| Plan Review Stops For Permit 03120501 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2004-01-11 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2004-01-11 |
Time |
12:33 |
Rev Time |
1.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2004-01-11 00:00:00 | | | | PROVISO | | | ------- | | | | | | EXITING PLAN NEEDS TO BE CORRECTED. SEE | | | SH. E-1, IDENTIFY THE REQUIRED EXIT | | | DOOR IN ROOM 104. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
F |
Date |
2004-02-24 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-02-24 |
Time |
07:54 |
Rev Time |
0.33 |
| Received By |
dpalmer |
Date |
2004-02-24 |
Time |
07:54 |
Sent To |
|
|
| Notes |
| 2004-02-24 00:00:00 | ************ UNSAT ***************** | | | | | | PLEASE SEE PREVIOUS REVIEW NOTES**** | | | PLEASE SEE PROVSIO NOTES ATTACHED. | | | | | | 1)NOTE: PLEASE SEE NOW A TITLE BLOCK | | | HAS BEEN ADDED, HOWEVER IT IS MISSING | | | INFORMATION REQUIRED UNDER FAC 61G1-16. | | | 004. PLEASE ALSO SEE FS 481.219. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2004-02-12 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-02-20 |
Time |
16:06 |
Rev Time |
0.33 |
| Received By |
dpalmer |
Date |
2004-02-12 |
Time |
07:43 |
Sent To |
|
|
| Notes |
| 2004-02-12 00:00:00 | ************* UNSAT **************** | | | | | | 1)NOTE: PLEASE SEE ORIGINAL PROVSIO. | | | I HAVE ATTACHED A COPY TO THESE NOTES. | | | PLANS NEED TO BE REVISE PER COMMENTS. | | | | | | 2)NOTE: PLEASE SEE THAT ALL PAGES/PLANS | | | SUBMITTED THAT ARE REQ'D TO BE SIGNED, | | | DATED AND SEALED BY THE ARCH/ENG OF | | | RECORD, ARE ALSO REQ'D TO HAVE TITLE | | | BLOCK WITH ALL INFORMATION AS REQ'D | | | UNDER FAC 61G1-16.004. | | | | | | PLEASE SEE THAT THESE ARE CONSIDERED | | | REVISIONS TO PLANS AND FEES WILL BE DUE | | | AT TIME OF SUBMITTING REVISION. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2004-01-15 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-02-03 |
Time |
16:21 |
Rev Time |
0.50 |
| Received By |
dpalmer |
Date |
2004-01-15 |
Time |
07:02 |
Sent To |
|
|
| Notes |
| 2004-01-15 00:00:00 | ************ PROVSIO/ REVISION ******* | | | | | | 1)NOTE: PLEASE SHOW ALL NEW CIRCUITING | | | ON PLANS AND CORRELATE WITH A PANEL | | | SCHEDULE TO BE SUBMITTED. | | | | | | 2)NOTE: PLEASE ALSO INCLUDE WHAT APPEARS | | | TO BE A NEW A/C SYSTEM . PLEASE VERIFY | | | NEW OR EXISTING ROOF TOP RECEPT. | | | IF NEW A/C SYSTEM, PLEASE ALSO SUBMIT | | | LOAD CALCULATIONS ON PANELS. | | | | | | 3)NOTE: PLEASE SHOW ALL CIRCUITING FOR | | | EM/ EXT LTS PER 700.12E. | | | | | | PLEASE SUBMIT ALL OF THE ABOVE INFORMAT- | | | -ION FOR REVIEW BEFORE ANY ROUGH | | | ELECTRICAL INSPECTION IS CALLED IN. | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE DO | | | NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2003-12-23 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2003-12-23 |
Time |
13:02 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2003-12-19 |
Time |
13:04 |
Sent To |
|
|
| Notes |
| 2003-12-23 00:00:00 | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | NOTE: PLEASE NOTE THAT ALL PLANS | | | DRAWN BY AN ARCHITECT/ENGINEER CONTAIN- | | | ING A TITLE BLOCK, MUST BE SIGNED, DATED | | | AND SEALED BY THE ARCH/ENGINEER OF | | | RECORD. PER FS/FAC 481.221 & 471.025. | | | SEE MECHANICAL COMMENTS. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2004-01-15 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2004-01-15 |
Time |
16:27 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2004-01-15 |
Time |
16:27 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2003-12-18 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2003-12-18 |
Time |
17:20 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2003-12-18 |
Time |
17:20 |
Sent To |
|
|
| Notes |
| 2003-12-18 00:00:00 | 1) IT IS NOT CLEAR WHERE THE DIRECTIONAL | | | EXIT SIGNS ARE LEADING PERSONS TO | | | EXITS. PLEASE CLARIFY. SIGNS SEEM TO | | | DIRECT PERSONS INTO 118 BUT NO EXIT | | | DOORS ARE VISIBLE. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2004-02-20 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-02-20 |
Time |
.6:06 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-02-20 |
Time |
16:06 |
Sent To |
E |
|
| Notes |
| 2004-02-20 00:00:00 | TO DP DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2004-02-03 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-02-03 |
Time |
16:21 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-02-03 |
Time |
16:21 |
Sent To |
E |
|
| Notes |
| 2004-02-03 00:00:00 | TO DP DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2004-01-13 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-01-13 |
Time |
14:16 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-01-13 |
Time |
14:16 |
Sent To |
|
|
| Notes |
| 2004-01-13 00:00:00 | TO COMM BD#14 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2003-12-09 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2003-12-09 |
Time |
11:40 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2003-12-09 |
Time |
11:40 |
Sent To |
|
|
| Notes |
| 2003-12-09 00:00:00 | TO COMM BD#7 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2004-01-23 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2004-01-23 |
Time |
14:29 |
Rev Time |
0.33 |
| Received By |
pkrauss |
Date |
2004-01-23 |
Time |
14:29 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2003-12-23 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2003-12-23 |
Time |
10:35 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2003-12-23 |
Time |
10:32 |
Sent To |
|
|
| Notes |
| 2003-12-23 00:00:00 | DENIED: | | | PLEASE NOTE PER FS 481.221, SIGNATURE | | | SHALL BE AUTHENTIC AND NOT A "STAMP". | | | PLANS ARE OTHERWISE CODE COMPLIANT. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|