Plan Review Details - Permit 03120438
Plan Review Stops For Permit 03120438
Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2004-03-19 Cont ID  
Sent By alange Date 2004-03-19 Time 15:24 Rev Time 0.50
Received By alange Date 2004-03-19 Time 15:24 Sent To  
Notes
2004-03-19 00:00:00REVISION FOR PRIVACY WALL AND FRONT
 WALK

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2004-03-08 Cont ID  
Sent By csiegber Date 2004-03-19 Time 12:48 Rev Time 0.50
Received By alange Date 2004-03-08 Time 10:19 Sent To  
Notes
2004-03-08 00:00:00RECEIVED REVISION...OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2004-02-18 Cont ID  
Sent By csiegber Date 2004-03-05 Time 16:35 Rev Time 0.33
Received By alange Date 2004-02-18 Time 15:32 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2004-02-13 Cont ID  
Sent By csiegber Date 2004-02-18 Time 10:29 Rev Time 1.00
Received By alange Date 2004-02-13 Time 11:23 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2004-02-09 Cont ID  
Sent By csiegber Date 2004-02-11 Time 09:48 Rev Time 1.25
Received By alange Date 2004-02-09 Time 14:16 Sent To  
Notes
2004-02-09 00:00:00DENIED
 1.SUBMIT PRODUCT APPROVALS FOR NEW
 WINDOWS AND DOORS.
 2.SUBMIT SHUTTER PRODUCT APPROVALS IF
 YOU WANT THEM ON THIS PERMIT.
 3.ADJUST PERMIT VALUE TO REFLECT
 ADDITIONAL WORK BEING DONE INCLUDING
 WINDOWS AND DOORS NOW ON THIS PERMIT.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-01-26 Cont ID  
Sent By csiegber Date 2004-02-09 Time 10:54 Rev Time 1.00
Received By alange Date 2004-01-26 Time 08:46 Sent To  
Notes
2004-01-26 00:00:00PROVISO
 PRODUCT APPROVALS FOR WINDOW CLASSICS
 NOT ON FBC PRODUCT APPROVAL SITE.
 HAVE THE ATACHED SITE SPECIFIC PRODUCT
 APPROVAL FORM COMPLETED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-01-12 Cont ID  
Sent By pkrauss Date 2004-01-23 Time 09:05 Rev Time 2.50
Received By alange Date 2004-01-12 Time 14:51 Sent To  
Notes
2004-01-12 00:00:001.SUBMIT PRODUCT APPROVALS FOR DOORS,
 WINDOWS, GARAGE DOORS AND SHUTTERS.
 2.SUBMIT ENERGY CALCULATIONS
 3.BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 4.SMOKE DETECTORS REQUIRED PER
 FBC 2304.3.4
 5.ATTIC ACCESS SIZE TO COMPLY WITH
 FBC 2309.7.1
  
 ART LANGE
 BUILDING PLANS EXAMINER
 561-805-6672

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2004-07-28 Cont ID  
Sent By dpalmer Date 2004-07-28 Time 16:40 Rev Time 0.50
Received By dpalmer Date 2004-07-28 Time 16:29 Sent To  
Notes
2004-07-28 00:00:00REDLINED MISSING EQUIPMENT GROUNDING
 CONDUCTORS ON RISER. 250.122

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2004-07-16 Cont ID  
Sent By csiegber Date 2004-07-26 Time 11:11 Rev Time 0.75
Received By dpalmer Date 2004-07-16 Time 14:30 Sent To P
Notes
2004-07-16 00:00:00************** UNSAT *****************
  
 1)NOTE: PLEASE SEE ADDTIONAL SHEETS
 WHICH ARE SIGNED AND SEALED BY THE ARCH
 OF RECORD ARE REQUIRED TO HAVE TITLE
 BLOCK PER FAC 61G1-16.004
  
 2)NOTE: PLEASE CORRELATE A/C LOADS WITH
 AWG AND OCP. PLEASE SEE 424.3B
 PLEASE SEE 60A OCP W/ #8 AWG, 5KW W/ 60A
 OCP. ETC.
  
 3)NOTE: PLEASE SEE LOAD CALCUALTIONS,
 MUST MEET 220.31B.
 A/C LOADS DERARTED, THIS IS NOT PERMITT-
 ED.PLEASE ADJUST
  
 4)NOTE: PLEASE SEE ONLY ONE PANEL SCHEDU
 -LE WAS SUBMITTED.
  
 5)NOTE: PLEASE SEE MAIN PANEL ALSO SHOWS
 AN ADDITIONAL FEED OUT OF THE TOP OF
 PANEL??
  
 6)NOTE: PLEASE SEE 210.52 FOR MISSING
 RECEPTS ON PLANS.
  
 7)NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ON EACH LEVEL OF A MULTI-LEVEL DWELLING
 UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER:FBC 905.2, NFPA-72 8-1.4
 PLEASE SEE 2 MISSING AND REDLINED ON
 PLANS.
  
 8)NOTE:PLEASE SHOW LOCATION OF SERVICE,
 PLANS SHOWS OLD METER LOCATION BUT NOTH-
 -ING SHOWN FOR NEW.
  
 9)NOTE: PLEASE SEE ALL CONTINOUS LOADS
 ARE TO BE SHOWN AT 125%. PLEASE SEE
 POOL HEATER AND PUMP.
  
 PLEASE SEE ONE SET HAS SOME OF THESE
 ITEMS REDLINED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2004-04-18 Cont ID  
Sent By csiegber Date 2004-07-12 Time 09:03 Rev Time 0.33
Received By dpalmer Date 2004-04-18 Time 08:31 Sent To  
Notes
2004-04-18 00:00:00************* UNSAT **************
  
 1)NOTE: PLEASE SUBMIT REVISED ELECTRICAL
 SHEETS SHOWING NEW "REVISED" AND ELEC-
 -TRICAL WORK AS SHOWN ON ORIG ELECTRICAL
 PLANS SUBMITTED FOR SCOPE OF WORK.
 PLANS MUST BE REVISED/REPRINTED SIGNED,
 DATED AND SEALED BY THE ARCH OF RECORD
 PER FS 481.221, FAC 61G1-16.004, FBC
 104.2.1, 104.2.1.3 ETC.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-01-14 Cont ID  
Sent By csiegber Date 2004-04-12 Time 08:32 Rev Time 0.50
Received By btrobaug Date 2004-01-14 Time 18:04 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-12-17 Cont ID  
Sent By csiegber Date 2004-01-14 Time 16:20 Rev Time 1.00
Received By btrobaug Date 2003-12-17 Time 16:20 Sent To P
Notes
2003-12-17 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION,MAKE NECESSARY CHANGES TO
 PLANS AND RESUBMIT FOR REVIEW.
  
 1} PLEASE INDICATE THE SIZE OF THE
 EXISTING SERVICE.THE RISER STATES A 300
 AMP PANEL BUT THE FEED CONDUCTORS ARE
 RATED FOR 200 AMPS PER 310.15(B).
  
 2} PLEASE USE THE CALCULATION IN
 220.31(B), SHOW ENTIRE LOAD,EXISTING
 AND ADDITIONAL.
  
 3} PLEASE NOTE THE A/C LOAD MUST BE
 TAKEN AT 100%.(220.31(B)).
  
 4} NOTE #6 IS INCORRECT UNLESS THE
 CIRCUITS MENTIONED ARE ARC FAULT.SMOKE
 DETECTORS LOCATED IN BEDROOMS MUST
 COMPLY WITH 210.12 AND BE ARC FAULT
 PROTECTED.
  
 5} PLEASE SHOW ALL OUTLET SPACING
 TO MEET 2',6',12' RULE PER 210.52,
 IN ALL ADDED SPACES.
  
 6} PLEASE NOTE MISSING OUTLET FOR
 A/C EQUIPMENT PER 210.63.
  
 7} SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
 IN THE VICINITY OF BEDROOMS AND CLOSE
 PROXIMITY OF STAIRWAYS. 2-5.2.1.3
 3'FT FROM BATHS/KITCHENS.2-5.2.1.6
  
 8} PLEASE SHOW RECEPTACLES IN HALLWAYS
 TO COMPLY WITH 210.52(H).
  
 9} PLEASE NOTE FRONT AND REAR
 RECEPTS REQ`D PER 210.52E
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2004-07-26 Cont ID  
Sent By csiegber Date 2004-07-26 Time 11:11 Rev Time 0.00
Received By csiegber Date 2004-07-26 Time 11:11 Sent To E
Notes
2004-07-26 00:00:00TO DP DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2004-07-12 Cont ID  
Sent By csiegber Date 2004-07-12 Time 09:03 Rev Time 0.00
Received By csiegber Date 2004-07-12 Time 09:03 Sent To E
Notes
2004-07-12 00:00:00TO DP DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2004-04-12 Cont ID  
Sent By csiegber Date 2004-04-12 Time 08:32 Rev Time 0.00
Received By csiegber Date 2004-04-12 Time 08:32 Sent To E
Notes
2004-04-12 00:00:00TO BT DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2004-03-19 Cont ID  
Sent By csiegber Date 2004-03-19 Time 12:48 Rev Time 0.00
Received By csiegber Date 2004-03-19 Time 12:48 Sent To B
Notes
2004-03-19 00:00:00TO AL DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2004-03-05 Cont ID  
Sent By csiegber Date 2004-03-05 Time 16:35 Rev Time 0.00
Received By csiegber Date 2004-03-05 Time 16:35 Sent To B
Notes
2004-03-05 00:00:00TO AL DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2004-02-18 Cont ID  
Sent By csiegber Date 2004-02-18 Time 10:29 Rev Time 0.00
Received By csiegber Date 2004-02-18 Time 10:29 Sent To B
Notes
2004-02-18 00:00:00TO AL DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-02-11 Cont ID  
Sent By csiegber Date 2004-02-11 Time 09:48 Rev Time 0.00
Received By csiegber Date 2004-02-11 Time 09:48 Sent To B
Notes
2004-02-11 00:00:00TO AL DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-02-09 Cont ID  
Sent By csiegber Date 2004-02-09 Time 10:54 Rev Time 0.00
Received By csiegber Date 2004-02-09 Time 10:54 Sent To B
Notes
2004-02-09 00:00:00TO AL DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-01-14 Cont ID  
Sent By csiegber Date 2004-01-14 Time 16:20 Rev Time 0.00
Received By csiegber Date 2004-01-14 Time 16:20 Sent To E
Notes
2004-01-14 00:00:00TO BT DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-12-12 Cont ID  
Sent By csiegber Date 2003-12-12 Time 11:59 Rev Time 0.00
Received By csiegber Date 2003-12-12 Time 11:59 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-12-08 Cont ID  
Sent By mmclean Date 2003-12-12 Time 11:13 Rev Time 0.00
Received By csiegber Date 2003-12-08 Time 14:59 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-01-23 Cont ID  
Sent By pkrauss Date 2004-01-23 Time 08:15 Rev Time 0.45
Received By pkrauss Date 2004-01-23 Time 07:20 Sent To B
Notes
2004-01-23 00:00:00PROVISO:
 DUCT INSTALLED ON THE ROOF SHALL
 COMPLY WITH SMACNA SECTION V AND FBC
 CHAPTER 13 SUB SECTION 610.
  
 SEALED DRAWING FROM ENGINEER INDICATING
 METHOD FOR DUCT ATTACHMENT TO THE ROOF
 TO FOLLOW. (ENGINEER TO FAX DRAWING)

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-12-22 Cont ID  
Sent By kstevens Date 2004-01-20 Time 13:16 Rev Time 0.33
Received By pkrauss Date 2003-12-22 Time 14:34 Sent To B
Notes
2003-12-22 00:00:00DENIED:
 PLEASE PROVIDE THE FOLLOWING INFORMATION
 FOR REVIEW.
 1.ENERGY & MAUNAL J CALCULATIONS FOR
 THE ADDITIION.
  
 2.PROVIDE THE FOLLOWING EQUIPMENT
 INFORMATION:MAKE, MODEL, BTU'S OF THE
 AHU AND SEER OF THE CONDENSER UNIT.
  
 3.PLEASE PROVIDE THE DUCT/GRILLE SIZE,
 LAYOUT AND MATERIAL.PLEASE NOTE PER
 REVISION TO THE 2001 FBC(M) 601.4
 EFFECTIVE JUNE 30,2003, RETURN OR
 TRANSFER AIR REQUIRED FROM ROOMS
 SEPARATED BY A DOOR.SEE ATTACHED FOR
 SIZING REQUIREMENTS.
  
 4.AUXILIARY DRAIN PAN WITH OVERFLOW
 PROTECTION REQUIRED PER 2001 FBC(M)
 307.2.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-01-20 Cont ID  
Sent By dpalmer Date 2004-07-16 Time 14:59 Rev Time 0.25
Received By kstevens Date 2004-01-20 Time 13:15 Sent To M
Notes
2004-01-20 00:00:00PREVIOUSLY APPROVED. NO NEW SHEETS

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-12-18 Cont ID  
Sent By btrobaug Date 2004-01-14 Time 18:25 Rev Time 1.00
Received By kstevens Date 2003-12-18 Time 09:11 Sent To M
Notes
2003-12-18 00:00:00PASSED/PROVISO - W/C'S SHALL NOT BE
 DOUBLE TRAPPED

Review Stop Z ZONING
Rev No 1 Status P Date 2003-12-12 Cont ID  
Sent By alange Date 2004-03-19 Time 15:24 Rev Time 0.00
Received By mmclean Date 2003-12-11 Time 16:55 Sent To I
Notes
2003-12-12 00:00:00OK PER ERIC SCHNEIDER FOR THEM TO
 FLIP TO MEET SIDE SETBACKS. MM
2003-12-11 00:00:00DENIED, NEED TO MEET THE REQUIRED SIDE
 SETBACK OF A TOTAL 15FT. CALLED LEFT MSG
 MM