Plan Review Details - Permit 03120536
Plan Review Stops For Permit 03120536
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2004-11-03 Cont ID  
Sent By rmcdouga Date 2004-11-03 Time 13:59 Rev Time 0.00
Received By rmcdouga Date 2004-11-03 Time 13:59 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2004-10-20 Cont ID  
Sent By mmclean Date 2004-10-20 Time 16:22 Rev Time 0.00
Received By rmcdouga Date 2004-10-20 Time 14:29 Sent To  
Notes
2004-10-20 00:00:00DENIED
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) THE OWNER/AGENT IS REQUIRED TO SIGN
 THE ENERGY CALC. FORMS.
  
 4) SUBMIT PRODUCT APPROVALS FOR THE
 OUTSWING ENTRY AND GARAGE DOORS. THE
 PRODUCT APPROVAL THAT WAS SUBMITTED IS
 FOR INSWING DOORS.
  
 5) SUBMIT PRODUCT APPROVALS FOR THE
 DOUBLE OUTSWING GLAZED FRENCH DOORS AT
 THE FAMILY ROOM.
  
 6)THE PRODUCT APPROVAL DRAWING SUBMITTED
 FOR THE 9'X 7' OVERHEAD GARAGE DOOR HAS
 A NEGATIVE DESIGN PRESSURE OF -36.2 PSF
 AND THE PLANS SPECIFY A NEGATIVE OF
 -39.8 PSF. SUBMIT DRAWINGS WITH DESIGN
 PRESSURES EQUAL TO OR GREATER THAN THE
 PRESSURES SPECIFIED ON PLANS.
  
 7) SUBMIT A KEY PLAN AND INSTALLATION
 SCHEDULE FOR THE STORM PANELS. SPECIFY
 THE TYPE OF MOUNT, ANCHOR TYPE AND
 SPACING. THIS IS REQUIRED TO BE
 SUBMITTED AT TIME OF PERMIT OR A
 SEPARATE PERMIT AND FEES WILL BE
 REQUIRED.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-01-23 Cont ID  
Sent By kstevens Date 2004-10-15 Time 18:22 Rev Time 1.00
Received By rmcdouga Date 2004-01-23 Time 09:36 Sent To  
Notes
2004-01-23 00:00:00DENIED
  
 1) COMMENTS FROM FIRST REVIEW HAVE NOT
 BEEN ADDRESSED. PLEASE MAKE CORRECTIONS
 AND SUBMIT REQUESTED ITEMS.
 NOTE: IN ORDER TO EXPEDIATE PLAN REVIEW
 PLEASE SUBMIT THE OLD PLAN SHEETS WHEN
 REVISED PLANS ARE RESUBMITTED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-01-14 Cont ID  
Sent By dpalmer Date 2004-01-21 Time 16:59 Rev Time 2.00
Received By rmcdouga Date 2004-01-14 Time 09:37 Sent To  
Notes
2004-01-14 00:00:00DENIED
  
 1) PROVIDE COPY OF PAPERWORK FOR LOT
 SUBDIVISION APPROVED BY CITY ZONING
 DEPARTMENT AND NEW PCN FROM PALM BEACH
 COUNTY.
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 4) REVISE THE TYPE OF CONSTRUCTION FROM
 TYPE V TO TYPE VI. BASED ON FBC TABLE
 600, THE PERCENT OF WALL ALLOWED AS
 OPENINGS IS EXCEEDED AND THE EXTERIOR
 WALLS WOULD HAVE TO HAVE A 2 HOUR FIRE
 RATING IF IT TYPE V UNPROTECTED
 CONSTRUCTION.
  
 5) THE MAXIMUM PRESSURES FOR OPENINGS
 LISTED ON SHEET 1 ARE INCORRECT. SEE FBC
 TABLE 1606.2B, WALL ZONE 5, 140MPH WIND
 SPEED AND 10 SQFT EFFECTIVE WIND AREA.
 FOR GARAGE DOOR SEE FBC TABLE 1606.2E
 FOR A 9'X7' DOOR AND ROOF ANGLE GREATER
 THAN 10 DEGREES.
  
 6) DETAIL 10 ON SHEET 3 FOR THE TIE BEAM
 DETAIL SPECIFIES ONE #5 TOP AND BOTTOM,
 BUT THE DRAWING SHOWS 2. PLEASE CORRECT.
  
 7) SPECIFY THE SPACING OF THE WEDGE
 ANCHORS FOR THE GARAGE DOOR BUCKS IN THE
 DETAIL ON SHEET 5. THE DIAMETERS OF THE
 WEDGE ANCHORS ARE GIVEN AS 1/2" AND 3/8"
 PLEASE INDICATE WHICH ONE IS CORRECT.
  
 8) PROVIDE A BUCK DETAIL FOR THE SIDE
 SWING DOORS.
  
 9) STRUCTURAL NOTE #11 ON SHEET 5 CALLS
 FOR THE ROOF SHEATHING TO BE NAILED WITH
 10D NAILS WHICH CONFLICTS WITH THE OTHER
 NOTES REQUIRING 8D NAILS. PLEASE CORRECT
  
 10) THE OWNER/AGENT IS REQUIRED TO SIGN
 AND DATE THE ENERGY CALC. FORM.
  
 11) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
 SUBMIT FOR ALL WINDOWS, DOORS, ROOFING,
 STORM PANELS AND TRUSS CONNECTORS.
  
 12) SUBMIT THE DRAWINGS FOR THE SINGLE
 HUNG WINDOWS WHICH ARE MISSING FROM THE
 PRODUCT APPROVAL.
  
 13) SUBMIT PRODUCT APPROVALS FOR THE
 SINGLE OUTSWING DOORS AND DOUBLE
 OUTSWING GLAZED FRENCH DOORS.
  
 14) SUBMIT A KEY PLAN AND INSTALLATION
 SCHEDULE FOR THE STORM PANELS. INDICATE
 THE TYPE OF MOUNT, TYPE OF ANCHORS AND
 ANCHOR SPACING. THIS INFORMATION IS
 REQUIRED AT TIME OF APPLICATION OR A
 SEPARATE PERMIT AND FEE WILL BE REQUIRED
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2006-02-22 Cont ID  
Sent By dpalmer Date 2006-02-22 Time 18:50 Rev Time 0.00
Received By dpalmer Date 2006-02-22 Time 18:50 Sent To PC
Notes
2006-02-22 00:00:00REVISED RISER OK, STAMPED RISER.
  
 SUBMITTED REVISED PANEL SCHEDULE AND
 LOAD CALCS RETURNED TO CONTRACTOR, CODE
 COMMENTS NOT APPLIED TO THIS.

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2006-01-25 Cont ID  
Sent By dpalmer Date 2006-01-25 Time 16:00 Rev Time 0.00
Received By dpalmer Date 2006-01-25 Time 16:00 Sent To PC
Notes
2006-01-25 00:00:00**********UNSAT *********
  
 1)NOTE: PLEASE SEE ADDRESSING NEEDS TO
 BE CORRECTED AS OUR SYSTEM IS SHOWING
 414 MADDOCK, THE PLANS IN FILE INDICATE
 414 ALSO, HOWEVER LTR IN FILE MENTIONS
 410 AND REV COVER SHEET INDICATES 408.
 PLEASE KNOW, ALL PLANS ON FILE CONTAIN
 414 IN THE TITLE BLOCK WHERE FAC
 61G15-23.002, 61G1-16.004 REQUIRES THE
 CORRECT ADDRESS FOR PROJECT TO BE ON THE
 TITLE BLOCKS FOR JOB.
  
 2)NOTE: PLEASE SEE RISER DIAGRAM
 INDICATES THE INSIDE PANEL (GARAGE)
 BEING FED BACK THROUGH THE METER CAN
 SHOWING LINE AND LOAD IN THE METER.
 PLEASE SEE THIS IS NOT PERMITTED.250.6
 ETC .
  
 3)NOTE: PLEASE SEE SERVICE IS SHOWING A
 MCB PANEL LOCATED OUTSIDE , HOWEVER IT
 IS HAS COME TO THE ATTENTION OF THIS
 OFFICE THAT THERE IS NO PANEL LOCATED
 OUTSIDE , AND ONLY A MAIN DISCONNECT?
 PLEAS CONFIRM AND REVISE ACCORDINGLY.
  
 4)NOTE: PLEASE PROVIDE REVISED PANEL
 SCHEDULE AS, SERVICE IS NOW SHOWN BEING
 DOWNGRADED TO 150A'[S WHEN ORIG PLANS
 CALLED FOR 200A'S, PLEASE PROVIDE ANY
 UPDATED CHANGES IN LOADS OR CIRCUITING.
 215.5
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW AND IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-09-23 Cont ID  
Sent By dpalmer Date 2004-09-23 Time 13:47 Rev Time 0.75
Received By dpalmer Date 2004-09-23 Time 13:46 Sent To P
Notes
2004-09-23 00:00:00OWES RE-SUB FEE, THIS IS THIRD REVIEW.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-01-21 Cont ID  
Sent By csiegber Date 2004-09-20 Time 07:30 Rev Time 0.25
Received By dpalmer Date 2004-01-21 Time 16:59 Sent To B
Notes
2004-01-21 00:00:00************** UNSAT ****************
  
 1)NOTE: PLEASE SEE THAT NO NOTES WERE
 ADDRESSED FROM THE ORIGINAL REVIEW.
 SAME PLANS CAME BACK IN W/OUT ANY CHANGE
 -S???
  
 PLEASE SEE COPY OF FS 553.80 (2)(B)
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-12-23 Cont ID  
Sent By csiegber Date 2004-01-20 Time 10:07 Rev Time 0.50
Received By dpalmer Date 2003-12-23 Time 07:00 Sent To M
Notes
2003-12-23 00:00:00*************** UNSAT ************
  
 1)NOTE: PLEASE PROVIDE AIC RATING FOR
 MAIN/ PANEL. 110.9 MAINS/PANELS/BRKRS
 ARE ALL TO BE RATED FOR THE AVAILABLE
 FAULT CURRENT.
  
 2)NOTE: PLEASE SEE NOTES ABOVE RISER
 DIAGRAM. PLEASE SEE NEC 680.22A5 FOR
 GFI'S AROUND POOL AREA. 20' NOT 15'
 PLEASE ALSO SEE 210.8A6 FOR GFI PROTECT-
 ION FOR RECEPTS SERVING KITCHEN COUNTER-
 SPACE IN KITCHENS. 6' RULE CHANGED
  
 3)NOTE: PLEASE SEE THAT A GARAGE DOOR
 OPENER CIRCUIT ON PANEL SCHEDULE AND
 LOAD, HOWEVER PLANS DO NOT SHOW/INDICATE
 THIS RECEPT IN GARAGE.
  
 4)NOTE: PLEASE SEE 210.52 FOR MISSING
 RECEPT IN BEDROOM?
  
 5)NOTE: PLEASE PROVIDE ROOM DESIGNATION
 ON PLANS.
  
 6)NOTE: PLEASE SEE 210.52C3 FOR MISSING
 RECEPT AT PENINSULAR.
  
 7)NOTE: PLEASE LIST THE REQUIRED ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE PER 210.12. PLEASE ALSO SEE
 THE 2002 NEC AS THIS HAS CHANGED FROM
 THE 1999 NEC
  
 8)NOTE: THIS IS ONLY A NOTE: PLEASE SEE
 THAT "PHONE" IS ONLY SHOWN IN KITCHEN
 AND ONE BEDROOM. PLEASE SHOW ALL
 LOCATIONS OF LV AT THIS TIME. IF NOT
 THNE REVISED PLANS WOULD HAVE TO BE
 SUBMITTED AT A LATER DATE. THIS IS JUST
 A NOTE; SPEAKER WIRING ETC.
  
 9)NOTE: PLEASE SEE BOTH SMALL BEDROOMS
 SHOW A J-BOX IN CEILING W/ NO MEANS
 OF CONTROL? THIS IS ALSO JUST A NOTE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-02-17 Cont ID  
Sent By adarroug Date 2006-02-17 Time 11:30 Rev Time 0.00
Received By adarroug Date 2006-02-17 Time 11:30 Sent To E
Notes
2006-02-17 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-01-22 Cont ID  
Sent By adarroug Date 2006-01-22 Time 12:19 Rev Time 0.00
Received By adarroug Date 2006-01-22 Time 12:19 Sent To E
Notes
2006-01-22 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-11-01 Cont ID  
Sent By csiegber Date 2004-11-01 Time 12:13 Rev Time 0.00
Received By csiegber Date 2004-11-01 Time 12:13 Sent To B
Notes
2004-11-01 00:00:00TO RM DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-09-20 Cont ID  
Sent By csiegber Date 2004-09-20 Time 07:30 Rev Time 0.00
Received By csiegber Date 2004-09-20 Time 07:30 Sent To E
Notes
2004-09-20 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-01-20 Cont ID  
Sent By csiegber Date 2004-01-20 Time 10:07 Rev Time 0.00
Received By csiegber Date 2004-01-20 Time 10:07 Sent To E
Notes
2004-01-20 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-01-15 Cont ID  
Sent By mmclean Date 2004-01-16 Time 14:27 Rev Time 0.00
Received By csiegber Date 2004-01-15 Time 16:28 Sent To Z
Notes
2004-01-15 00:00:00RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-01-14 Cont ID  
Sent By mmclean Date 2004-01-14 Time 11:23 Rev Time 0.00
Received By rmcdouga Date 2004-11-03 Time 14:08 Sent To  
Notes
2003-12-16 00:00:0012/10/03TO Z
 TO SFD RACK/E

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2003-12-30 Cont ID  
Sent By dpalmer Date 2003-12-23 Time 07:04 Rev Time 0.25
Received By hmoser Date 2003-12-30 Time 18:41 Sent To P
Notes
2003-12-30 00:00:00NO PLANS

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-10-15 Cont ID  
Sent By kstevens Date 2004-10-15 Time 18:22 Rev Time 0.25
Received By kstevens Date 2004-10-15 Time 18:22 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2004-01-03 Cont ID  
Sent By dpalmer Date 2004-09-23 Time 13:47 Rev Time 0.25
Received By jleech Date 2004-01-03 Time 06:13 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2004-03-12 Cont ID  
Sent By mmclean Date 2004-10-20 Time 16:22 Rev Time 0.00
Received By mmclean Date 2004-03-12 Time 16:21 Sent To B
Notes
2004-10-20 00:00:00VARIANCE APPROVED ON 3/12/04 CASE# 3102
 BY JOHN ROACH, PLANNER 822/1448 MM

Review Stop Z ZONING
Rev No 2 Status N Date 2004-01-16 Cont ID  
Sent By mmclean Date 2004-01-16 Time 14:26 Rev Time 0.00
Received By mmclean Date 2004-01-16 Time 14:26 Sent To I
Notes
2004-01-16 00:00:00OK TO PASS ON TO BLDG PER SHIRLEY GRAHAM

Review Stop Z ZONING
Rev No 1 Status F Date 2004-01-14 Cont ID  
Sent By csiegber Date 2004-01-15 Time 16:28 Rev Time 0.00
Received By mmclean Date 2004-01-14 Time 11:51 Sent To  
Notes
2004-01-14 00:00:00DENIED, NEED TO APPLY FOR A VARIANCE OR
 SHOW PROOF OF SUBDIVSION CALL CONTR FILE
 A FOR PICK UP MM