| Plan Review Stops For Permit 03120564 |
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2003-12-10 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2003-12-10 |
Time |
16:23 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2003-12-10 |
Time |
16:23 |
Sent To |
M |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2003-12-16 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2003-12-10 |
Time |
16:23 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
2003-12-16 |
Time |
11:33 |
Sent To |
|
|
| Notes |
| 2003-12-16 00:00:00 | PROVISO: | | | PLANS DO NOT INDICATE THE FIRE RATING OF | | | THE WALL.SHOULD WALL CARRY A FIRE | | | RATING, PROVIDE FIRE DAMPERS IN | | | ACCORDANCE WTIH 2001 FBC(M) 607.1.2, | | | | | | TRANSFER GRILLE SHALL COMPLY WITH | | | REVISION TO THE 2001 FBC(M) 601.4 | | | EFFECTIVE JUNE 30, 2003: | | | RETURN SHALL USE 50 SQ INCHES OF GRILLE | | | AREA TO 100 CFM OF SUPPLY AIR. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
|