-14 Cont ID  
Sent By csiegber Date 2004-01-14 Time 10:03 Rev Time 0.00
Received By csiegber Date 2004-01-14 Time 10:03 Sent To  
Notes
2004-01-14 00:00:00TO COMM BD#2

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-01-26 Cont ID  
Sent By pkrauss Date 2004-01-26 Time 07:24 Rev Time 0.00
Received By pkrauss Date 2003-12-10 Time 16:48 Sent To  
Notes
2003-12-10 00:00:00TO COMM BD#18

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-01-26 Cont ID  
Sent By pkrauss Date 2004-01-26 Time 07:24 Rev Time 0.35
Received By pkrauss Date 2004-01-26 Time 07:22 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2003-12-29 Cont ID  
Sent By pkrauss Date 2003-12-29 Time 09:21 Rev Time 0.15
Received By pkrauss Date 2003-12-29 Time 09:14 Sent To  
Notes
2003-12-29 00:00:00NO MECHANICAL PLANS SUBMITTED FOR REIVEW
 PLEASE PROVIDE THE FOLLOWING INFORMATION
 WITH MECHANICAL PERMIT APPLICATION.
 1.OUTSIDE AIR CALCULATIONS PER 2001
 FBC(M) 403.3.
  
 2.EQUIPMENT SCHEDULE - INDICATE
 LOCATION OF CONDENSER UNITS SHOULD A
 SPLIT SYSTEM BE INSTALLED.
  
 3.PROVIDE MANUFACTURER SUBMITTAL DATA
 FOR THE FREEZER/REFRIGERATOR & DELI
 COOLER.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 4 Status P Date 2004-02-27 Cont ID  
Sent By kstevens Date 2004-02-27 Time 17:35 Rev Time 1.00
Received By kstevens Date 2004-02-27 Time 17:35 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2004-02-23 Cont ID  
Sent By kstevens Date 2004-02-23 Time 10:54 Rev Time 0.50
Received By kstevens Date 2004-02-23 Time 10:54 Sent To  
Notes
2004-02-23 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FLORIDA ADMIN. CODE
 FLORIDA STATUTES.
  
 COMMENTS FROM PREVIOUS REVIEWS HAVE NOT
 BEEN ADDRESSED: (12-22-03 & 1-24-04) -
 NUMBERS WILL BE THE SAME FOR CLAIRITY.
 2) CONTACT RODNEY COMPO, ENVIRONMENTAL
 COMPLIANCE, FOR GREASE INTERCEPTOR RE-
 QUIREMENTS. WASTE ORD. #2938-96 - (561)
 837-4074.
 6) SHT 24 FLOOR DRAINS ARE NOT APPROVED
 FOR INDIRECT WASTE. FLOOR SINKS ARE RE-
 QUIRED PER SECTION 802.3
 7) ALL SHEETS - THE DATE THAT THE SIGNA-
 TURE AND SEAL IS AFFEIXE AS PROVIDED
 HEREIN SHALL BE ENTERED ON SAID PLANS
 IMMEDIATELY UNDER THE SIGNATURE OF THE
 PROFESSIONAL ENGINEER. 61G15-23.002(1)
 AND FS 471.025.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2004-01-24 Cont ID  
Sent By kstevens Date 2004-01-24 Time 07:01 Rev Time 1.00
Received By kstevens Date 2004-01-24 Time 07:01 Sent To  
Notes
2004-01-24 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FLORIDA ADMIN. CODE
 FLORIDA STATUTES
  
 COMMENTS FROM PREVIOUS REVIEW HAVE NOT
 BEEN ADDRESSED: (12-22-03) - NUMBERS
 WILL BE THE SAME FOR CLAIRITY.
 1) ROUTE PLANS TO THE DEPT. OF BUSINESS
 REGULATION HOTEL & RESTURANT DIVISION
 FOR REVIEW PRIOR TO RESUMBITTING TO THE
 CITY FOR REVIEW. (954) 958-5520. SECTION
 101.4.7 - (PLANS MUST BE STAMPED AND
 COPIES OF THE SPECIFICATION SHEETS ATT-
 ACHED TO PLANS).
 2) CONTACT RODNEY COMPO, ENVIRONMENTAL
 COMPLIANCE, FOR GREASE INTERCEPTOR RE-
 QUIREMENTS. WASTE ORD #2938-96- (561)
 837-4074.
 5) SHT 08 SANT. RISER DIAGRAM DOES NOT
 MEET CODE REQUIREMENTS. A TRAP IS REQ-
 UIRED FOR THE MOP SINK AND BOTH FLOOR
 SINKS. 1002.1
 6) SHT 24 FLOOR DRAINS ARE NOT APPROVED
 FOR INDIRECT WASTE. FLOOR SINKS ARE RE-
 QUIRED PER SECTION 802.3
 7) ALL SHEETS - THE DATE THAT THE SIGNA-
 TURE AND SEAL IS AFFIXED AS PROVIDED
 HEREIN SHALL BE ENTERED ON SAID PLANS
 IMMEDIATELY UNDER THE SIGNATURE OF THE
 PROFESSIONAL ENGINEER. 61G15-23.002(1)
 AND FS 471.025.
 NEW COMMENT*******
 1B SEE ATTACHED SHEET CONCERNING FLORIDA
 STATUTE 533.80(2)(B).
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-12-22 Cont ID  
Sent By kstevens Date 2003-12-22 Time 08:19 Rev Time 1.00
Received By kstevens Date 2003-12-19 Time 18:54 Sent To  
Notes
2003-12-22 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLA. ADMIN. CODE
 FLA. STATUTES
  
 1) ROUTE PLANS TO THE DEPT. OF BUSINESS
 REGULATION HOTEL & RESTURANT DIVISION
 FOR REVIEW PRIOR TO RESUBMITTING TO THE
 CITY FOR REVIEW. (954) 958-5520
 SECTION 101.4.7
 2) CONTACT RODNEY COMPO, ENVIRONMENTAL
 COMPLIANCE, INDUSTRIAL PRETREATMENT FOR
 GREASE INTECEPTOR REQUIREMENTS. WASTE
 ORD. 2938-96. (561) 837-4074
 3) SHT 04 EQUIPMENT LEGEND #15 NOT LOCA-
 TED ON FLOOR PLAN. PLEASE CLAIRFY. SEC.
 104.2.1
 4) WATER FILTER SHALL COMPLY WITH NSF
 STANDARDS. SUBMIT MANUF. SPECIFICATION
 SHEET.SECTION 303.4
 5) SHT 08 SANT. RISER DIAGRAM DOES NOT
 MEET CODE REQUIREMENTS. A TRAP IS REQ-
 UIRED FOR THE MOP SINK AND BOTH FLOOR
 SINKS. 1002.1
 6) SHT 24 FLOOR SINKS ARE NOT APPROVED
 FOR INDIRECT WASTE. FLOOR SINKS ARE RE-
 QUIRED PER SECTION 802.3
 7) ALL SHEETS - THE DATE THAT THE SIGNA-
 TURE AND SEAL IS AFFIXED AS PROVIDED
 HEREIN SHALL BE ENTERED ON SAID PLANS
 IMMEDIATELY UNDER THE SIGNATURE OF THE
 PROFESSIONAL ENGINEER. 61G15-23.002(1)
 FS 471.025.
 8) ALL SHEETS - ENGINEERS SHALL LEGIBLY
 INDICATE THEIR NAME, ADDRESS AND LICENSE
 NUMBER ON EACH SHEET. IF PRACTICING
 THROUGH A DULY AUTHORIZED ENGINEERING
 BUSINESS, THE NAME, ADDRESS, AND CERTIF-
 ICATE OF AUTHORIZATION NUMBER OF THE
 ENGINEERING BUSINESS IS REQUIRED ON EACH
 SHEET. 61G15-23.002(2) - FS 471.025
 9) SHT 04 SHOW CLEAR FLOOR SPACE AND
 TURNING AREA IN ACCESSIBLE TOILET ROOM.
 SECTION 11-4.22.3
 10) RPZ BACKFLOW REQUIRED ON WATER SERV-
 ICE. SECTION 608.13.2
 11) THERMAL EXPANSION CONTROL REQUIRED
 PER 607.3.2.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]