Plan Review Details - Permit 03120564
Plan Review Stops For Permit 03120564
Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-12-10 Cont ID  
Sent By csiegber Date 2003-12-10 Time 16:23 Rev Time 0.00
Received By csiegber Date 2003-12-10 Time 16:23 Sent To M
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-12-16 Cont ID  
Sent By csiegber Date 2003-12-10 Time 16:23 Rev Time 0.35
Received By pkrauss Date 2003-12-16 Time 11:33 Sent To  
Notes
2003-12-16 00:00:00PROVISO:
 PLANS DO NOT INDICATE THE FIRE RATING OF
 THE WALL.SHOULD WALL CARRY A FIRE
 RATING, PROVIDE FIRE DAMPERS IN
 ACCORDANCE WTIH 2001 FBC(M) 607.1.2,
  
 TRANSFER GRILLE SHALL COMPLY WITH
 REVISION TO THE 2001 FBC(M) 601.4
 EFFECTIVE JUNE 30, 2003:
 RETURN SHALL USE 50 SQ INCHES OF GRILLE
 AREA TO 100 CFM OF SUPPLY AIR.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.